CONTROL SYSTEM
SM YAZ318 1-A.1 GB
11-5
3. Each channel that is identified as ‘no communication’ channel will be referred as
STBY unit.
4. The unit resumes its normal operation with only the operative channels.
11.3.3
Temperature Measurements
11.3.3.1
Thermistor failures definition
Thermistor
Type a – Disconnected
Type b – Shorted
OAT Temp
<
-30
o
C
Temp > 75
o
C
OCT
Temp < -35C
Temp > 75
o
C
CTT Temp
<
-30
o
C
Temp > 125
o
C
HST Temp
<
-30
o
C
Temp> 125
o
C
OMT Temp
<
-35
o
C
Temp > 75
o
C
ICT Temp
<
-30
o
C
Temp > 75
o
C
RGT Temp
<
-30
o
C
Temp > 126
o
C
RLT Temp
<
-30
o
C
Temp > 126
o
C
11.3.3.2
System responses for different thermistor failure
Thermistor
Default value
System Reaction
OCT 43°C
OAT 6°C
CTT 43°C
Compressor
is
stopped.
OMT
43°C
Compressor is stopped in cooling mode.
HST 43°C
Compressor
is
stopped.
RGT 43°C
RLT 43°C
ICT 43°C
11.3.4
Flash Memory Programming
In order to upgrade the ODU software the auxiliary port will be used. A special application
should be run on a PC to transmit the new firmware. Special programmer (Panasonic)
should be used to update the S/W.
Summary of Contents for SX 12 DCI
Page 17: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 1 4 OUTLINE DIMENSIONS 4 1 Indoor Unit PNXA009 012...
Page 20: ...OUTLINE DIMENSIONS SM YAZ318 1 A 1 GB 4 4 4 5 Indoor Unit DLF09 12 DCI...
Page 23: ...OUTLINE DIMENSION SM YAZ318 1 A 1 GB 4 7 4 10 OUTDOOR UNIT YAZ318...
Page 35: ...OPERATING CURVES 6 2 SM YAZ318 1 A 1 GB 6 1 2 Heating Technician Mode...
Page 36: ...OPERATING CURVES SM YAZ318 1 A 1 GB 6 3 6 1 3 Tubing Length correction Factor...
Page 41: ...TUBING CONNECTIONS SM YAZ318 1 A 1 GB 10 1 10 TUBING CONNECTIONS...