background image

12

Duplexvent

 Flexi-V 1500

Filter type

Flow rate (m

3

/h)

800

1000

1200

1500

1800

ISO
ePM1 55% (F7)

Initial pressure loss (Pa)

13

21

30

47

68

Final pressure loss (Pa)

200

200

200

200

200

ISO
ePM10 50% (M5)

Initial pressure loss (Pa)

2

4

5

8

11

Final pressure loss (Pa)

200

200

200

200

200

Duplexvent

 Flexi-V 2500

Filter type

Flow rate (m

3

/h)

800 1000 1500 2000

2200 2500

ISO
ePM1 55% (F7)

Initial pressure loss (Pa)

13

18

31

48

55

67

Final pressure loss (Pa)

200

200

200

200

200

200

ISO
ePM10 50% (M5)

Initial pressure loss (Pa)

3

4

8

12

15

18

Final pressure loss (Pa)

200

200

200

200

200

200

Duplexvent

 Flexi-V 3500

Filter type

Flow rate (m

3

/h)

1000 1500  2000  2500

3000 3500

ISO
ePM1 55% (F7)

Initial pressure loss (Pa)

10

13

24

30

47

64

Final pressure loss (Pa)

200

200

200

200

200

200

ISO
ePM10 50% (M5)

Initial pressure loss (Pa)

2

4

6

11

15

22

Final pressure loss (Pa)

200

200

200

200

200

200

Note: Values in the tables apply to external static pressure 200 Pa. Different pressure requirements
may result in a different situation. If needed, the detailed initial and final pressure loss data of the
filters are available on request from the supplier of the unit.

Make sure that the position of the label makes it possible to regularly inspect the values recorded.

Unscrew the rotating knob as much as possible to set zero on the scale (the bottom knob
identified by - +), then screw it back by approximately two full turns to have leeway to make
settings in both directions.

Unscrew the FILL plug (the top knob) and keep filling the machine with measuring liquid (included
in delivery) until the liquid is visible near the zero mark on the scale. Use the bottom knob to set
the value on the scale precisely to zero. Screw the top filling plug in.

After installing the manometers do not tilt the machine or the door (if they are installed on the
door). Measurement liquid might leak out.

4.9. 

Installing hot water heating coil

During the mechanical installation of the hot water air heater follow the manual supplied with this
optional accessory.

The supply (and top-up) water should fulfil especially the following criteria:

The water must be limpid and colourless.

The pH value of water must not be lower than 7. If water contains dissolved neutral salts its pH
value is to be between 8,5 and 9,5. Soda lye or trisodium phosphate (Na

3

PO

4

) can be used for

alkalinisation.

The content of carbon dioxide in an ion and non-ion form is to be as small as possible.

The 

remaining

supply water hardness

 should be lower than 7 mmol/l (at q < 23 kW/m2) and 5

mmol/l (at q > 23 kW/m2).

To soften the water, the following chemicals can be used: trisodium phosphate Na

3

PO

4

 or cation-

exchange resin (in case water is harder than 7 mmol/l; circuits with high volume of water; when
electrical boilers and radiation boilers are present).

The amount of

calcium ion

 in the water up to 3,5 mmol/l (at q < 23 kW/m2) and up to 1,8 mmol/l

(at q > 23 kW/m2).

All

CO

2

 up to 75 mg/l (at q < 23 kW/m2) and 10 mg/l (at q > 23 kW/m2).

Exact composition of top-up water is mentioned in the norm

Č

SN 07 7401

, in the annex, Table 1.

Summary of Contents for Duplexvent Flexi-V DV1800

Page 1: ...Installation use and maintenance manual Installation use and maintenance manual for Duplexvent Flexi V DV500 900 1800 2800 3500...

Page 2: ...h the design technical conditions specified by the manufacturer and applicable legislation and technical standards in effect The appliance may not be installed and operated in an aggressive environmen...

Page 3: ...12 4 10 Installing mixing valve of hot water air heater 13 4 11 Installing shut off dampers e1 i1 13 4 12 Installing flexible flanges 13 4 13 Installing and connecting water chiller to the cool sourc...

Page 4: ...esistance or it must be drained for the period during which outdoor temperature might fall below 5 C We recommend draining water from the chiller with pressurized air not using a gravity flow Applianc...

Page 5: ...wered fans with flexibly mounted engines a highly efficient heat recovery exchanger assembled from thin walled plastic boards for the recovery of heat cool a by pass damper slide out filters and drain...

Page 6: ...m is installed in ventilated rooms Duplexvent Flexi V units may only be used provided that it has been arranged via appropriate measures that the dew point will not be exceeded in the heat recovery ex...

Page 7: ...nel will display the message Orientation is not set 4 Proceed back to the default screen click on the cogwheel in the bottom left corner 5 Click on the Settings symbol in the top right corner 6 Enter...

Page 8: ...included in delivery 4 pieces in sizes 500 and 900 6 pcs in size 1800 2800 and 3500 Level the appliance horizontally on both longer and shorter side Use adjustable stand feet Adjustable bases must be...

Page 9: ...g must be firmly connected to extraction ports to achieve a uniform flow rate in the whole cross section of extraction ports A duct being at least 2 m long must be always connected to fan outlets to p...

Page 10: ...Filter with the class ISO ePM1 55 F7 is the filter of outdoor air and it is placed in the compartment e1 ODA Filter with the class ISO ePM10 50 M5 is the filter of extracted air and it is placed in th...

Page 11: ...o collection points on the unit s surface using tubes Connect the tube to the top of the manometer and run it to the metal bushing on the unit s surface also see a separate manometer installation manu...

Page 12: ...tings in both directions Unscrew the FILL plug the top knob and keep filling the machine with measuring liquid included in delivery until the liquid is visible near the zero mark on the scale Use the...

Page 13: ...tion SW of Duplexvent units tab Controls Wiring diagram 4 10 Installing mixing valve of hot water air heater During the mechanical installation and connection of the mixing valve of the hot water air...

Page 14: ...rained technician following the separate documentation set included The controls are described in a separate guide on operating the control system The unit is to be protected using a breaker with char...

Page 15: ...ommissioning if stricter hygienic requirements apply wiping disinfection must be carried out After disinfecting make sure that no toxicologically suspicious or odour active substances enter supply air...

Page 16: ...arameters including error messages Browse the unit s operational history Set e mail notification with Alarm or Warning messages for up to three e mail addresses You will find more information in the G...

Reviews: