7

Read Before Installation

Tools/Materials

Use

Notes

Gauge Manifold

Evacuating,refrigerant charging

5.09MPa on the High-pressure side.

Charging Hose

Evacuating, refrigerant charging

Hose diameter larger than the concentional ones.

Refrigerant Recovery Equipment

Refrigerant recovery

Refrigerant Cylinder

Refrigerant charging

Write down the refrigerant type. Pink in color at the top of the cylinder.

Refrigerant Cylinder Charging Port Refrigerant charging

Hose diameter larger than the conventional ones.

Flare Nut

Connecting the unit to piping

Use Type-2 Flare nuts.

Tools/Materials

Use

Notes

Gas leak detector

Detection of gas leaks

The ones for HFC type refrigerant may be used.

Vacuum Pump

Vacuum drying

May be used if a reverse flow check adaptor is attached.

Refrigerant Recovery Equipment

Recovery of refrigerant

May be used if designed for use with R410A.

Flare Tool

Flare machining of piping

Chages have been made in the flare machining dimension.Refer to the next page.

Tools/Materials

Use

Notes

Vacuum Pump with a Check Valve

Vacuum drying

Bender

Bending pipes

Pipe Cutter

Cutting pipes

Torque Wrench

Tightening flare nuts

Only    12.70 (1/2'') and    15.88(5/8'') have a larger flare machining dimension.

Welder and Nitrogen Cylinder

Welding pipes

Refrigerant Charging Meter

Refrigerant charging

Vacuum Gauze

Checking vacuum degree

Tools/Materials

Use

Notes

Charging Cylinder

Refrigerant Charging

Must not be used with R410-type units.

CAUTION

Items to Be Checked

(1). Verify the type of refrigerant used by the unit to be serviced. Refrigerant Type: R410A

(2). Check the symptom exhibited by the unit to be serviced. Look in this service handbook for symptoms relating to the

      refrigerant  cycle.

(3). Be sure to carefully read the safety precautions at the beginning of this document.
(4). If there is a gas leak or if the remaining refrigerant is exposed to an open flame, a noxious gas hydrofluoric acid may

      form. Keep workplace well ventilated.

Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.

Chloride in some types of refrigerants such as R22 will cause the refrigerating machine oil to deteriorate.

Necessary Tools and Materials

Prepare the following tools and materials necessary for installing and servicing the unit.

Necessary tools for use with R410A(Adaptability of tools that are for use with R22 and R407C).
1. To be used exclusively with R410A ( Not to be used if used with R22  or R407C )

2. Tools and materials that may be used with R410 with some restrictions

3. Tools and materials that are used with R22 or R407C that can also be used with R410A

4. Tool and materials that must not used with R410A

Tools for R410A  must be handled with special care, and keep moisture and dust from entering the cycle.

Summary of Contents for AWAU-YUDA060-H13

Page 1: ...OUTDOOR UNIT INSTALLATION MANUAL EN Please read this manual carefully before using this air conditioner Please keep this manual safely for future use R410A AWAU YUDA060 H13...

Page 2: ......

Page 3: ......

Page 4: ...be checked for any damages If the damaged base is not repaired the unit may fall down and cause accidents When need maintenance and repairment call dealer to handle it Incorrect maintenance and repai...

Page 5: ...to run an abnormal cycle and abnormal cycle and cause the unit to burst In the event of a refrigerant gas leak provide adequate ventilation to the room If leaked refrigerant gas is exposed to a heat...

Page 6: ...at flares and flange connections Use liquid refrigerant to charge the system Charge the unit with gas refrigerant will cause the refrigerant in the cylinder to change its composition and will lead to...

Page 7: ...ling draining pipes follow the instructions in the manual and make sure that they properly drain water so as to avoid dew condensation If not installed properly they may cause water leaks and damage t...

Page 8: ...Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R410 type units CAUTION Items to Be Checked 1 Verify the...

Page 9: ...ess If a clutch type flare tool is used to machine flares on units that use R410A make the protruding part of the pipe between 1 0 and 1 5mm Copper pipe gauge for adjusting the length of pipe protrusi...

Page 10: ...il from flowing back into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degre...

Page 11: ...10 Name of Parts Air inlet Air outlet Compressor Inside of unit YUDA060 YUDA060 will be used as brief model name in this manual AWAU H13...

Page 12: ...acles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a strong wind Place surrounded at four sides are not suitable for installation A 1m or more of ove...

Page 13: ...Installation Procedure 3 Installation dimension Unit mm 12 Installation of Outdoor Unit YUDA060 580 25 1250 948 380 340...

Page 14: ...l not to let foreign matters such as sands enter the pipe 4 Piping connection method Forced fastening without centering may damage the threads and cause a gas leakage Model One way piping length Verti...

Page 15: ...M g additional refrigerant per meter That is Refrigerant charging amount L 5m x 45 g m Air Tightness Test When pressurizing for 24 hours a variation of 1 C in the ambient temperature will cause a var...

Page 16: ...the inspection of gas leakge No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed the step 6 If it does not stop gas leakage discharge whole refrigerant...

Page 17: ...broken please change it with the type of T3 15A 250VAC But for YUDA060 the type is T6 3A 250VAC The wiring method should be in line with the local wiring standard The power cable and connecting cable...

Page 18: ...RIC POWER IS SUPPLIED BE SURE TO EXECUTE OFF OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING This unit has a function of automatic restart system after recovering power stoppage 1 Before...

Page 19: ...Troubleshooting 18...

Page 20: ......