                Final Operational Checks

 

 

With the unit operating in Central Heating mode the mono bloc unit flow rate, can now be checked, to make sure the minimum 

flow rate is been achieved. 

 

1.

 

Enter SERVICEMAN menu as described in the previous sections. 

2.

 

Select Operation Parameters. 

3.

 

Scroll through and check the minimum flow rate for the unit fitted is been achieved adjust the flow setter 

if required. 

 

 

 

OPERATION  PARAMETER 

#01 

GAS  BOILER 

OFF 

T1  LEAVING  WATER  TEMP. 

35°C 

WATER  FLOW 

1.72m 

3

/h 

HEAT  PUMP  CAPACTIY 

11.52kW 

POWER  CONSUM. 

1000kWh 

Ta  ROOM  TEMP 

25°C 

 

ADDRESS 

3/9 

 

 

 

 

 

 

 

Fault Codes 

 

Error 

code 

 

C7 

Transducer module temperature too high protect 

E0 

Water flow failure (E8 appears 3 times)

 

E1 

Phase sequence error (for 3 phase models)

 

E2 

Communication error between the main control board of hydraulic module and user interface

 

E3 

Backup electric heater exchanger water outlet temperature sensor T1 error

 

E4 

Domestic hot water tank temperature sensor T5 error

 

E5 

Air side heat exchanger refrigerant outlet temperature sensor T3 error

 

E6 

Outdoor ambient temperature sensor T4 error

 

E7 

Balance tank sensor Tbt1 error

 

E8 

Water flow failure within 3 times

 

E9 

Suction pipe temperature sensor Th error

 

EA 

Discharge pipe temperature sensor Tp error

 

Eb 

Solar board sensor Tsolar error

 

Ec 

Balance tank sensor Tbt2 error

 

Ed 

Water side heat exchanger water inlet temperature sensor Twin error

 

Unit 

Minimum Flow 

Rate 

Maximum Flow 

Rate 

AW-WHPMA04-91 

6.64 Lpm* 

0.40 m³h* 

14.16 Lpm 

0.85 m³h 

AW-WHPMA06-91 

6.64 Lpm* 

0.40 m³h* 

20.82 Lpm 

1.25 m³h 

AW-WHPMA08-91 

6.64 Lpm* 

0.40 m³h* 

27.48 Lpm 

1.65 m³h 

AW-WHPMA10-91 

6.64 Lpm* 

0.40 m³h* 

33.32 Lpm 

2.0 m³h 

AW-WHPMA12-91 

11.62 Lpm* 

0.70 m³h* 

41.65 Lpm 

2.50 m³h 

AW-WHPMA14-91 

11.62 Lpm* 

0.70 m³h* 

45.81 Lpm 

2.75 m³h 

AW-WHPMA16-91 

11.62 Lpm* 

0.70 m³h* 

49.98 Lpm 

3.0 m³h 

AW-WHPMA12-91 3ph 

11.62 Lpm* 

0.70 m³h* 

41.81 Lpm 

2.50 m³h 

AW-WHPMA14-91 3ph 

11.62 Lpm* 

0.70 m³h* 

45.81 Lpm 

2.75 m³h 

AW-WHPMA16-91 3ph 

11.62Lpm* 

0.70 m³h* 

49.98 Lpm 

3.0 m³h 

*Please be aware if, only the minimum flow rate is achieved through the unit the unit 
will not function to its full output. 

 

Summary of Contents for AW-WHPMA04-91

Page 1: ...Airwell Typical Installation with Third Party controls Installation and Setup Monobloc system Rev 1 3 March 29th 2022 Draft for Comments...

Page 2: ...ia the third party controller The heat pump controls the domestic hot water temperature itself including an optional sterilization cycle assisted by the immersion heater using a drive open 3 port valv...

Page 3: ...onobloc should be installed on a base suitable for withstanding the weight of the unit and should be level The steel plinth is Structural and MUST NOT be removed There shall be a proper means of dispo...

Page 4: ...y from the PCB This would require an additional 13amp supply and suitably sized cable All supplies should be via a double switched isolator and all cables should be sized in accordance with BS7671 The...

Page 5: ...sed The Domestic Hot water sensor is connected directly to the PCB on plug CN13 There is a flying lead with a plug on for connecting this this is located at the right hand side of the unit As in the p...

Page 6: ...h 1 2 should be set to OFF OFF this will deactivate the IBH internal back up heater is not fitted to the Airwell unit as standard S1 Dip switch 3 4 should be set to OFF OFF this will deactivate the IB...

Page 7: ...terms and conditions Please find further details below 1 Make sure the water hydraulics are piped up in accordance with the manufacturer s instructions 2 Make sure the electrical connections are wired...

Page 8: ...row to SERVICEMAN and press OK Enter the SERVICEMAN code 234 Select DHW MODE SETTING Set DHW Mode to YES DISINFECT should be set YES if the immersion is controlled by the heat pump DHW PRIORITY should...

Page 9: ...to Weather Temp Set Scroll down to Zone1 H Mode low temp Press the ON OFF button to turn on Scroll right to the Number 9 and Confirm with OK Press Back until you return to the Home Screen Test Mode Th...

Page 10: ...he venting process and topped up as required To return to the home screen press Back until the home screen is displayed If point check is selected A number of outputs can be tested manually Scroll dow...

Page 11: ...into Operations In order to put the unit into operation you must turn on the modes within the home screen This is done by selecting the mode highlighting on the main screen and then by pressing the ON...

Page 12: ...tic hot water tank temperature sensor T5 error E5 Air side heat exchanger refrigerant outlet temperature sensor T3 error E6 Outdoor ambient temperature sensor T4 error E7 Balance tank sensor Tbt1 erro...

Page 13: ...llel HE Communication error between main board and thermostat transfer board H F Refrigerant system EEPROM error HH H6 appears 10 times in 120min HP Low pressure protection pressure 0 6MPa for 3 times...

Page 14: ...tion Status AW WHPMA04 91 10 1 A AW WHPMA06 91 11 9 A AW WHPMA08 91 14 9 A AW WHPMA10 91 16 2 A AW WHPMA12 91 24 2 A AW WHPMA14 91 25 22 A AW WHPMA16 91 26 96 A AW WHPMA12 91 3ph 7 94 A AW WHPMA14 91...

Reviews: