background image

AUTO GEN CHECKOUT 

 

Thermostat should be calling for Heat or Cool. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

-12- 

12 VDC On Either Yellow Or Gray Wire To 

Blue On Wall Thermostat Plug At Unit 

YES 

12 VDC At 4 Pin Plug 

Red (+) & Black (-) 

NO 

Check All Wiring And Connections From Indoor 

Section To Thermostat.  Repair As Needed.  If 

All Are Good, Replace Thermostat. 

YES 

Refer To APU Service Guide 

NO 

Check All Wiring And 

Connections To P.C. Board.    

If Connections Are Good, 

Replace P.C. Board. 

Summary of Contents for 46101-8114

Page 1: ...Associated Products Division SERVICE MANUAL FOR 46101 8114 46103 8114 BACKWALL AIR CONDITIONING SYSTEM...

Page 2: ...ERE PERSONAL INJURY DEATH OR EQUIPMENT DAMAGE DUE TO ELECTRICAL SHOCK ALWAYS BE SURE THE POWER SUPPLY TO THE APPLIANCE IS DISCONNECTED BEFORE DOING ANY WORK ON THE APPLIANCE THIS CAN NORMALLY BE ACCOM...

Page 3: ...3 UNIT SPECIFICATIONS AND IDENTIFICATION 3...

Page 4: ...4 UNIT DEPICTION FIGURES 4...

Page 5: ...pre charged unit designed to hang vertically on the back wall of a sleeper cab It is designed to be easily accessed for service and can be removed quickly for service or replacement All the electrica...

Page 6: ...6...

Page 7: ...7...

Page 8: ...ndoor Blower High NO Refer To Indoor Blower High Checkout 15 Second Time Delay Compressor Outdoor Fan NO Refer To Outdoor Fan Checkout NO Refer To Compressor Checkout Thermostat Call Generator Start O...

Page 9: ...ward on any chart until all preceding steps have been confirmed good Do Not start in the middle of any chart without knowing everything previous upward on the chart is OK or you may replace the wrong...

Page 10: ...15 VAC Is Already Present 12 VDC P C Board GH B YES Fan Only Green Blue Cooling Mode Yellow Blue YES 12 VDC At P C Board GH B Refer To Auto Gen Checkout 115 VAC At P C Board High NO Check Low Voltage...

Page 11: ...d Connectors To Plug And Thermostat Repair As Needed If All Are Good Replace Thermostat YES 12 VDC At P C Board Y B YES 115 VAC P C Board Compressor Relay COM Check Compressor 1 Start Relay Check For...

Page 12: ...On Wall Thermostat Plug At Unit YES 12 VDC At 4 Pin Plug Red Black NO Check All Wiring And Connections From Indoor Section To Thermostat Repair As Needed If All Are Good Replace Thermostat YES Refer...

Page 13: ...rd WI NO Check Wiring And Connections From Thermostat Wiring Plug Gray Wire To W1 If Wiring Is Good Replace P C Board YES Is Indoor Low Speed Running Thermostat Set For Low Heat Thermostat Set For Hig...

Page 14: ...ow Checkout then proceed below 12 VDC At P C Board GL B YES NO Check All Wiring And Connections From GL On P C Board 115 VAC At P C Board Low YES Check Wiring To Motor Check Capacitor Motor Windings F...

Page 15: ...10 CONTROL BOX COMPONENTS 15 15...

Page 16: ...r W1 1st Stage Heat Signal From Thermostat W2 2nd Stage Heat Signal From Thermostat GH Indoor Blower Signal From Thermostat Y Compressor Signal From Thermostat Power To Compressor Power To 2nd Stage H...

Page 17: ...11 WIRING DIAGRAM 17...

Page 18: ...Associated Products Division Airxcel Inc Associated Products Division P O Box 4020 Wichita KS 67204 1976 607 3 12...

Page 19: ......

Reviews: