11
The unit must be secured against movement.
Ceiling-suspended position:
The appliance is suspended from anchors of sufficient load bearing capacity (provided by the
building contractor) using four (sizes 650, 1100, 1600 and 2600), and six (size 3600) suspension
eyes (included in delivery) with
Ø
11 mm holes.
Due to the condensate drain the appliance must be sloped toward section i2 (EHA), see the
picture
:
5.8. Connecting the condensate drain pipe
The unit is versatile and in total has 4 condensate outlets for 2 directions of air flow and 2
installation positions. A single specific condensate outlet is always used for a particular
application.
For the window position use the condensate outlet in section i2 (EHA)
ℎ
1
=
∆
10
+ 50 [
]
ℎ
2
=
∆
2 ∙ 10
+ 50 [
]
ℎ = 1,5
∆
10
+ 100 [
]
Δp – maximum positive / negative working pressure in the compartment of the unit. The height of
condensate drain pipe h = 15 cm is sufficient for all installations.
For the ceiling position use the condensate outlet in section i2 (EHA)