25
English
DIP
OFF
ON
STANDARD
1
Pump ON only if the unit is ON
Pump always ON
OFF
2
Step ventilation
Continuous ventilation
OFF
3
Pump Off in antifreeze protection
Pump On in antifreeze protection
ON
4
Discharge of comp. 1
Discharge of comp. 2
OFF
5
Normal
Slave
OFF
6
Ambient temperature compensation
No compensation
ON
7
Enable input 5 pump’ thermal switch
Disable input 5
pack unit = OFF
non pack = ON
8
Forced defrosting OFF
Forced defrosting ON
OFF
9
Serial address
OFF
10
Serial address
OFF
11
Serial address
OFF
12
Serial address
OFF
6.2 Dip Switches
The control is provided with 2 DIP switch blocks: DSW1 (12 dips)
and DSW2 (8 dips).
Function of DSW1 DIPS (user setting)
DSW2 dips setting : only for service technician
Display keys
Display screen
6 - AQL/AQH Control
Display keys
All the information is displayed on 4 displays (7-segments).
Cool and heat setpoint : can be selected inside the standard
parameter menu.
Use the
and
keys to enter the display menus as follows :