background image

En-8

Tighten with 2 wrenches.

Holding wrench

Flare nut 

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

4.4. Installing heat insulation

Install the heat insulation material after performing a refrigerant leak check (see the In-
stallation Manual for the outdoor unit for details).

4.4.1. COUPLER HEAT INSULATION

•  Insulate by the coupler heat insulation (Accessories) around the gas pipe and liquid 

pipe of indoor side.

•  After installing the coupler heat insulation, wrap both end with vinyl tape so that there 

is no gap.

• After af

fi

 xing the coupler heat insulation, secure it with 2 cable ties (large), one on 

each end of the insulation.

•  Make sure that the cable ties overlap the heat insulation pipe.

Coupler heat 
insulation 
(Accessories)

Cover this portion with 
heat insulation.

cable tie (Large) 
(Accessories)

Heat insulation

 

CAUTION

After checking for gas leaks (refer to the Installation Manual of the outdoor unit), 
perform this section.

Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do 
so may cause water leaks.

5.  INSTALLING DRAIN PIPES

 

WARNING

Do not insert the drain piping into the sewer where sulfurous gas occurs. (Heat 
exchange erosion may occur)

Insulate the parts properly so that water will not drip from the connection parts.

Check for proper drainage after the construction by using the visible portion of 
transparent drain port and the drain piping 

fi

 nal outlet on the body.

 

CAUTION

Do not apply adhesive agent on the drain port of the body.
(Use the attached drain hose and connect the drain piping)

5.1A. When drain pump is used

•  Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].
•  Do not perform a rise, trap and air bleeding.
•  Provide a downward gradient (1/100 or more).
•  Provide supporters when long pipes are installed.
•  Use an insulation material as needed, to prevent the pipes from freezing.
•  Install the pipes in a way that allows for the removal of the control box.

Gap of 1.5 to 2 m

700 mm or less

Horizontal or 

upward gradient

Supporter

Max. 300 mm

Locally arranged pipe

GOOD

VP25 [O.D 
32 mm or more]

Rise

Air bleeding

PROHIBITED

Trap

Observe the following procedures to construct centralized drain pipe 

fi

 ttings.

VP30 or more [O.D 38 mm or more]

Downward gradient 1/100 or more

700 mm or less

5.1B. When drain pump is not used (Natural 

drainage)

 

CAUTION

Set “7.4. Switching of drainage function”
Drain pump cannot be used if it is installed in wall mounted type/floor standing 
concealed type.

If the drain pump is not used, please replace with the drain cap.

Wall mounted type / 

Floor standing concealed type

Ceiling concealed type

•  Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32 mm].
•  Do not perform a rise, trap and air bleeding.
•  Provide a downward gradient (1/100 or more).
•  Provide supporters when long pipes are installed.
•  Use an insulation material as needed, to prevent the pipes from freezing.
•  Install the pipes in a way that allows for the removal of the control box.

9374342341-01_IM.indb   Sec1:8

9374342341-01_IM.indb   Sec1:8

30/01/2013   17:05:32

30/01/2013   17:05:32

Summary of Contents for ARXD04GALH

Page 1: ...Espa ol MANUEL D INSTALLATION MANUAL DE INSTALACI N APPAREIL INT RIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Itali...

Page 2: ...may occur After turning off the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service personnel to repairs W...

Page 3: ...mpleted Do not discard any accessories needed for installation until the installation work has been completed Name and Shape Q ty Application Operating Manual 1 Installation Manual 1 This book Install...

Page 4: ...sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space...

Page 5: ...must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to pr...

Page 6: ...ion which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall...

Page 7: ...sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be...

Page 8: ...the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool excl...

Page 9: ...parts Check for proper drainage after the construction by using the visible portion of transparent drain port and the drain piping final outlet on the body CAUTION Do not apply adhesive agent on the...

Page 10: ...ories Hard PVC side Hose band 4 mm or less 20 mm 2 Hose band 1 Drain hose Fasten the Hose band 2 at the position where horizontal against earth ground The Hose band 2 must be positioned at the right s...

Page 11: ...insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit or RB unit Erroneous wiring m...

Page 12: ...ssion Transmission Power supply Breaker Power supply Remote controller Master Remote controller Slave Remote controller Breaker Breaker Indoor unit Remote control 2 2 2 3 3 3 Indoor unit Indoor unit 1...

Page 13: ...orque M3 screw Transmission X1 X2 Remote controller Y1 Y2 Y3 0 5 to 0 6 N m 5 to 6 kgf cm CAUTION To peel the film from the lead cable use a dedicated tool that will not damage the conductor cable Whe...

Page 14: ...he current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage t...

Page 15: ...Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate external dimension depending on the number of...

Page 16: ...Set the Setting Number to 02 Refer to 7 7 Function setting for details about Function Number and Setting Number 1 6 7 IR receiver unit Optional parts For the installation method please refer to the IN...

Page 17: ...AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD 1 Factory setting 0 Rotary switch REF AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD S...

Page 18: ...ing information Function Number Setting Number Setting Static Pressure 26 00 0 Pa 01 10 Pa 02 20 Pa 03 30 Pa 04 40 Pa 05 50 Pa 06 60 Pa 50 Pa 07 70 Pa 50 Pa 08 80 Pa 50 Pa 09 90 Pa 50 Pa 31 25 Pa Fact...

Page 19: ...temperature use setting 02 01 Adjust 1 02 Adjust 2 Heat air temperature trigger 31 00 Default Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 T...

Page 20: ...s Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller UTY RNKY UTY RNK...

Reviews: