F1 F2 R1 R2
L
N
F1
F2R
1
R2
ELB
Power
Beraker
220~240V AC
50Hz
Size
Tightening torque
Remote controller and main bus communication wiring and forced off
terminal block(4P)
M3.5
0.8~1.0N.m
Power supply and Ground terminal block(2P)
M4
1.2~1.5N.m
Electrical characteristics
Specification for field supplied ELB and wire
Unit
Power supply
Fan motor
Model
Hz
Volts
MCA
MFA
KW
FLA
CKV007
50
220~240
0.27
16
0.06
0.18
CKV009
0.27
16
0.06
0.18
CKV012
0.27
16
0.06
0.18
CKV015
0.55
16
0.10
0.32
CKV018
0.55
16
0.10
0.32
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps(A)
KW : Fan Motor Rated output(kW)
FLA : Full Load Amps(A)
Model
Power supply wiring
Remote controller wiring
Main bus wiring
Field ELB
Wire and Size
Wire
Size
CKV007
16A
Must comply
with maximum
current and local
codes(0.75mm
2
)
Twisted-pair
wires
1.0mm
2
CKV009
CKV012
CKV015
CKV018
BEFORE POWER ON
�
Is there any gas leakage at flare nut connections?
�
Has the heat insulation been carried out at flare nut connection?
�
Is the connecting cable being fixed to terminal board firmly?
�
Is the connecting cable being clamped firmly?
�
Is the drainage ok? (Refer to “Drainage test” section)
�
Is the earth wire connection properly done?
�
Is the indoor unit properly hooked to the installation plate?
�
I s the power supply voltage complied with rated value?
AFTER POWER ON
�
Is there any abnormal sound?
�
Is the cooling operation normal?
�
Is the thermostat operation normal?
�
Is the remote control’s LCD operation normal?
NOTE: For the piping and wiring methods,leakage test,vacuum process and installation setting
through HMI, please refter to “Outdoor unit Installation Manual”.
NOTE:
�
All field supplied parts and materials and electrics
works must conform to local codes.
�
Use copperwire only.
�
All wiring must be performed by an authorized
electrician.
�
Every indoor unit must have a sub circle breaker
and the whole system must have a main circle
breaker.
�
Be sure to ground the air conditioner.
�
The appliance shall be installed in accordance with
national wiring regulations ,and shall be provided
to ensure all-pole disconnection from the supply
mains, and distance between the poles shall be
more than 3 mm .
CHECK ITEMS
ELB: Electricity leakage breaker.
Press the wires under the clips tightly.
Fig 16
Fig 15