15
Outdoor power source and power cable
Item
Model
Power
source
Power cable
section
(mm
2
)
Circuit
breaker
(A)
Rated current of residual
circuit breaker (A)
Ground fault interruptor (mA)
response time (S)
Ground wire
Section
(mm
2
)
Screw
Individual power
1PH,
220-230V~, 50Hz
6
25
25A 30mA below 0.1S
6
M5
1PH,
220-230V~,
50/60Hz
16
50
50A 30mA below 0.1S
16
M5
3N~,
380-400V, 50/60Hz
4
20
20A 30mA below 0.1S
4
M5
4
20
20A 30mA below 0.1S
4
M5
Electric wiring and the application
• Power cable must be fixed firmly.
• Each outdoor must be earthed well.
• When power cable exceeds the range, thichen it appropriately.
Indoor power source and communication wiring
Item
Indoor
total
current (A)
Power cable
section
(mm
2
)
Wire length
(m)
Rated current
of overcurrent
breaker
(A)
Rated current of residual
circuit breaker(A)
Ground fault interruptor(mA)
response time(S)
Communication wire section
Outdoor/indoor
(mm
2
)
Indoor/indoor
(mm
2
)
<10
2
23
20
20A, 30mA, below 0.1s
2-core × (0.75-2.0mm
2
)
shielded wire
≥10 and <15
3.5
24
30
30A, 30mA, below 0.1s
≥15 and <22
5.5
27
40
40A, 30mA, below 0.1s
≥22 and <27
10
42
50
50A, 30mA, below 0.1s
• Power cable and communication wire must be fixed firmly.
• Each indoor must be grounded well.
• When power cable exceeds the range, increase the gauge appropriately.
• Shielded layer of communication wires must be connected together and be earthed at single
point.
• The total length of communication wire cannot exceed 1000m.
Communication wire for wired controller
• The shielding lay of the signal line must be grounded at one end.
• The total length of the signal line shall not be more than 250m.
Length of Signal Line (m)
Wiring Dimensions
≤250
0.75mm
2
× 3 core shielding line
AWAU-YCV080-H11
AWAU-YCV150-H11
AWAU-YCV150-H13
AWAU-YCV180-H13