CHAPTER 4 
 

FUNCTION

 

 
 

4.0 

 
 
 
 
 

Function description  
 
All  of  the  following  information  and  instructions  are  intended  for  use  by 
authorized  electricians.  All  times  may  vary  slightly  due  to  component 
tolerances and ambient temperatures. 
 
Exceed of the humidity threshold or demand ventilation  caused by switching 
the  switch  will  lead  to  the  turning  on  of  the  fan.  The  required  ventilation  is 
superior to the humidity control. 
 
Automatic mode: 

The humidity control works without connecting a switch.

 

Demand ventilation: 

By connecting e.g. a 2 speed switch from the Airflow range of 

accessories the fan can be used on different speed levels 1 and 2. The use of the 
switch is consistent with the functions of the fan by default.  
The speed of the fan level is continuously adjustable (factory setting Level 1 - 70%, 
Level 2 - 100% of the maximum speed). The adjustment applies to both - demand 
ventilation  as  well  as  for  the  humidity  control.  In  order  to  ensure  a  sufficient 
dehumidification, the rotational speed is in the automatic mode, but always at least 
50%  in  the  low  stage  and  at  least  80%  in  the  high  stage,  even  with  a  smaller 
potentiometer setting.  

 
1. Humidity functions  

You  can  choose  between  single-stage,  dual-stage  and  continuous  humidity 
functions. The choice of the humidity function is technically bound to the allocation of 
timer functions to certain fan levels. 
 

Single-stage humidity function 

In  the  single-stage  humidity  function,  the  desired  dehumidification  stage  can  be 
preset.  The  fan  is  turned  on  at  the  stage  when  dehumidification  is  required.  This 
feature is set at the factory to ensure a speedy dehumidification.     

Dual-stage humidity function  

During dual-stage humidity function, the fan will turn on first to the stage with a lower 
speed. Once the humidity level reaches 10%, the fan will turn on to the higher stage 
and will remain on as long as the humidity remains above the threshold. It will turn 
back to the lower stage automatically after the humidity level comes back down to 
less than 10 percent. Switching between the stages should have a minimum runtime 
of 10 minutes. This function returns soft dehumidification to the humidity values over 
the  switching  on  threshold.  A  continued  rise  in  the  room’s  humidity  then  results  in 
strong dehumidification.   

Infinitely variable humidity function 

During  continuous  humidity  function  the  air  volume  is  automatically  controlled, 
depending  on  the  room’s  humidity.  When  the  humidity  increases,  the  fan  speed 
increases. This ensures continuously increasing dehumidification during slowly rising 
humidity.  It  is  useful  to  go  back  to  the  factory  setting  to  start  the  dehumidification 
even  at  a  low  level  of  humidity  in  the  room  (e.g.  left  stop  corresponds 
dehumidification from 40% RH, this corresponds to about 20% of the fan speed).       

 
2. Humidity Control 

The  electronics  detect  two  different  types  of  humidity  increases  in  the  air,  it 
distinguishes  between  a  slow  and  rapid  increase  of  moisture.  The  switch-on 
threshold is adjustable between 40% RH and 90% RH.  
 

High humidity (slower increase in humidity) 

For  slow  increase  in  humidity  (caused  possibly  by  washing,  drying  of  textiles, 
temperature lowering) the fan can be set above the threshold (factory setting is set to 
70% RH) and runs until the humidity has dropped by 10%.  
 

Summary of Contents for QT 150HT

Page 1: ...llation and Operating Instructions QuietAir 150mm Axial Fan MODEL QT 150HT TwoSpeed Fan 220 260m3 hr With Delay Start Automatic Humidity control and Timer Low Energy Quiet Long Life Extra Safe Delay S...

Page 2: ...rotection 2 3 Start up performance Chapter 3 SPECIFICATIONS DIMENSIONS 3 0 Specifications 3 1 Product lifetime 3 2 Accessories 3 3 Dimensions Chapter 4 FUNCTION 4 0 Function description Chapter 5 CLEA...

Page 3: ...d accident prevention regulations should be observed All electrical work and commissioning should be carried out by authorized and qualified electricians Maintenance and installation work should be ca...

Page 4: ...its intended purpose The product complies with the valid regulations and CE guidelines at the time of its production 1 5 Transport The fan is factory packed so that it is protected against normal tran...

Page 5: ...a this should conform to the local supply network On the test stand fan performance complied with DIN EN ISO 5801 1 10 Noise data The noise data which relate to distances is valid under free flow cond...

Page 6: ...ff the fan switch on inhibit activates the fan for 15 sec to protect the motor from rapid on off switching CHAPTER 3 SPECIFICATIONS DIMENSIONS M1 150 F 3 0 Specifications Impeller 137 Electrical suppl...

Page 7: ...is required This feature is set at the factory to ensure a speedy dehumidification Dual stage humidity function During dual stage humidity function the fan will turn on first to the stage with a lowe...

Page 8: ...ase reduction during the fan operation The reduction however hasn t been enough to fall below the turn off threshold Short stop time activated since it can be assumed that after a short break the humi...

Page 9: ...ng Safety instructions listed in Chapter 1 2 should be observed Before cleaning always ensure that the fan is isolated from the power supply and secured against restarting Clean cover protective guard...

Page 10: ...contamination of the ventilation unit After unpacking and before installation the following points must be checked if any transport damage is noticed broken or bent parts free rotation of the impelle...

Page 11: ...draft shutter and guide vane If required backdraft shutter included in delivery can be installed behind the guide vane Fig 6 During the housing installation the guide vane should be mounted vertically...

Page 12: ...t The wiring diagram SS 1082 which can be found on Page 16 should always be used to ensure proper wire placement Check sealing of the connection cables and cable wires clamp If mounted at the inlet sp...

Page 13: ...Safety instructions listed in Chapter 1 2 must be observed To guarantee the proper function of the fan the following should be checked regularly Appearance of dust or dirt in the housing on the motor...

Page 14: ...settings stage 1 approx 70 and stage 2 approx 100 The adjustment applies to both the demand ventilation as well as for the humidity control To ensure sufficient dehumidification speed is in automatic...

Page 15: ...s humidity function the air volume is automatically controlled depending on the room humidity When the humidity increases the fan speed increases This ensures continuously increasing dehumidification...

Page 16: ...round There is humidity decrease reduction during the fan operation The reduction however hasn t been enough to fall below the turn off threshold Short stop time activated since it can be assumed that...

Page 17: ...witches 3 and 4 6 10 15 21 minutes If you switch between stages the delay timer will be ignored By simultaneous shut down of the both stages applicable delay time can be ignored As always the technica...

Page 18: ...16 12 Schematic overview for QT150 HT Fig 14...

Page 19: ...the impeller doesn t run freely note possible causes of failure in Chapter 8 1 Bearing noise Vibrations see Chapter 8 1 Power consumption according to the specifications on the type plate see Chapter...

Page 20: ...r corrosion mechanical loading fatigue and or other effects that could not be directly discerned should be disposed in accordance with local and international laws and regulations The same applies to...

Page 21: ...ble electrical supply 3 Has not been subjected to issue neglect or damage 4 Has not been modified or repaired by any person not authorised by Airflow Developments Ltd 5 Has been installed in accordanc...

Page 22: ...ement by an assessed and registered Competent Person should follow a Best Practice process and adopt air flow measurement Method A The Unconditional Method using a suitable UKAS certified measuring in...

Reviews: