PERFORMANCE DATA & PRESSURE CURVES
SM XLFDCI 1-A.1 GB
5.4.2
Heating Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR DB ID COIL(
O
C)
15
20
25
ENTERING WB
OD COIL(
o
C)
TH
Pl
TH
Pl
TH
Pl
-10
1.75 0.76 1.69 0.81 1.62 0.85
-7
1.89 0.78 1.82 0.82 1.75 0.87
-2
2.00 0.79 1.94 0.84 1.87 0.88
2
2.44 0.83 2.34 0.88 2.24 0.93
6
3.44 0.89
3.34 0.95
3.22 1.01
10
3.74 0.94 3.64 1.00 3.54 1.07
15
4.04 0.98 3.94 1.05 3.84 1.12
20
4.25 1.01 4.15 1.09 4.04 1.18
*
the above chart includes the weighted deicing infleuence.
LEGEND
TH – Total Heating Capacity, kW
PI
– Power Input, kW
WB –
Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD –
Outdoor
5.5
Capacity Correction Factor Due to Tubing Length
5.5.1 Cooling
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.02
1
0.961
0.948
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.
5.5.2 Heating
TOTAL TUBING LENGTH (One Way)
3m
7.5m
10m
15m
20m
25m
30m
40m
50m
1.05
1
0.975
0.963
---
---
---
---
---
*
Minimum recommended tubing length between indoor and outdoor units is 3m.