background image

 

14 

 

 Installation and Operating Instructions                                                                                         

        

CHAPTER 8 
 

CARE AND 
MAINTENANCE

 

 
 
 
 
 
 
 
 
 
 
 
 

8.0 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Care and maintenance  

Safety instructions listed in Chapter 1.2 must be observed! 

Prior to all work always ensure that the fan unit is isolated from the 
power supply and secured against restarting! 

In principle the devices are maintenance-free; the unit is not user 
serviceable. Nevertheless all necessary maintenance work must be carried 
out by qualified electricians! 

Excessive deposits of dirt, dust, fats etc. on the impeller, motor, protective 
grids and especially between housing and impeller are not allowed; as it can 
lead to heavy imbalance in the impeller, overheat the motor or even block 
the impeller. In those instances the device has to be cleaned.     

In case of no longer use the unit must be serviced before operation.  

 

Should be examined: 

  Secure mounting of the fan / replace if in doubt 

  Remove contaminant deposits   

  Mechanical damage, shut down the device, replace damage parts  

  Firm seating of bolt connections, loosen screws  

  Housing quality (cracks, brittleness of the plastic)  

  Overrunning of the impeller, the impeller doesn`t run freely, note 

possible causes of failure in Chapter 8.1 

  Bearing noise 

  Vibrations – see Chapter 8.1 

  Power consumption according to the specifications on the type plate – 

see Chapter 8.1 

 

8.1 

Decommissioning and disposal 
Safety instructions listed in Chapter 1.2 should be observed! 
During transportation safety instructions listed in Chapter 1.4 should be 
observed.  

 

Parts  and  components  of  the  fan  which  have  reached  the  end  of  their 
lifespan,  for  instance  because  of  the  wear  and  tear,  corrosion,  mechanical 
loading,  fatigue  and/or  other  effects  that  could  not  be  directly  discerned, 
should  be  disposed  in  accordance  with  local  and  international  laws  and 
regulations. The same applies to auxiliary materials such as oils, greases or 
other substances. The conscious or unconscious re-use of used components 
such  as  impellers,  bearings,  belts,  etc.  may  endanger  persons,  the 
environment  as  well  as  the  equipment  itself.  Relevant  local  operating 
regulations should be observed and applied. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 DANGER

 

CAUTION 

 DANGER

 

Summary of Contents for QT 150T

Page 1: ...Instructions QuietAir 150mm Axial Fan MODEL QT 150T TwoSpeed Fan 220 260m3 hr With Delay Start and Adjustable Timer control Basic Switching with timer Low Energy Quiet Long Life Extra Safe Interval Ti...

Page 2: ...ion Chapter 3 SPECIFICATIONS DIMENSIONS 3 0 Specifications 3 1 Product lifetime 3 2 Accessories 3 3 Dimensions Chapter 4 FUNCTION 4 0 Function description Chapter 5 CLEANING DEINSTALLATION 5 0 Cleanin...

Page 3: ...applicable safety and accident prevention regulations should be observed All electrical work and commissioning should be carried out by authorized and qualified electricians Maintenance and installati...

Page 4: ...the necessary notification of claim immediately has to be reported to the carrier Any delay in complaint will result in a loss of benefit entitlement 1 7 Storage When storing for a long period of tim...

Page 5: ...n work must be carried out only by an approved electrician The QT150T should not to be used by children and persons with reduced physical mental or sensory capacities without proper practical experien...

Page 6: ...Protection class II Power input W 10 6 Weight approx kg 1 2 Rated current mA 100 70 Rotational speed 1900 1600 Flow volume m3 h 260 220 Shut down min 6 10 15 21 adjustable Interval H 0 8 12 24 adjust...

Page 7: ...ges the run on time will be ignored By mutual shut down of the both stages the run on time will be considered only when time function will be activated on both stages 4 Intermittent operation The fan...

Page 8: ...8 Installation and Operating Instructions All of the following information and instructions are intended for use by authorized electricians Fig 1 Fig 2...

Page 9: ...lation unit After unpacking and before installation the following points must be checked if any transport damage is noticed broken or bent parts free rotation of the impeller 6 2 Installation The QT15...

Page 10: ...on Commissioning Safety instructions listed in Chapter 1 2 should be observed All electrical installations to be carried out by an approved electrician in accordance with presented manual and wiring d...

Page 11: ...of the device Check the rotation of the impeller All parts of the fan especially screws and protective grid must be checked for tightness Do not mislay the screws included with the unit Ensure that t...

Page 12: ...tches 7 and 8 are activated 4 Push button operation If there is no switch on delay DIP 1 2 off off activated then switch inputs 1 or 2 can be controlled by a push button For this relevant stage time f...

Page 13: ...pon connection of the operating voltage the fan is for 1 min in a test mode prerequisite DIP switches factory settings see SS 1081 In this case switch on delay and run on time functions are within the...

Page 14: ...parts Firm seating of bolt connections loosen screws Housing quality cracks brittleness of the plastic Overrunning of the impeller the impeller doesn t run freely note possible causes of failure in C...

Page 15: ...ng Winding is short circuiting the motor Contact Airflow Technical Support Damaged cable or connector Replace parts if necessary replace motor Contact Airflow Technical Support Connected incorrectly C...

Page 16: ...nected to an unsuitable electrical supply 3 Has not been subjected to issue neglect or damage 4 Has not been modified or repaired by any person not authorised by Airflow Developments Ltd 5 Has been in...

Page 17: ...ement by an assessed and registered Competent Person should follow a Best Practice process and adopt air flow measurement Method A The Unconditional Method using a suitable UKAS certified measuring in...

Reviews: