PERFORMANCE DATA
DHK DCI 19 Version - 2
5.2 JOSI-DKH012-N11 / JOAU-DKY012-H11
1) Cooling
ID COIL ENTERING AIR DB/WB TEMPERATURE [C
0
]
OD COIL ENTERING
AIR DB
TEMPERATURE [C
0
]
DATA
22/15
24/17
27/19
29/21
32/23
-10 - 20
(protection range)
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
PI
25 - 50 % of nominal
25
TC
3.42
3.65
3.87
4.09
4.32
SC
2.61
2.67
2.72
2.77
2.83
PI
0.86
0.88
0.89
0.91
0.93
30
TC
3.26
3.48
3.70
3.93
4.15
SC
2.55
2.60
2.65
2.71
2.76
PI
0.96
0.98
0.99
1.01
1.03
35
TC
3.09
3.32
3.54
3.76
3.99
SC
2.48
2.53
2.59
2.64
2.69
PI
1.06
1.08
1.10
1.11
1.13
40
TC
2.93
3.15
3.38
3.60
3.82
SC
2.42
2.47
2.52
2.58
2.63
PI
1.16
1.18
1.20
1.21
1.23
46
TC
2.73
2.95
3.18
3.40
3.63
SC
2.34
2.39
2.44
2.50
2.55
PI
1.28
1.30
1.32
1.33
1.35
Legend:
TC - Total Cooling Capacity [kW]
SC - Sensible Capacity [kW]
PI - Power Input [kW]
WB - Wet Bulb Temperature
DB - Dry Bulb Temperature
ID - Indoor
OD - Outdoor
Summary of Contents for JSP060040
Page 12: ...DIMENSIONS Version 2 12 DHK DCI For JOSI DKH009 N11 For JOSI DKH012 N11...
Page 13: ...DIMENSION DHK DCI 13 Version 2 For JOSI DKH018 N11 For JOSI DKH024 N11...
Page 16: ...DIMENSIONS Version 2 16 DHK DCI...
Page 28: ...WIRING DIAGRAM Version 2 28 DHK DCI 7 3 Outdoor unit JOAU DKY018 H11...
Page 29: ...WIRING DIAGRAM DHK DCI 29 Version 2 7 4 Outdoor unit JOAU DKY024 H11...
Page 66: ...EXPLODED VIEW AND SPARE PART LIST Version 2 66 DKH DCI 12 2 JOSI DKH012 N11...
Page 68: ...EXPLODED VIEW AND SPARE PART LIST Version 2 68 DKH DCI 12 3 JOSI DKH018 N11...
Page 70: ...EXPLODED VIEW AND SPARE PART LIST Version 2 70 DKH DCI 12 4 JOSI DKH024 N11...
Page 72: ...EXPLODED VIEW AND SPARE PART LIST Version 2 72 DKH DCI 12 5 JOAU DKY009 H11...
Page 74: ...EXPLODED VIEW AND SPARE PART LIST Version 2 74 DKH DCI 12 6 JOAU DKY012 H11...
Page 76: ...EXPLODED VIEW AND SPARE PART LIST Version 2 76 DKH DCI 12 7 JOAU DKY018 H11...
Page 78: ...EXPLODED VIEW AND SPARE PART LIST Version 2 78 DKH DCI 12 8 JOAU DKY024 H11...
Page 80: ...SERVICE MANUAL DKH DCI Series...