BM1 introduction
14. Dip Switch Setting
BM1 introduction
Note
:
System can not operate without locking, and cannot operate when the locking number is not in accordance with
the actual quantity
BM1_1
Indoor unit quantity
lock
0
Start to search indoor unit
(
Default
)
1
Stop searching indoor unit and lock the quantity
BM1_2
BM1_3
BM1_4
BM1_5
Capacity selection
BM1_2
BM1_3
BM1_4
BM1_5
Capacity selection
0
0
1
1
8HP
0
1
0
1
10HP
0
1
1
1
12HP
BM1_6
Indoor ON/OFF
simultaneous control
0
Indoor units ON/OFF simultaneous controlIn
available
(
Default
)
1
Indoor units ON/OFF simultaneous controlIn
unavailable
BM1_7
Defrosting level
0
Ordinary (Default)
1
Strengthen defrosting
BM1_8
Quiet running
function
0
Quiet running function is invalid (Default)
1
Quiet running function is valid
47