background image

  

 

IV.   OPERATION 

 

I. 

For Cooling (Refer to Figure 1, page 3). 

 

A. 

Turn the selector switch to the “LOW COOL” or “HIGH COOL” position. 

 
B. 

Rotate the thermostat (temperature control) to the position that is the most comfortable to you.  The 
thermostat will turn the compressor on when the temperature of the air entering the air conditioner rises 
a few degrees above the setting you have selected.  The temperature of the air entering continues to 
cycle the compressor on and off in the above mentioned fashion until the selector switch is turned to 
another mode of operation. 

 
C. 

Position the end louvers to the desired amount of discharge air flow. 

 
 

Note:  The fan operation is constant, only the compressor cycles on the thermostat. 

 

II. 

Operation During Cooler Nights (Cooling Operation). 

 

It is important, when the outdoor temperature drops in the evening or during the night to below 75°F (24°C), 
that the thermostat (temperature control) be set at a midpoint between “Warmer” and “Cooler”.  If the setting is 
at “Cooler”, the evaporator coil may become iced-up and greatly reduce the amount of air delivery.  During the 
day when the temperatures have risen above 75°F (24°C), reset the thermostat switch to the desired setting. 
 

Note: 

Should icing occur, it is necessary to let the cooling (evaporator) coil defrost before normal cooling 

operation is resumed.  During this time, operate the unit in the “HIGH FAN” position with the system at 
maximum air flow.  When increased or full air flow is observed, the cooling coil should be clear of ice. 
 

III. 

Short Cycling 

 

When an air conditioner is in operation, its compressor circulates refrigerant under high pressure.  Once off, it 
will take two to three minutes for this high pressure to equalize. 
 
The air conditioning compressor is unable to start against high pressure.  Therefore, once the air conditioner is 
turned off, it is important to leave it off for two to three minutes before restarting. 
 
Short cycling the compressor (or starting it before pressures have equalized), will in some instances, kick the 
circuit breaker or overload. 
 

IV. 

Heat Operation 

 
Turn the selector switch to the “LOW HEAT” position.  At “LOW HEAT”, the fan operates on low speed with 
air temperature rise at maximum. 
 
Rotate the thermostat (temperature control) switch to the position that is the most comfortable to you.  The 
thermostat will turn the heater on when the temperature of the air entering the air conditioning unit drops below 
this setting a few degrees, and automatically turns off when the temperature of the air entering the air 
conditioner rises a few degrees above this setting.  The heater will continue to cycle on and off in this fashion 
until the selector switch is turned to another mode of operation. 
 

-4- 

“More information https://www.caravansplus.com.au"

Summary of Contents for Coleman-Mach 4735 Series

Page 1: ...IR CONDITIONER Service Contact Coast to Coast RV Services Pty Ltd PO BOX 415 REGENTS PARK DC NSW 2143 Australia Tel 61 2 9645 7600 technical coastrv com au Coleman is a registered trademark of The Coleman Company Inc used under license Mach is a registered trademark More information https www caravansplus com au ...

Page 2: ...umber of the unit Both numbers can be found on the data label on the unit Model No ________________________ Serial No ________________________ II OPERATING GUIDELINES The air conditioner is designed to provide cooling and dehumidification An electric coil provides heating in cool weather Note The electric heating assembly is intended to take the chill out of the indoor air when the air is a few de...

Page 3: ...ons 9400 ceiling assemblies will have the knobs at the bottom of the ceiling assembly See Figure 2 The Operation section explains the operational characteristics of each mode of operation B The Thermostat temperature control In the cooling mode the thermostat regulates the ON and OFF temperature setting at which the compressor will operate The thermostat also controls the ON and OFF temperature se...

Page 4: ...efrost before normal cooling operation is resumed During this time operate the unit in the HIGH FAN position with the system at maximum air flow When increased or full air flow is observed the cooling coil should be clear of ice III Short Cycling When an air conditioner is in operation its compressor circulates refrigerant under high pressure Once off it will take two to three minutes for this hig...

Page 5: ...of the biggest advantages to your new Coleman Mach air conditioner is that the maintenance needed to keep the unit in good care is minimal In fact about the only thing you the owner must take care of is the cleaning and replacement of the filters Filters are made from long life non allergenic natural fibers or foam which can be cleaned and reused and which completely filter the circulated air when...

Page 6: ...s to trip the circuit breakers have an electrician check the starting amperage and running amperage on the unit If the circuit breakers continue to trip and the electrical consumption is found to be normal it will require the replacement of the faulty circuit breaker If all electrical power to the air conditioner is normal but neither the fan nor the compressor will operate the connector plug loca...

Page 7: ...ess the filters pull on the tabs on the return air grilles The filters should be washed in warm water or vacuumed clean and replaced The filters should be inspected every 2 weeks and cleaned as required Note If the unit is operated in a dusty environment the filters should be inspected and cleaned more frequently FIGURE 2 7 Tabs to access filter Tabs to access filter More information https www car...

Page 8: ...me type rather than being repaired Refurbished parts may be used to repair the goods 3 WHAT THE CLIENT MUST DO TO CLAIM THE WARRANTY 3 1 To claim the benefit of the warranty the Client will need to sequentially i first contact the Supplier and ii present the defective Goods to the Supplier for inspection including inspection for defective workmanship or otherwise provide evidence of the claimed De...

Page 9: ...hould be referred to the installer The Goods must be installed in accordance with the Manufacturer s instructions and any relevant legislation or code 6 3 This warranty covers the Client only and it is not transferrable if the Goods are sold by the Client during the warranty period 7 WARRANTY EXCLUSIONS 7 1 This warranty will not apply where i the Goods have been improperly modified or repaired or...

Page 10: ...ox Yes No Receipt No Description of defects Give as much detail as possible Use a separate page if required Date of purchase services provided I hereby declare that the information provided above is true and correct and to the best of my knowledge and belief and I have complied with all the conditions of the warranty Signed Name please print Dated Please note the issue or completion of this form b...

Page 11: ...RV Products Division Airxcel Inc RV Products Division P O Box 4020 Wichita KS 67204 1976 671 Rev 1 3 15 PP More information https www caravansplus com au ...

Reviews: