Indoor Unit 1
Supply:1PH,220-230V~,50/60Hz
Supply:1PH,220-230V~,50/60Hz
Supply:1PH,220-230V~,50/60Hz
wall mounted type
Indoor Unit 2 wall mounted type
Indoor Unit 2
except wall mounted type
L N
14
Electrical Wiring
Warning
Attention
Supply Wiring Drawing
Breaker for
Electricity Leakage
Overflow Breaker
Breaker for
Electricity Leakage
Overflow Breaker
Breaker for
Electricity Leakage
Overflow Breaker
Electrical construction should be made with specific mains circuit by the qualified personnel according
to the installation instruction. Electric shock and fire may be caused if the capacity of power supply
is not sufficient.
During arranging the wiring layout, specified cables should be used as the mains line, which accords
with the local regulations on wiring. Connecting and fastening should be performed reliably to avoid
the external force of cables from transmitting to the terminals. Improper connection or fastness may
lead to burning or fire accidents.
There must be the ground connection according to the criterion. Unreliable grounding may cause
electrical shocks. Do not connect the grounding line to the gas pipe, water pipe, lightening rod and
telephone line.
Only copper wire can be used. Breaker for electric leakage should be provided, or electric shock
may occur.
The wiring of the mains line is of Y type. The power plug L should be connected to the live wire
and plug N connected to null wire while should be connected to the ground wire. For the type
with auxiliary electrically heating function, the live wire and the null wire should not be misconnected,
or the surface of electrical heating body will be electrified. If the power line is damaged, replace it
by the professional personnel of the manufacturer or service center.
The power line of indoor units should be arranged according to the installation instruction of indoor
units.
The electrical wiring should be out of contact with the high-temperature sections of tubing as to avoid
melting the insulating layer of cables, which may cause accidents.
After connected to the terminal tier, the tubing should be curved into be a U-type elbow and fastened
with the pressing clip.
Controller wiring and refrigerant tubing can be arranged and fixed together.
The machine can’t be powered on before electrical operation. Maintenance should be done while
the power is shut down.
Seal the thread hole with heat insulating materials to avoid condensation.
Signal line and power line are separately independent, which can’t share one line. [Note: the power
line, signal line are provided by users. Parameters for power lines are shown as below: 3×(1.0-1.5)
mm
2
;
parameters for signal line: 2×(0.75-1.25)mm
2
( shielded line)]
5 butt lines (1.5mm) are equipped in the machine before delivery, which are used in connection
between the valve box and the electrical system of the machine. The detailed connection is displayed
in the circuit diagram.
Indoor units and outdoor units should be connected to the power source separately. Indoor units
must share one single electrical source, but its capacity and specifications should be calculated.
Indoor & outdoor units should be equipped with the power leakage breaker and the overflow breaker.
An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be
connected in fixed wiring.
Supply:3N~,380-400V,50/60Hz
L1L2 L3 N
G
Main Unit of Outdoor
Unit
Breaker for
Electricity Leakage
Overflow Breaker
Supply:3N~,380-400V,50/60Hz
Sub Unit 1 of Outdoor
Unit
L1L2 L3 N
G
Breaker for
Electricity Leakage
Overflow Breaker
Supply:3N~,380-400V,50/60Hz
Sub Unit 2 of Outdoor
Unit
L1L2 L3 N
G
Breaker for
Electricity Leakage
Overflow Breaker
L N
1 2
TW3
TW1
L N
1 2
TW3
TW1
Summary of Contents for AWSI-CBV005-N11
Page 24: ......