TROUBLESHOOTING
SM YAZ318 1-A.1 GB
12-5
No Fault Name
Fault Description
Corrective Action
20 Heat sink Over Heating
Compressor stopped due to
heatsink protection
Check that the airflow around the
ODU is free and the fan is running
free. Check fan motor
21 Deicing
During deicing procedure
No action required
22 Compressor
Over
Heating
Compressor stopped due to over
heat protection
Check if gas is missing in the system
23 Compressor
Over
Current
Compressor stopped due to over
current protection
No action required
24 No OFAN Feedback
No encoder signal can be detected
from the OFAN
Check DC-FAN hall sensor
connection/plug for damage. Check
DC-FAN for any blockage. Measure
between U-V, U-W for resistance
using multimeter. Resistance value
should be below 1 OHM. If
multimeter display high resistance,
replace DC-FAN motor, otherewise
replace controller.
25 OFAN IPM fault / OFAN
IPM Driver Pin
OFAN IPM module detect shoot-
through current / OFAN IPM driver
control pin is unconditionally latch
to high state
Check DC-FAN hall sensor
connection/plug for damage. Check
DC-FAN for any blockage. Measure
between U-V, U-W for resistance
using multimeter. Resistance value
should be below 1 OHM. If
multimeter display high resistance,
replace DC-FAN motor. Return
controller if error is persistent.
26 Compressor Lock
No correct drive current can be
detected from the compressor
Check compressor cable or
compressor wire assembly. Make
sure the phase sequence of U-V-W is
correctly plug into the compressor.
27 Bad Communication
Lost of communication from indoor
unit
Check communication wire between
indoor and outdoor unit
28
Missing ODU
configuration
All the DIP is set to 0 (the DIP are
not configured).
This problem cannot happen in
DCI80. Previously, this fault is used
to detect model plug that fall down.
29 Undefined ODU Model
The outdoor model is not defined in
the software.
Wrong Outdoor DIP setting.
Too old outdoor software. Update
software
30 Outdoor/Indoor
Coil
Overheating
This protection combines the
following:
Overheating in cooling mode
(based on OMT reading).
Overheating in heating mode
based on ICT.
Improper ventilation of the coils
Over charged system
Problem with ICT sensors or OMT
sensor (fake up).
Illegal too small indoor unit’s
installation (heating).
31 Operation
conditions
are exceeded
For cooling:
For Heating:
This is not a fault but information on
the ambient operation:
The unit operates outside the defined
operation range.
The OAT fakes and cause false
alarm.
Summary of Contents for SX 12 DCI
Page 17: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 1 4 OUTLINE DIMENSIONS 4 1 Indoor Unit PNXA009 012...
Page 20: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 4 4 5 Indoor Unit DLF09 12 DCI...
Page 23: ...OUTLINE DIMENSION SM YAZ318 1 A 1 GB 4 7 4 10 OUTDOOR UNIT YAZ318...
Page 35: ...OPERATING CURVES 6 2 SM YAZ318 1 A 1 GB 6 1 2 Heating Technician Mode...
Page 36: ...OPERATING CURVES SM YAZ318 1 A 1 GB 6 3 6 1 3 Tubing Length correction Factor...
Page 41: ...TUBING CONNECTIONS SM YAZ318 1 A 1 GB 10 1 10 TUBING CONNECTIONS...