En-8
WARNING
Install an earth leakage breaker. In addition, install the earth leakage breaker so that
the entire AC main power supply is cut off at the same time. Otherwise, electric shock
or
fi
re could result.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable
fi
rmly to the terminal board. Imperfect installation may
cause a
fi
re.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly quali
fi
ed persons in order to avoid a hazard.
CAUTION
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cables to the transmission or remote controller
terminals, as this will damage the product.
Never bundle the power supply cable and transmission cable, remote controller cable
together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of
the PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor unit for more than 10 seconds to discharge static
electricity charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.
1
6.1. Electrical requirement
Voltage rating
230 V
Operating range
198 to 264 V
• Select the power cable type and size in accordance with relevant local and national
regulations.
• Speci
fi
cations for local wiring power cord and branch wiring are in compliance with local
code.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Refer to the table for the breaker speci
fi
cations of each installation condition. Perform
the power crossover wiring within the range of the same refrigerant system. When the
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B
below.
A. Current breaker requirements
Model
MCA
MFA
AB
□
A30GATH
0.52 A
20 A
AB
□
A36GATH
0.66 A
AB
□
A45GATH
0.98 A
AB
□
A54GATH
1.32 A
MCA: Minimum Circuit Ampacity
MFA: Main Fuse Ampacity
When the power crossover wiring is done, make it so that the total of the MCA of the
connected RB units and indoor units does not exceed the 15 A. For RB unit MCA, refer to
the RB unit installation manual.
If the capacity of connected RB units and indoor units exceeds the upper limit, either add
breakers or use a breaker with a greater capacity.
B. Earth leakage breaker requirements
Breaker capacity
* Maximum connectable “indoor units” or
“indoor units + RB units”
30 mA, 0.1 sec or less
44 or less **
100 mA, 0.1 sec or less
45 to 128
* Heat pump type: indoor units, Heat recovery type: indoor units and RB units.
** If the total number of units connected to the breaker exceeds 44, either add a 30mA
breaker, or use breakers with a greater capacity.
6.1.1. Cable speci
fi
cations
Follow the speci
fi
cations below for the power supply, transmission and remote controller
cable.
Recommended
cable size (mm
2
)
Cable type
Remark
Power
supply cable
2.5
Type245 IEC57
or equivalent
1ø 50 Hz
198 to 264 V
2 Cable + earth (ground)
Transmission cable
0.33
LONWORKS
compatible cable
22 AWG
LEVEL 4 (NEMA)
non-polar 2 core,
twisted pair solid core
diameter 0.65 mm
Remote controller
cable
(2-wire type)
0.33 to 1.25
Sheathed PVC cable*
Non polar 2 core
Remote controller
cable
(3-wire type)
0.33
Sheathed PVC cable*
Polar 3 core
*: Use shielded cable in accordance with local rules for
remote controller cable.
]1
6.2. Wiring method
(EXAMPLE)
*1: When connecting to the Heat Recovery System, refer to the installation manual of
the RB unit.
*2: Earth (Ground) the remote controller if it has an earth (ground) cable.
*3: When connecting the 2-wire type remote controller, Y3 is not used.
Outdoor unit or RB unit *1
Transmission
Power supply
Remote controller
(Master)
Remote controller
(Slave)
Remote
controller
(Crossover wiring of power supply)
Power supply
Breaker
Indoor unit
Power supply
Pull box
Power supply
Pull box
Power supply
Power supply
Indoor unit
Indoor unit
Breaker
Breaker
Remote
control
*2
*2
*2
*3
*3
*3
Indoor unit
Indoor unit
Indoor unit
Transmission
Breaker
* Earth (Ground) the remote controller if it has an earth (ground) wire.
Connect the earth (ground) wire of the remote controller to the earth (ground) terminal of
transmission.
1
6.3. Unit wiring
Before attaching the cable to terminal block.
6.3.1. Power supply cable
Adjust the length of power supply cable to avoid excessive tension with referring
fi
gure
below.
Earth (Ground) cable
20 mm
45 mm
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after looping it
around the end of the cable.
(2) Use the speci
fi
ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.