ELECTRONICS FUNCTION
DHK DCI 39 Version - 2
10.3 Main Protection
10.3.1
Three minutes delay at restart for
compressor
Less than 1 minute delay for the 1
st
time
stand-up and 3 minutes delay for others.
10.3.2
Temperature protection of
compressor top
The unit will stop working when the compressor
top temp. Protector cut off, and will restart after
the compressor top temp. Protector restart.
10.3.3
Temperature protection of
compressor discharge
Compressor discharge temp. T5>115
℃
for 5s,
compressor stops.
10.3.4
Fan speed is out of control
When indoor fan speed keeps too low
(300RPM) for certain time, the unit will stop and
the LED will display the failure
10.3.5
Inverter module protection
The Inverter module has a protection function
about current, voltage and temperature. If these
protections happen, the corresponding code
will display on indoor unit and the unit will stop
working.
10.3.6
Indoor fan delayed open function
When the unit starts up, the louver will be active
immediately and the indoor fan will open 7s
later.
If the unit runs in heating mode, the indoor fan
will be also controlled by anti-cold wind
function.
10.3.7
Compressor preheating functions
Preheating permitting condition:
When T4(outdoor ambient temperature)
<
3°C,
the preheating function will be activated.
10.3.8
Sensor protection at open circuit and
breaking disconnection.
When there’s only one temperature sensor in
malfunction , the air conditioner will keep
working but show the error code, in case of any
emergency use.
When there’s more than one temperature
sensor in malfunction, the air conditioner will
stop working.
10.3.9
Refrigerant leakage detection
This function is only active in cooling mode. It
can better prevent the compressor being
damaged by refrigerant leakage or compressor
overload.
Open condition:
When compressor is active, the value of the
Coil temperature of evaporator T2 has no
change or very little change.
10.4 Operation Modes and Functions
10.4.1
Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled,
and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto.
(4) The louver operates same as in cooling
mode.
(5) Auto fan:
a
b
c
d
T1
e
10.4.2
Cooling Mode
10.4.2.1 Compressor running rules
When T1- Ts <
ΔT -2
℃
, the compressor will
stop,
when T1
—
Ts >
ΔT -0.5
℃,
the compressor will
be activated.
ΔT is the programmed parameter of
temperature compensation.
When the AC run in mute mode, the
compressor will run with low frequency.
When the current is more than setting value,
the current protection function will be activated,
and the compressor will stop.
10.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan
speed according to T4.
Summary of Contents for JSP060040
Page 12: ...DIMENSIONS Version 2 12 DHK DCI For JOSI DKH009 N11 For JOSI DKH012 N11...
Page 13: ...DIMENSION DHK DCI 13 Version 2 For JOSI DKH018 N11 For JOSI DKH024 N11...
Page 16: ...DIMENSIONS Version 2 16 DHK DCI...
Page 28: ...WIRING DIAGRAM Version 2 28 DHK DCI 7 3 Outdoor unit JOAU DKY018 H11...
Page 29: ...WIRING DIAGRAM DHK DCI 29 Version 2 7 4 Outdoor unit JOAU DKY024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 2 66 DKH DCI 12 2 JOSI DKH012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 2 68 DKH DCI 12 3 JOSI DKH018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 2 70 DKH DCI 12 4 JOSI DKH024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 2 72 DKH DCI 12 5 JOAU DKY009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 2 74 DKH DCI 12 6 JOAU DKY012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 2 76 DKH DCI 12 7 JOAU DKY018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 2 78 DKH DCI 12 8 JOAU DKY024 H11...
Page 80: ...SERVICE MANUAL DKH DCI Series...