Note :
(1) Fix the parts with screws.
(2) Don't intake the strong wind directly to
the outlet air-flow hole.
(3) A one meter distance should be
kept from the unit top.
(4) Don't block the surroundings of the unit with sundries.
(5) If the outdoor unit is installed in a place that is exposed
to the wind, install the unit so that the outlet grid is NOT
pointing in the direction of the wind.
(a) Concrete foundation
(b) Foundation anchor
Concrete foundation
Unit
Anchor bolt
1. Selection of the place of installation
Select the place of installation satisfying the following conditions and, at the same time, obtain a consent from the client or
user.
Place where air circulates.
Place free from heat radiation from other heat sources.
Place where drain water may be discharged.
Place where noise and hot air may not disturb the neighborhood.
Place where there is not heavy snowfall in the winter time.
Place where obstacles do not exist near the air inlet and air outlet .
Place where the air outlet may not be exposed to a strong wind.
Place surrounded at four sides are not suitable for installation. A 1m or more of overhead space is needed for the unit.
Avoid mounting guide-louvers to the place where short-circuit is a possibility.
When installing several units, secure sufficient suction space to avoid short circuiting.
Open space requirement around the unit
Installation of Outdoor Unit
Wind direction
NO
L2
L3
L1
500
(Servicing
space)
Air outlet
Air inlet
Air inlet
Distance
open
open
open
500 mm
150 mm
150 mm
300 mm
300 mm
300 mm
L1
L2
L3
Case I
Case II
Case III
Fix the unit on the foundation in a proper way according to the condition of the installation place, referring to the following
information.
2. Installation of outdoor unit
Give enough room for the concrete foundation to fix by anchor bolts.
Place the concrete foundation deep enough.
Install the unit so that the angle of inclination must be less than 3 degrees.
Anchor bolt
Concrete foundation
Unit
To fix by bolts
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
17
Summary of Contents for YUDA060
Page 1: ...SERVICE MANUAL YUDA060 CAD060 Outdoor unit YUDA060 Indoor unit CAD060...
Page 7: ..._ VbTZR Zb _ UZdZ_ Vb 3 Dimension 580 25 1250 948 380 340 YUDA060 7...
Page 16: ...Name of Parts _ VbTZR Zb _ UZdZ_ Vb Air inlet Air outlet Compressor Inside of unit YUDA060 16...
Page 18: ...3 Installation dimension Unit mm _ VbTZR Zb _ UZdZ_ Vb 580 25 1250 948 380 340 YUDA060 18...
Page 40: ..._ VbTZR Zb _ UZdZ_ Vb 5 2 Indoor unit 5 2 1 PCB for indoor unit 40...
Page 59: ..._ VbTZR Zb _ UZdZ_ Vb 59...
Page 63: ..._ VbTZR Zb _ UZdZ_ Vb 63...
Page 64: ..._ VbTZR Zb _ UZdZ_ Vb wIWXb ST WPb c cWXb Ud RcX x 64...