Check if the wires of the
compressor connect well
Measured the compressor winding
With milliohm meter, check if the compressor
Resistance is balance
Check if the high/ low pressure is normal
Change the module
Reconnect or change the wires
Change the compressor
Yes
Yes
Yes
No
No
[82] Compressor current protection
[108] Transient over current in IPM module rectifier side software
[109 Current detection circuit abnormality
[123] Transient over current in IPM module rectifier side hardware