En-9

(1) Ceiling concealed type

Gap of 1.5 to 2 m

100 mm or more

Downward gradient  

2.5 to 5.0 mm

Supporter

Locally arranged pipe

GOOD

VP25 [O.D 32 mm 
or more]

Air bleeding

Rise

PROHIBITED

Trap

Observe the following procedures to construct centralized drain pipe 

fi

 ttings.

VP30 or more 
[O.D 38 mm or more]

Downward gradient 
1/100 or more

(2) Wall mounted type/Floor standing concealed type

100 mm 

or more

Downward gradient 

2.5 to 5.0 mm

Locally arranged pipe

GOOD

VP25 [O.D 32 mm 

or more]

Air bleeding

Rise

PROHIBITED

Trap

Observe the following procedures to construct centralized drain pipe 

fi

 ttings.

VP30 or more 
[O.D 38 mm or more]

Downward gradient 1/100 
or more

5.2. Install the drain pipe

(1)  Be sure to use supplied Drain hose 

1

 and Hose band 

2

 

2

 Hose band (Accessories)

Drain 
hole

1

 Drain hose (Accessories)

Hard PVC side 

Hose band

4 mm or less

20 mm

2

 Hose band

1

 Drain hose

Fasten the Hose band 

2

 at the position where 

horizontal against earth (ground).
The Hose band 

2

 must be positioned at the right 

side of the Drain hose 

1

 as in the 

fi

 gure.

(2)  Be sure to connect Drain pipe with adhesive (polyvinyl chloride) so that there is no 

leakage.

Applying 
area of 
adhesive

Joint pipe 
(Field supply)

Drain pipe (VP25) 

(Field supply)

4 mm or less

 

CAUTION

Do not connect to the Drain hole with adhesive. Using adhesive may cause damage 
and water leaks.

(3)  After installing the Drain hose 

1

, check if the drainage is smooth.

 

CAUTION

To prevent excessive force on Drain hose 1, avoid bends or twists. (To bend or twist 
may cause water leaks.)

(4)  After checking for drainage, attach the Drain hose insulation B 

3

 to insulate, following 

the instructions as in the 

fi

 gures.

To avoid space with Drain hose 

1

 and Hose band 

2

, press 

fi

 rmly the Drain hose 

insulation B 

3

.

3

 Drain hose insulation B 

(Accessories)

Ensure there is 
no space.

9374342341-01_IM.indb   Sec1:9

9374342341-01_IM.indb   Sec1:9

30/01/2013   17:05:35

30/01/2013   17:05:35

Summary of Contents for ARXD04GALH

Page 1: ...Espa ol MANUEL D INSTALLATION MANUAL DE INSTALACI N APPAREIL INT RIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Itali...

Page 2: ...may occur After turning off the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service personnel to repairs W...

Page 3: ...mpleted Do not discard any accessories needed for installation until the installation work has been completed Name and Shape Q ty Application Operating Manual 1 Installation Manual 1 This book Install...

Page 4: ...sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space...

Page 5: ...must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to pr...

Page 6: ...ion which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall...

Page 7: ...sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be...

Page 8: ...the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool excl...

Page 9: ...parts Check for proper drainage after the construction by using the visible portion of transparent drain port and the drain piping final outlet on the body CAUTION Do not apply adhesive agent on the...

Page 10: ...ories Hard PVC side Hose band 4 mm or less 20 mm 2 Hose band 1 Drain hose Fasten the Hose band 2 at the position where horizontal against earth ground The Hose band 2 must be positioned at the right s...

Page 11: ...insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit or RB unit Erroneous wiring m...

Page 12: ...ssion Transmission Power supply Breaker Power supply Remote controller Master Remote controller Slave Remote controller Breaker Breaker Indoor unit Remote control 2 2 2 3 3 3 Indoor unit Indoor unit 1...

Page 13: ...orque M3 screw Transmission X1 X2 Remote controller Y1 Y2 Y3 0 5 to 0 6 N m 5 to 6 kgf cm CAUTION To peel the film from the lead cable use a dedicated tool that will not damage the conductor cable Whe...

Page 14: ...he current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage t...

Page 15: ...Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate external dimension depending on the number of...

Page 16: ...Set the Setting Number to 02 Refer to 7 7 Function setting for details about Function Number and Setting Number 1 6 7 IR receiver unit Optional parts For the installation method please refer to the IN...

Page 17: ...AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD 1 Factory setting 0 Rotary switch REF AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD S...

Page 18: ...ing information Function Number Setting Number Setting Static Pressure 26 00 0 Pa 01 10 Pa 02 20 Pa 03 30 Pa 04 40 Pa 05 50 Pa 06 60 Pa 50 Pa 07 70 Pa 50 Pa 08 80 Pa 50 Pa 09 90 Pa 50 Pa 31 25 Pa Fact...

Page 19: ...temperature use setting 02 01 Adjust 1 02 Adjust 2 Heat air temperature trigger 31 00 Default Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 T...

Page 20: ...s Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller UTY RNKY UTY RNK...

Reviews: