W: www.aukdistribution.com
T: 0191 516 6553
c֯
15
, set to
Set T4H2
This will give a weather compensated curve of 45 degrees flow temp
degrees
5
2 degrees outside and a Flow temp of 30 degrees at 1
-
at
ambient air temprture
outside
OK
with
d
s to selections must be confirme
All change
Press Back
lect Room Thermostat
Se
tat to
Change Room Thermos
1
Zone
OK
ss
Pre
ss Back Twice to return to the home screen
Pre
To Activate the Weather Compensated Curve entered earlier, the next steps must be followed.
From the main screen press Menu button
Select Pre-set temperature and press
OK
Go across to Weather Temp. Set
Scroll down to Zone1 H-Mode low temp,
Press the
ON/OFF
button to turn on.
Scroll right to the Number 9 and Confirm with
OK
Press Back, until you return to the Home Screen.
Test Mode
The unit can be put into a Test mode, this is done through the SERVICEMAN menu accessed as above.
In the Test mode menu, there are a couple options that can be selected in this menu, these include testing of all Outputs.
This will allow the installer to check the unit has been wired correctly, there is also a handy air purge function within this menu.
We recommend that the air purge function is carried out before initially starting the unit. Please Find below the details
on carrying out this process.
Enter SERVICEMAN mode using the password as
Detailed in the previous section.
Scroll down and Select Test Run with
OK