CONTROL SYSTEM
Service Manual
– YBZE DCI 1-A.1 GB
12-9
12.7.4
Compressor over Heating Protection
The Discharging temperature is used as t
he compressor’s internal temperature. If the discharge
temperature rises above a certain level, the operating frequency upper limit is set to keep this
temperature from going up further.
Compressor frequency will be reduced when CTT reaches above 97C
Compressor will stop when CTT reaches 110C
If the unit stops as such protection for 6 times
(the counter will be cleared after the compressor has
run for 7min)
, it can not resume running automatically and display malfunction, it can resume by
remote control ON/OFF reset.
12.7.5
Compressor over Current Protection
Detect an input current by the CT during the compressor is running, and set the frequency upper
limit from such input current. In case of heat pump model, this control is the upper limit control
function of the frequency which takes priority of the lower limit of four way valve activating
compensation.
Detail
For model 14: Compressor will stop when AC current >= 16.0A for continuously 2.5s
For model 18/30: Compressor will stop when AC current >= 20.0A for continuously 2.5s
If the unit stops as such protection for 6 times (the counter will be cleared after the compressor has
run for 7min), it can not resume running automatically and display malfunction, it can resume by
remote control ON/OFF reset.
12.7.6
Outdoor Coil Deicing Protection
This protection is for Heat Pump Only
This protection is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than its setting values when finishing the deicing
protection.
In the deicing protection, IFAN is forced OFF.
12.7.6.1 Deicing Starting Conditions
The starting conditions must be made with the outdoor air temperature (OAT) and outdoor coil
temperature (OCT). Under the conditions that the system is in heating operation, after the time for
defrosting is judged to be satisfied, if the temperature for deicing is satisfied after detections for
continuous 1 minute, the deicing operation will start.
Downloaded from
www.Manualslib.com
manuals search engine
Summary of Contents for YBZE218-324-430
Page 4: ...Downloaded from www Manualslib com manuals search engine...
Page 14: ...Downloaded from www Manualslib com manuals search engine...
Page 16: ...Downloaded from www Manualslib com manuals search engine...
Page 20: ...Downloaded from www Manualslib com manuals search engine...
Page 22: ...Downloaded from www Manualslib com manuals search engine...
Page 24: ...Downloaded from www Manualslib com manuals search engine...
Page 26: ...Downloaded from www Manualslib com manuals search engine...
Page 32: ...Downloaded from www Manualslib com manuals search engine...
Page 34: ...Downloaded from www Manualslib com manuals search engine...
Page 36: ...Downloaded from www Manualslib com manuals search engine...
Page 50: ...Downloaded from www Manualslib com manuals search engine...