AirMaid 10000V Installation, Operation And Maintenance Manual Download Page 5

4

5

 2.  PLANNING YOUR  INSTALLATION

Selecting the Correct AirMaid

Choose the AirMaid model from the following table based upon the total duct airflow for the application. If the duct has 

several branches, equip each branch with the correctly sized model for its airflow. In this way we maintain a consistent 

concentration of ozone (typically from 0.5 to 1.0 ppm) throughout all sections of the duct system. For larger airflows, 

simply install several units in parallel. For restaurants with a higher than average grease or odor discharge, please consult 

with your nearest AirMaid sales representative for recommendations for your specific application.

AirMaid 

Ozone Capacity 

Max Exhaust Treated 

Use parallel units for higher airflow

             Bleed Airflow

           

                      

     

.

        Specification                Target

Pressure Drop 

(ΔP @ Target Bleed rate)

2000V 

2000 mg/h 

600 cfm

30–50 cfm          40 cfm

0.40 inH

2

O

5000V 

5000 mg/h 

1500 cfm 

30–50 cfm          40 cfm

0.40 inH

2

O

10000V 

10000 mg/h 

3000 cfm 

45–85 cfm          75 cfm

0.75 inH

2

O

20000V 

20000 mg/h 

6000 cfm 

90–170 cfm        150 cfm

0.48 inH

2

O

Inlet Air Supply (Bleed Air): Adjust to the "Target Bleed Airflow" when able

Filtered Air. The air supplied and bled through the AirMaid generator is the “fuel“ to create its ozone and must be filtered. 

To minimize equipment maintenance, use an air source with the least pollutants. Inlet air is preferred taken from a filtered 

central ventilation or MUA supply. If this is not possible, then a filter box satisfying at least class MERV5/EU3 shall be in-

stalled. Filter box inlet air can be taken from above an inner ceiling, from an adjoining space, or from the outdoors with 

precautions taken to prevent the entry of moisture. If taken from the outdoors, never position the inlet in the vicinity of the 

discharge from any ventilation system which commonly contain moisture and pollutants. If air must be taken from inside a 

kitchen space, please position the intake the farthest distance possible from preparation or cooking areas. The temperature 

of the inlet air shall never exceed 104°F.

Bleed Airflow. With the extraction fan running the airflow through each inlet pipe must always fall within the specification:  

45–85 cfm per inlet pipe (Models 10000V and 20000V), 30–50 cfm (Models 2000V and 5000V).

When used in conjunction with VAV/VSD systems, if the total Bleed Airflow through the AirMaid generator drops below 

the minimum specification at the lowest extraction fan speed then power to AirMaid must then be cut off.

Static Pressure: -0.08 inH

2

O to -40 inH

2

O

With the extraction fan running the Static Pressure inside the generator, when measured at the Pressure Check Point 

(locations marked in 

RED

), must always fall within the specification: -0.08 inH

2

O to -40 inH

2

O. This is necessary for 

correct and reliable operation of the internal Pressure Safety Switch.

When used in conjunction with VAV/VSD systems, the Static Pressure must fall within specifications even at the lowest 

extraction fan speed or the power to AirMaid must then be cut off.

1x40 CFM TARGET

2000V/5000V

2x75=150 CFM

TARGET 20000V

1x75 CFM TARGET

10000V

INLET

INLET

INLET

Pressure Check Point

Pressure Check Point

Summary of Contents for 10000V

Page 1: ...stallation Operation and Maintenance AirMaid V Series Ozone Cleaning System NORTH AMERICAN 120 VAC 2000V 5000V 10000V 20000V AirMaid ozone cleaning system Innovative Air Treatment Revised February 14...

Page 2: ...2...

Page 3: ...and extraction ducts must be installed by qualified per sonnel in compliance with all manufacturer instructions as well as local state and national building electric and fire safety codes Troubleshoo...

Page 4: ...generator 4 If the regular inspection and cleaning maintenance for the product are not followed 5 Any other damage resulting from accident alteration misuse if the serial number is removed or defaced...

Page 5: ...EU3 shall be in stalled Filter box inlet air can be taken from above an inner ceiling from an adjoining space or from the outdoors with precautions taken to prevent the entry of moisture If taken fro...

Page 6: ...e point of exhaust With this in mind we recommend a minimum dwell time of 2 seconds to obtain good results for the reduction of cooking odor However please keep in mind that a longer dwell time will o...

Page 7: ...THIS TYPICAL INSTALLATION DETAIL IS FOR REFERENCE ONLY THE PROJECT SPECIFIC INSTALLATION MUST MEET ALL LOCAL STATE AND NATIONAL BUILDING ELE CTRIC AND FIRE SAFETY CODES LAYOUT SHOWN IS COMPLIANT WITH...

Page 8: ...nlet and outlet pipes Multiple duct connections are unnecessary As long as you have sufficient static pressure to obtain the correct bleed airflow through the generator then multiple connections to th...

Page 9: ...ownward Never screw or drill through the generator Hang using 5 16 in threaded rods and anchor these with nuts on each side of the respective bracket 2 Fasten the outlet pipe 6 between the ozone gener...

Page 10: ...eir own alarm panel Electrical Connection The installation must be performed by an authorized electrician and follow national standards and regulations The fan interlock displayed on the diagram below...

Page 11: ...if you choose not to accept their factory defaults ALARM DELAY 5 minutes INSP CLEAN 12 months 4 Perform Functional Check Of CGC Cell s 4 1 Ensure the ventilation system of the facility is running norm...

Page 12: ...on with Interzon 7 1 Register the generator online within 10 days installation at www interzon com Registering the AirMaid generator installation is important to both the reseller and end customer Fir...

Page 13: ...em with the static pressure Kitchen hood filters might not be installed properly or a fire damper or control damper if installed is not open Perform troubleshooting following the flow chart in section...

Page 14: ...the delay is set to 5 minutes in order to prevent an alarm in case of a temporary disruption SET INSP CLEAN Service and maintenance interval in months After this time period the alarm panel will blin...

Page 15: ...if cleaning is performed before the timed reminder is displayed 1 Number of registered events 2 Cause A Alarm C Calibration P Pressure Fault N Not Connected generator not detected 3 Event Duration 4...

Page 16: ...the glass electrodes of the ozone cells are not damaged or cracked A proper ozone cell should be clean and free from any mechanical damage according to the picture to the right above Caution The glas...

Page 17: ...ired negative pressure is established The thermal switch prevents the ozone generator from overheating The main switch is supplied with a thermal overload protection of 4A Facts about Ozone Ozone is a...

Page 18: ...or Troubleshooting completed Turn off the main power switch and remove the service hatch on the bottom of the generator Are all electrodes of the CGC Cell s free from damage Please perform the steps i...

Page 19: ...one E mail Product Identification Model AirMaid 2000V AirMaid 5000V AirMaid 10000V AirMaid 20000V Product Serial No Date of installation mm dd yyyy From Commissioning Generator Airflow cfm Generator P...

Page 20: ...6 8 544 444 39 SE 183 62 T by Stockholm E mail info interzon com Sweden Internet www interzon com Reproduction modification or translation without a prior written consent is forbidden with the excepti...

Reviews: