Eubank EAA/EGA Wall Mount AC Installation & Operation Manual
03/2021 Rev.4
7
1.4
Air Flow, Weights and Filter Sizes
Complete electrical and performance specifications and dimensional drawings are in the Eubank Wall
Mount Air Conditioner Product Data Sheets.
Note:
Follow local codes and standards when designing duct runs to deliver the required airflow.
Minimize noise and excessive pressure drops caused by duct aspect ratio changes, bends, dampers and
outlet grilles in duct runs.
MODEL
0.10
0.15
0.20
0.25
0.30
0.40
0.50
EAA1020
800
785
770
725
680
600
EAA1024
800
785
770
725
680
600
500
EAA1030
1200
1150
1100
1050
1000
900
800
EAA1036
1290
1230
1170
1115
1060
1000
920
EAA1042
1500
1430
1360
1295
1230
1160
1070
EAA1060
1900
1850
1800
1700
1600
1500
1350
EGA1072
1900
1850
1800
1700
1600
1500
1350
Values in bold are the minimum air flow.
Air flow ratings of 208-230 volt units are at 230v. Air flow ratings of 460 volt units are at 460 volts. Operation of units at a voltage different from the rating point
will affect air flow
.
Table 1. CFM @ External Static Pressure (Wet Coil) (IWG)
MODEL
INCHES
MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING
EAA1020/1024
30 x 16 x 2
762 x 406 x 52
80138
1
8
EAA1030/1036/1042
36½ x 22 x 2 927 x 559 x 52
80162
1
8
EAA1048/1060
18 x 24 x 2
457 x 610 x 52
81257
2
8
EGA1072
18 x 30 x 2
457 x 762 x 52
93184
2
8
Table 2. Return Air Filter Sizes
MODEL
LBS
KG
Non-Economizer
EAA1020/1024
355
160
EAA1030/1036/1042
535
245
EAA1048/1060
625
284
EGA1072
680
309
With Economizer
EAA1020/1024
375
170
EAA1030/1036/1042
590
268
EAA1048/1060
640
291
EGA1072
740
336
Table 3. Shipping Weights for Eubank Wall Mount AC Units
1.5 General Operation
Model
Ventilation Configuration
Temperature Range
Non-Economizer
Standard ("N")
20ºF – 120ºF (-7ºC – 48.9ºC)
Desert Duty ("ND")
32ºF – 130ºF (-0ºC – 54ºC)
Extreme Duty ("NE"), 60 Hz Only
0ºF – 130ºF (-18ºC – 54ºC)
With Economizer
Standard ("CE")
-40ºF – 120ºF (-40ºC – 48.9ºC)
Desert Duty ("CD")
-40ºF – 130ºF (-40ºC – 54ºC)
Extreme Duty ("CE"), 60 Hz Only
-40ºF – 130ºF (-40ºC – 54ºC)
Table 4. Ambient Temperature Operating Range
Model
EAA1018A EAA1020A EAA1024A EAA1030A EAA1036A EAA1042A EAA1048A EAA1060A EGA1072A
A
A
A C D Z A C D Z A C D Z A C D Z A C D Z A C D Z A C D Z
w/o Hot Gas Reheat
65
85
85
90
105
123
128
125
150
160
w/Hot Gas Reheat
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Table 5. Refrigerant Charge (R410A, Ounces)