TROUBLESHOOTING
13-5
SM
JE
DE 1-A.1 GB
13.1.4
Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system
is in Test Mode (in Test mode, system operates in fixed settings). The performance curves
given in this manual are given for unit performance in test mode when high indoor fan speed is
selected.
Entering test mode please refer to section 12- Control system.
13.2
Simple procedures for checking the Main Parts
13.2.1
Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this
range, abnormal operation of the system is expected. If in range check the Power (Circuit)
Breaker and look for broken or loosed cable lugs or wiring mistake(s).
13.2.2
Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor
unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse
and power up again.
Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
13.2.3
Checking the Outdoor Fan Motor.
For AC motor
Check the voltage between two pins Hi and N of connector OFAN on controller, normal
voltage is 220~240VAC.
For DC Motor
Check the voltage between any two pins of connector OFAN on controller, normal voltage is
280~380VDC
13.2.4
Checking the Compressor.
The compressor is brushless permanence magnetic DC motor. Three coil resistance is
same. Check the resistance between three poles. The normal value should be with the
almost same value. Pay attention U,V, W are respective to connect to
RED,YELLOW,BLUE
wires.
13.2.5
Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two pins of reverse valve connector,
normal voltage is 220~240VAC.
Summary of Contents for ELECTRA AWAU-VDDE009-H11
Page 14: ...OUTLINE DIMENSION SM JEDE 1 A 1 GB 4 2 4 2 Outdoor VDDE009 4 3 Outdoor VDDE012...
Page 15: ...4 3 SM JEDE 1 A 1 GB SOUND LEVEL CHARACTERISTICS 4 4 Outdoor VDDE018 4 5 Outdoor VDDE024...
Page 21: ...SM JEDE 1 A 1 GB 9 1 WIRING DIAGRAM 9 WIRING DIAGRAM 9 1 JEDE009 JEDE012 9 2 JEDE018...
Page 22: ...WIRING DIAGRAM SM JEDE 1 A 1 GB 9 2 9 3 JEDE024 9 4 VDDE009...
Page 23: ...9 3 SM JEDE 1 A 1 GB WIRING DIAGRAM 9 5 VDDE012 9 6 VDDE018 VDDE024...
Page 47: ...14 2 SM JEDE 1 A 1 GB CHARACTERISTICS OF SENSOR 14 1 3 CTT CTT R T Chart...
Page 51: ...EXPLODED VIEW SPARE PART LIST 15 4 SM JEDE 1 A 1 GB 15 4 Exploded view of indoor unit JEDE018...
Page 58: ...SM JEDE 1 A 1 GB 15 11 SERVICING 15 11 Exploded view of outdoor unit YDDE018...
Page 60: ...SM JEDE 1 A 1 GB 15 13 SERVICING 15 13 Exploded view of outdoor unit VDDE024...
Page 63: ...SM JEDE 1 A 1 GB a APENDIX APPENDIX...
Page 64: ...SM HDDE 1 A 1 GB 15 15 SERVICE MANUAL JEDE009 012 018 024...