Air Evacuation
Note on Adding Refrigerant
Some systems require additional charging depending on pipe lengths. The standard pipe length varies
according to local regulations.
T
he standard pipe length is 5m (16‘). The refrigerant should be charged
from the service port on the outdoor unit’s low pressure valve. The additional refrigerant to be
charged can be calculated using the following formula:
CAUTION
DO NOT
mix refrigerant types.
Liquid Side Diameter
φ
6.35(1/4”)
φ
9.52(3/8”)
φ
12.7(1/2”)
(Total pipe length -
standard pipe length)
x65g(0.69oZ)/m(ft)
R410A:
(orifice tube in the outdoor unit):
(Total pipe length -
standard pipe length)
x15g(0.16oZ)/m(ft)
(Total pipe length -
standard pipe length)
x30g(0.32oZ)/m(ft)
R32:
(orifice tube in the outdoor unit):
(Total pipe length -
standard pipe length)x
12g(0.13oZ)/m(ft)
(Total pipe length -
standard pipe length)x
24g(0.26oZ)/m(ft)
(Total pipe length -
standard pipe length)x
40g(0.42oZ)/m(ft)
OUTDOOR UNIT
Refrigerent/GWP
Charge (5m)
(Kg)
AW-
YDFA
0
12
-H91
R32/675
AW-Y
DFA018
-H91
AW-Y
DFA024
-H91
AW-Y
DFA036
-H91
R32/675
R32/675
R32/675
0,87
1,15
1
,50
2,40
AW-Y
DFA036
-H9
3
R32/675
2,40
AW-Y
DFA0
48
-H9
3
R32/675
2,80
AW-Y
DFA0
60
-H9
3
R32/675
2,95
AW-Y
MD
0
12
-H
1
1
R410/2088
1,
05
AW-Y
MD018
-H
1
1
1,
35
AW-Y
MD024
-H
1
1
1,
95
AW-Y
MD036
-H
1
1
3,20
AW-Y
MD036
-H
13
3,20
AW-Y
MD048
-H
13
4,00
AW-Y
MD060
-H
13
4,30
R410/2088
R410/2088
R410/2088
R410/2088
R410/2088
R410/2088
Summary of Contents for CDM Cassette AW-YDFA012-H91
Page 2: ......
Page 31: ...Page 31...