6
(3) Installation place selection
Installation instruction
Air-conditioner can't be
installed in the place with
flammable gas. Or it will
cause fire hazard.
The outdoor unit should not
be installed at the place
where much water can drop
in.
The unit should be installed at
the strong enough place. Or it will
cause vibration and noise.
• It is better not install the unit
at the below places, or it will
cause damage.
• The place where there is
corrosive gas (spring area, etc).
• The place blowing salty air
(seaside, etc).
• The place existing strong coal
smoke.
• The place with high humidity.
• The place where there is device
emitting Hertzian waves.
• The place where voltage
changes greatly.
• During installation, install
the anti-vibration rubber
between the unit and the
bracket.
The outdoor unit should
not be installed next to
living rooms.
Note:
1. Do not install the unit at the place where the flammable gas will leak.
2. Install the unit at the strong enough place.
3. Install the unit at the flat place.
4. After opening the electric box cover for maintenance, please fix the cover with screw firmly.
(4) Transportation
• During transportation, please don't unwrap the packaging, and move the
unit to the installation location as closely as possible.
• Don't hang the unit only at two points. When hanging the unit, don't sit on
the unit. The unit should be upright.
• When removing the unit with the forklift, put the fork into the special
hole at the bottom of the unit. When being hanged, the rope should be 4
pieces of steel cable with over 6mm diameter.
• Put the cushion at the contact section between steel cable and the unit
against the distortion or damage.
• Forbid lifting the unit by lifting the wood bottom seat.
Note:
When multiple modules are installed, the outdoor unit should be ranked by capacity, the larger
capacity is closer to the main pipe of gather pipe.
Steel cable
Cushion