background image

14

3.4. 

Ducts and Grilles

The materials needed and method of fitting the ducting 
depend on the unit, the options chosen and the customer’s 
order.

For this reason, we can provide only general instructions 
for fitting the ducts. 

The length of the ducting is calculated on the basis of the 
thickness of the wall/dimensions of the roof.

NB! At the AM 1000 (Versions H, S1, S2) you have to 
use Ø400 wall grilles and reduction pieces Ø400 to 
Ø315 inside the wall.

NB! Please note that the duct holes in the wall must 
have an outward downward gradient of 1-2% to 
prevent heavy rain from entering the unit.

NB! The supply air grille for unit versions S1 and S2 
should be installed with the slats facing down and 
the exhaust air grille with vertical slats facing right.

NB! Exhaust air ducts and supply air ducts must be 
insulated against condensation on the ducts, if they 
are within the building envelope. The extract air 
ducts and inlet air ducts must be insulated against 
temperature loss and condensation forming inside 
the ducts if they are mounted outside the building 
envelope, or run through an unheated room.

NB! Condensation and heat insulation should be 
performed according to standards and rules in effect.

NB! Fire requirements according to standards and 
rules in effect must be observed.

NB! The installation of ventilation ducts should be 
performed according to standards and rules in effect.

NB! Exhaust air ducts and supply air ducts must be 
insulated against noise if they are visible.

Finally, fit a suitable circular grille with the slats pointing 
downwards on the outside of the outer wall or a roof cap 
up on the roof.

To avoid an increase in noise level, it is important that the 
ducts should not get twisted or compressed against the 
supply air spigot and the exhaust air spigot of the unit.

NB! Remember to seal around the penetrations. See 
section “Sealing the Gaps Around Ducts”.

3.5. 

Roof Cap

2

3

1

Fit roof caps on the roof to finish off the installation of 
exhaust and supply through a roof. Installation will depend 
on the roof construction (3). The illustration shows which 
roof caps are for exhaust (1) and supply (2).

NB! Fire requirements for the installation of multiple 
systems must be observed according to the standards 
and rules in effect.

3.6. 

Sealing the Gaps Around Ducts

Sealing of the gaps around ducts is performed as shown 
in the sectional drawing below.

1

2

3

4

5

2

5

4

Application of a seal (shown here on a model with wall 
ducts) is important at the ducts (3) indside and the outside 
edges (4) in order to prevent draughts between the unit 
(1) and the wall/roof (2) as well as between the ducts (3) 
and the wall/roof (2).

Sealing on the inside between the pipes (3) and the wall/

Summary of Contents for AM 1000

Page 1: ...1 2 3 AM 1000 INSTALLATION...

Page 2: ...unit should not be used without the filters specified in the Operator s Manual The manufacturer cannot be held liable for damage arising from use or installing in contravention of these instructions T...

Page 3: ...Sealing the Gaps Around Ducts 14 3 7 Fitting of Panels 15 3 8 Installation Check 15 Appendix 1 Dimensional Drawings 16 AM 1000 HH T 16 AM 1000 HH B 17 AM 1000 HH DIDE 18 AM 1000 HS2 T 19 AM 1000 VV T...

Page 4: ...4...

Page 5: ...note 1 Airmaster air handling unit 4 sections 2 Wall Ceiling frame 3 3 split service cover 4 Panel set a set consists of one to three long panels and double that number of short panels 5 Control panel...

Page 6: ...re restored and fully functional once the unit has been installed NB Read this section Installation fully before start ing installation NB The wall to which the unit is fitted must have an evensurface...

Page 7: ...toration of the function of the vapour barrier is optional available and can be delivered by Airmaster Important Ductholesinthewallmusthaveanoutward downward gradient of 1 2 to prevent heavy rain from...

Page 8: ...al fit the wall frame if necessary 3 Mark the holes for the ducts according to Appendix 1 Dimensional Drawings 4 Drill all marked holes NB Thedrillingofholes sizeoftheholesandmaterials used for fittin...

Page 9: ...hes to thesection Thisunderlaymayforexamplebestrong clean cardboard or equivalent NB Avoid damaging the profile in the middle of the centre section 2 Push the section against the wall frame and screw...

Page 10: ...ction 9 Fasten the section to the centre section Two bolts are mounted in the left section and three screws are supplied loose with the sections 10 Lift the right section using appropriate lifting equ...

Page 11: ...ection wires and secure them at the control box 17 Lift the base plate to its top position and secure it 18 Lift the front section using appropriate lifting equipment to the centre section NB Whenlift...

Page 12: ...x 2 through the cable strip 3 to the side of the right section of the air handling unit NB Do not bend the condensate drain hose 25 Lead the condensate drain hose out of the front section at the right...

Page 13: ...strong clean cardboard or equivalent 30 Lift the side covers to the centre covers one at a time using appropriate lifting equipment Hang the service cover slanted on to the side cover push it up again...

Page 14: ...andards and rules in effect must be observed NB The installation of ventilation ducts should be performed according to standards and rules in effect NB Exhaust air ducts and supply air ducts must be i...

Page 15: ...ent has been fitted and connected and the functions of the unit thoroughly tested Press the panels to the clips on the unit until they attach securely to the clips The perforated circles in the side a...

Page 16: ...6 579 14 70 260 330 330 240 90 14 397 36 87 45 87 41 250 66 42 156 1770 262 i k h Appendix 1 16 Appendix 1 Dimensional Drawings AM 1000 HH T 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling f...

Page 17: ...579 14 70 260 330 330 240 90 14 397 45 427 41 250 66 42 156 629 35 1160 35 466 i k h 2 5 6 7 3 8 4 1 9 B Appendix 1 17 AM 1000 HH B 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling frame 6 C...

Page 18: ...90 14 397 976 30 629 35 1160 35 466 34 36 87 1162 219 45 87 41 250 66 42 156 1770 262 i k h 3 8 6 7 2 5 1 4 9 B Appendix 1 18 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling frame 6 Condensa...

Page 19: ...579 14 70 260 330 330 240 90 14 397 976 30 629 35 1160 35 466 219 45 87 41 42 156 250 66 2008 262 i h Appendix 1 19 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling frame 6 Condensate drain 7...

Page 20: ...6 250 66 h 1770 262 i k 1214 1244 315 2325 560 315 6 2 8 3 6 7 5 4 1 9 B Appendix 1 20 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling frame 6 Condensate drain 7 Electrical Connections 8 Cei...

Page 21: ...56 251 h 1770 262 i k 315 2295 560 1214 1244 2325 1199 315 6 6 7 3 1 2 8 4 5 9 B Appendix 1 21 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling frame 6 Condensate drain 7 Electrical Connectio...

Page 22: ...41 250 66 42 156 34 h 1770 262 i k 2370 2325 560 1214 1244 315 783 257 315 315 6 Appendix 1 22 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling frame 6 Condensate drain 7 Electrical Connectio...

Page 23: ...50 66 42 156 629 35 1160 35 466 262 i h 1214 1244 347 1199 315 560 2310 2325 315 6 Appendix 1 23 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling frame 6 Condensate drain 7 Electrical Connect...

Page 24: ...0 90 14 397 629 35 1160 35 466 976 30 36 87 34 45 427 41 520 262 257 250 66 42 156 3 6 7 5 1 2 8 4 9 B Appendix 1 24 1 Exhaust 2 Supply 3 Inlet 4 Extract 5 Wall frame Ceiling frame 6 Condensate drain...

Page 25: ...H HREHRE VH S1S2 S1RES2RE HV VV VS2 HS1 VS1 HS2 2 2 2 2 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1 1 1 1 T B DI DE DIDE 3 4 3 3 3 3 4 4 4 4 Appendix 1 25 Model Versions AM 1000 1 Exhaust 2 Supply 3 Inlet 4 Extract...

Page 26: ...258 315 1162 257 583 315 257 1162 783 258 583 315 315 87 305 1464 305 163 260 36 1353 113 305 215 305 109 260 36 114 128 Appendix 1 26 Version DI Version DE Version DIDE Version HREHRE Version S1RES2...

Page 27: ...325 16 0 325 16 0 60 251 30 30 1500 1500 2 1 2 1 325 16 0 325 16 0 60 251 1500 1500 2 1 2 1 60 mm 60 mm Appendix 1 27 Holes to be Drilled for Air Ducts VV VH VS1 VS2 1 Exhaust 2 Supply...

Page 28: ...14157 Version 2018 01 09 Industrivej 59 Tel 45 98 62 48 22 info airmaster dk DK 9600 Aars Fax 45 98 62 57 77 www airmaster as com Denmark...

Reviews: