40
ICE CFA1120A-3360A & CGA3180A I&O Manual 03/2021 Rev.5
D. Heating Mode Check & Record Readings
Circuit 1
Circuit 2
(if applicable)
Room Temperature
________
________
Outside Temperature
________
________
Evap. Entering Air DB Temp
________
________
Evap. Entering Air WB Temp
________
________
Evap. Leaving Air DB Temp
________
________
Evap. Leaving Air WB Temp
________
________
Heater Contactor Amps (L1)
________
________
Heater Contactor Amps (L2)
________
________
Heater Contactor Amps (L3)
________
________
E. Cooling Mode Check & Record Refrigerant Pressures
Recheck voltage imbalance in cooling mode:
Measured Line to Line Volts L1&L2_______V.
L1&L3 ________V.
L2&L3______V.
(L1&L2 + L1&L3 + L2&L3)/3 = Avg. Voltage = _______________
Max. Deviation from avg. voltage = ______________volts
Voltage imbalance = (100 x Max. Deviation)/avg. Voltage = ___________%