SAFETY REQUIREMENTS 
 

The fan complies with the requirements according to the EU 
norms and directives. 
 
In case if a fan with the level of protection that corresponds to 
the second distinctive number IPX4 is used in humid conditions, 
it is necessary to provide additional protection in order to prevent 
moisture access.  Possible protection means: 
 
1.  If a fan is installed in a horizontal position, the duct length on 
 

both sides should be not less than 1m. 

 
2.  In any fan position it is necessary to install a cap on the 
 

suction branch tube. 

 
Precautions must be taken to avoid the black-flow of gases into 
the room from the open flue of fans or other open-fire 
appliances. 
 

NOTE: 

Installation and connection of the fan should be done by 

a qualified person in accordance with the IEE wiring regulations. 
 
Prior to connecting the fan to power supply, it is necessary to 
make sure that there is no visible faults on the rotor, case, grid 
and that there are no foreign items in air flow part of the case, 
which may damage rotor’s blades. 
 

CAUTION: 

Do not use the fan in highly explosive environment. 

Summary of Contents for AV200B

Page 1: ...INSTALLATION OPERATING INSTRUCTIONS AVENTA TURBO In Line Centrifugal Fans 9041425 AIRFLOW TM...

Page 2: ...nd other solid additives as well as sticky substances and fibre materials The temperature of ambient air should not be higher than the values indicated The fans are installed in horizontal and in vert...

Page 3: ...A B L E Weight kg AV100B 100 250 230 27 30 270 30 2 15 AV125B 125 250 217 27 30 270 30 2 2 AV150B 150 160 300 286 30 30 320 30 2 6 AV200B 200 340 280 30 30 354 40 4 0 AV250B 250 340 265 30 30 354 40...

Page 4: ...level dBa Ambient Temperature CO Protection AV100B 230 80 0 34 250 2820 46 25 55 IPX4 AV125B 230 79 0 34 355 2800 46 25 55 IPX4 AV150B 230 80 0 35 460 2725 46 25 55 IPX4 AV200B 230 107 0 47 780 2660...

Page 5: ...ess than 1m 2 In any fan position it is necessary to install a cap on the suction branch tube Precautions must be taken to avoid the black flow of gases into the room from the open flue of fans or oth...

Page 6: ...th not less than 3mm at all poles The fan is installed vertically or horizontally Direction of air charging is to comply with direction of arrow on the fan case To mount the fan on the wall or ceiling...

Page 7: ...alternating current power line It is good practise to provide a 3 amp fused spur isolator to isolate fan for maintenance or repair Figure 3 THE FAN IS COMPLETED WITH The complete set includes Fan 1 un...

Page 8: ...f rotor should be thoroughly cleaned every 6 months In order to do it release the screws 3 fig 1 and detach the grille 2 from the case 1 Use detergent dissolved in water to clean the rotor blades Avoi...

Page 9: ...Has not been subjected to misuse neglect or damage 4 Has not been modified or repaired by any person not authorised by Airflow Developments Ltd 5 Has been installed in accordance with Building Regula...