2-6
PRODUCT DATA SHEET
SM YAZDCI 1-A.1 GB
2.3.7
SX009 DCI Specifications
Model Indoor Unit
SX009 DCI
Installation Method of Pipe
Flared
Power supply
V/Ph/Hz
220-240/1/50
INDOOR
Fan type & quantity
Centifugal x 2
Fan speeds
H/M/L
RPM
760/670/500
Air flow
(1)
H/M/L
m3/hr
400/350/300
External static pressure
Min
Pa
0
Sound power level
(2)
H/M/L
dB(A)
54/49/41
Sound pressure level
(3)
H/M/L
dB(A)
42/37/29
Moisture removal
l/hr
1
Condenstate drain tube I.D
mm
16
Dimensions
WxHxD
mm
820x630x190
Net Weight
kg
21
Package dimensions
WxHxD
mm
920x726x273
Package weight
kg
25
Units per pallet
units
14units per pallet
Units stacking
units
7 levels
2.3.8
SX012 DCI Specifications
Model Indoor Unit
SX012 DCI
Installation Method of Pipe
Flared
Power supply
V/Ph/Hz
220-240/1/50
INDOOR
Fan type & quantity
Centifugal x 2
Fan speeds
H/M/L
RPM
830/760/500
Air flow
(1)
H/M/L
m3/hr
450/400/300
External static pressure
Min
Pa
0
Sound power level
(2)
H/M/L
dB(A)
56/53/41
Sound pressure level
(3)
H/M/L
dB(A)
45/41/30
Moisture removal
l/hr
1.5
Condenstate drain tube I.D
mm
16
Dimensions
WxHxD
mm
820x630x190
Net Weight
kg
22
Package dimensions
WxHxD
mm
920x726x273
Package weight
kg
26
Units per pallet
units
14units per pallet
Units stacking
units
7 levels
NOTE:
(1)
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511.
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit.