CONTROL SYSTEM
12-2
Service Manual
– YBZE DCI 1-A.1 GB
12.1.2
Compressor Frequency Control
12.1.2.1 Compressor frequency setting
The Load calculation is done by each indoor unit controller, based on a PI control scheme which
is based on the difference between SPT and RAT.
ODU controller will decide the compressor frequency based on the total load from all the indoors.
Compressor frequency will be limited within following ranges:
Mode
Minimum Frequency (MinFreq)
Maximum Frequency (MaxFreq) *
YBZE218
YBZE324
YBZE430
YBZE218
YBZE324
YBZE430
Cooling
15
15
15
110
110
110
Heating
15
15
15
110
110
110
* Maximum frequency is also decided by different indoor combinations.
12.1.2.2 Frequency Changes Control
Frequency change rate is 1 Hz/sec.
12.1.2.3 Compressor Starting Control
30Hz
40Hz
50Hz
60Hz
70Hz
80Hz
90Hz
1min
2min
2min
12.1.2.4 Minimum On and Off Time
Prohibit turning ON the compressor for 3 minutes after turning it off. (Except during deicing
protection)
Prohibit turning OFF the compressor for 7 minutes after turning it on (except protections required
immediate compressor stop)
Downloaded from
www.Manualslib.com
manuals search engine
Summary of Contents for YBZE218-324-430
Page 4: ...Downloaded from www Manualslib com manuals search engine...
Page 14: ...Downloaded from www Manualslib com manuals search engine...
Page 16: ...Downloaded from www Manualslib com manuals search engine...
Page 20: ...Downloaded from www Manualslib com manuals search engine...
Page 22: ...Downloaded from www Manualslib com manuals search engine...
Page 24: ...Downloaded from www Manualslib com manuals search engine...
Page 26: ...Downloaded from www Manualslib com manuals search engine...
Page 32: ...Downloaded from www Manualslib com manuals search engine...
Page 34: ...Downloaded from www Manualslib com manuals search engine...
Page 36: ...Downloaded from www Manualslib com manuals search engine...
Page 50: ...Downloaded from www Manualslib com manuals search engine...