Power wiring figure
Indoor and outdoor use their individual power source. All indoors use one power source. Must
install the leakage breaker and the over current breaker, or electric shock will occur.
a. Power cable model:
YCV080: H05RN-F; B-YCV150;YCV180: H07RN-F
b. The diameter of earth cable cannot be smaller than power cable's.
c. Power cable must be fixed firmly.
d. Each outdoor must be earthed well.
e. When power cable exceeds the range, thicken it appropriately.
f. The temperature of refrigerant circuit will be high, please keep the power cable away from the
copper tube.
g. An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring.
leakage breaker
L1 L2 L3 N
outdoor
power source: 3N~, 380-400V, 50Hz
L
N
indoor 3
(non wall mounted unit)
power source: 1PH, 220-230V~, 50Hz
L
N
indoor 1
(wall mounted unit)
power source: 1PH, 220-230V~, 50Hz
over current breaker
leakage breaker
over current breaker
L
N
indoor 2
(wall mounted unit)
power source: 1PH, 220-230V~, 50Hz
leakage breaker
over current breaker
over current breaker
leakage breaker
B-YCV150
YCV180
L
N
outdoor
power source: 1PH, 220-230V~, 50Hz
over current breaker
leakage breaker
YCV080
Specs for power cable and communication wire
1PH,
220-230V~,
50Hz
1. Outdoor power source and power cable
YCV080
model
circuit
breaker
(A)
power
cable
section
(mm
2
)
earthing wire
section
(mm
2
)
screw
item
6
M5
power
source
3N~,
380-400V,
50Hz
rated current of residual
current circuit breaker(A)
leakage current (mA)
response time(s)
30A 30mA below 0.1S
6
4
30
20
20A 30mA below 0.1S
4
M5
B-YCV150
YCV180