PERFORMANCE DATA
Service Manual –KXL DCI
Revision 0
5-1
5. PERFORMANCE
DATA
5.1
KXL 24 DCI
5.1.1
Cooling Capacity (kW)-Run Mode
ID COIL ENTERING AIR DB/WB TEMPERATURE [C
0
]
OD COIL
ENTERING AIR DB
TEMPERATURE
[C
0
] DATA
22/15
24/17
27/19
29/21
32/23
TC
80 - 110 % of nominal
SC
80 - 105 % of nominal
-10 - 20
(protection range)
PI
25 - 50 % of nominal
TC 7.09 7.51 7.93 8.34 8.76
SC 6.09 6.19 6.28 6.37 6.46
25
PI 1.81 1.85 1.89 1.93 1.97
TC 6.73 7.15 7.56 7.98 8.40
SC 5.86 5.95 6.04 6.13 6.22
30
PI 2.06 2.10 2.14 2.18 2.22
TC 6.36 6.78 7.20 7.62 8.04
SC 5.62 5.71 5.80 5.89 5.98
35
PI 2.31 2.35 2.39 2.43 2.47
TC 6.00 6.42 6.84 7.25 7.67
SC 5.38 5.47 5.56 5.65 5.74
40
PI 2.56 2.60 2.64 2.68 2.72
TC 5.56 5.98 6.40 6.82 7.24
SC 5.10 5.19 5.28 5.37 5.46
46
PI 2.86 2.90 2.94 2.98 3.02
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OU –
Outdoor
5.1.2 Capacity
Correction Factors