Service Manual - KXL DCI
12-17
12.13.2
Outdoor Units SW Parameters
Model dependent parameters for GC 24/30 DCI
Compressor Parameters
Value
MinOFFTime
3
MinOnTime
3
MaxCTT1
90
MaxCTT2
90
MinSpeedAsCTT1
26
MinSpeedAsCTT2
26
MaxSpeedC
75
MaxSpeedH
95
Step1RPS
40
Step2RPS
60
Step3RPS
75
NormAcc
(sec/RPS)
1
NormDec
(sec/RPS)
1
Down1
(Sec/RPS)
12
Down2
(Sec/RPS)
7
DeiceAcc
(Sec/RPS)
0.2
DeiceDec
(Sec/RPS)
0.5
EEV Parameters
Value
NormEEVRate
30
EEVCompOFFOpen
200
EEVCompOFFTime
60
EEVMaxOpen
500
EEVMinOperOpenC
60
EEVMaxOperOpenC
500
EEVMinOperOpenH
70
EEVMaxOperOpenH
500
EEVMinOperOpenHInIDU
60
EEVMaxOperOpenHInIDU
140
EEVIDUOFFOpen
130
EEVMoveSteps
20
EEVTConstC
30
EEVTConstH
30
BlncTimTrnsStC
1
BlncTimStdyStC
1
BlncTimTrnsStH
1
BlncTimStdyStH
1
CompOffTimToTrnsSt
20