CONTROL SYSTEM
11-24
SM VAR 1-A.1 GB
b. High
Pressure
Protection
Mode: (AUTO)
COOLING
or
DRY
Temp: Selected desired temperature
Fan: Any
Timer: Any
I-FEEL: ON or OFF
Control Function
To protect the COMP from the high pressure build-up in the outdoor coil during normal
cooling operation, by switching OFF the IFAN and COMP.
OCT [
o
c]
Any
OFF
Any
ON
Any
Blink
ON
COMP
OFAN
IFAN
OPER
LED
52
55
61
66
L
COMP is forced OFF
OFAN is forced ON
IFAN forced
to LOW
68
OFAN follow operation of
COMP
COMP is forced OFF
OFAN is forced ON
For all models except WAX & P2000
For WAX & P2000 models
NOTE
The ICT is also monitored during COOL and DRY modes, in case the
RV control circuit is faulty. Whenever ICT reaches 70
o
C, which
indicates a high pressure in the indoor coil, the COMP will be forced
OFF automatically. The COMP can be turned ON again only after the
ICT is under 70
o
C again and after the 3 min COMP ON delay time. The
OPER LED will not blink in this case.