TECHNICAL SPECIFICATIONS
POWER SUPPLY
VS
: Standard ventilation
HV
: High ventilation
*
mains switch not supplied: to be provided by the installer.
4650
6450
power supply
3 ~230 v* - 50 Hz 3 ~230 v* - 50 Hz
Outdoor unit
UC 74
UC 104
power supply
~230 v - 50 Hz
~230 v - 50 Hz
Nominal power input
W
611
1222
maximum intensity
A
3.1
6.2
Starting intensity
A
5.5
11
Cable size
mm
2
1.5
1.5
INTERCONNECTION WITH OUTDOOR UNIT (AIR COOLED UNIT)
IMPORTANT
These values are given for information only. They should be checked and adjusted according to prevailing standards.
They depend on the mode of installation and the type of wires selected.
Note
: 1 Cooling unit and 2x15 kW heating are considered in terms of dehumidification
*
THREE PHASE 230 V
: Installation regulated in France.
4650
6450
power supply
3 ~230 v* - 50 Hz
3N ~400 v - 50 Hz
3 ~230 v* - 50 Hz 3N ~400 v - 50 Hz
models
X ARv
X AO
X ARv
X AO
X ARv
X ARv
• C ventilation(vS/Fv)
Nominal power input
kW
17/19
13.9/16
17/19
13.9/16
24.6/26.2
24.6/26.2
maximum intensity
A
76/85
67/76
45/50
39/44
109/117
64/69
Starting intensity
A
176/203
146/173
102/117
84/99
249/273
144/159
motor fuse rating am
A
80/100
80
50
40/50
125
80
Cable size
mm
2
25/35
25
10
10
50
16/25
• Electrical heating + ventilation (vS/Fv)
Nominal power input
kW
39.4/41.5
39.4/41.5
39.4/41.5
39.4/41.5
48.4/50
48.5/50
maximum intensity
A
128/137
128/137
73/78
73/78
155/158
89/94
Starting intensity
A
170/203
146/173
100/115
84/99
244/268
139/154
motor fuse rating am
A
160
160
80
80
160
100
Cable size
mm
2
70
70
25
25
70
35
• ventilation (vS/Fv) + Electrical heating (or dehumidification)
Nominal power input
kW
39.4/41.5
37.9/40
39.4/41.5
37.9/40
44.3/45.9
44.3/45.9
maximum intensity
A
135/144
130/139
79/84
74/79
156/164
91/96
Starting intensity
A
242/269
219/246
139/154
125/140
307/331
177/192
motor fuse rating am
A
160
160
100
80
160/200
100
Cable size
mm
2
70
70
25/35
25
70
35
7