PRODUCT DATA SHEET
SM YUDE 2-A.1 GB
2-9
2.9
AWSI-CADE036-N11 //
AWAU-YUDE036-H11
Model Indoor Unit
AWAU-CADE036-N11
Model Outdoor Unit
AWAU-YUDE036-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
10,0(3,2-11,5)
12,0(2,9-14,5)
Pdesign
kW
10,0
10,4
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
687
3832
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-32
Rated power input (Maximum power input)
kW
4,65
4,85
Rated current (Maximum current)
A
21,5
22,5
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
720/680/600/520
720/680/600/520
Air flow
(3)
H/M/L
m3/hr
1850
1850
External static
pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
63
Sound pressure level
(5)
H/M/L
dB(A)
51/49/46/43
Moisture removal
l/hr
3,8
Condensate drain tube I.D
mm
25mm
Dimensions
WxHxD
mm
840x840x320
Weight
kg
31
Package dimensions
WxHxD
mm
963x963x409
Packaged weight
kg
38
Units per pallet
units
5
Stacking height
units
5
OUTDOO
R
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
900
Air flow
H/L
m3/hr
5300
Sound power level
(4)
H/L
dB(A)
70
Sound pressure level
(5)
H/L
dB(A)
63
Dimensions
WxHxD
mm
1107x1100x440
Weight
kg
92
Package dimensions
WxHxD
mm
1158x1235 x493
Packaged weight
kg
100
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
3,5
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
Summary of Contents for YUDE024
Page 21: ...PERFORMANCE DATA SM YUDE 2 A 1 GB 5 1 5 PERFORMANCE DATA...
Page 26: ...WIRING DIAGRAMS 8 2 SM YUDE 2 A 1 GB 8 2 AWAU YUDE036 H11...
Page 27: ...WIRING DIAGRAMS SM YUDE 2 A 1 GB 8 3 8 3 AWAU YUDE036 H13 TBD...
Page 28: ...WIRING DIAGRAMS 8 4 SM YUDE 2 A 1 GB 8 4 AWSI CADE024 030 036 N11 For model 30 42...
Page 30: ...WIRING DIAGRAMS 8 6 SM YUDE 2 A 1 GB 8 6 AWSI DBD024 030 036 N11...
Page 72: ...APPENDIX SM YUDE 2 A 1 GB 14 1 14 APPENDIX APPENDIX...