Airflow Instruments PAN300 Series Operation And Service Manual Download Page 6

iv

 

(This page intentionally left blank) 

 

Summary of Contents for PAN300 Series

Page 1: ...POSITIVE AND NEGATIVE DUCT ACCREDITATION PANDA SYSTEM AIRFLOW INSTRUMENTS MODEL PAN300 SERIES OPERATION AND SERVICE MANUAL P N 6005447 REV B MARCH 2021...

Page 2: ......

Page 3: ...ibration are not covered by this warranty f This warranty is VOID if the instrument is opened by anyone other than a factory authorized service center with the one exception where requirements set for...

Page 4: ...med to have accepted this LIMITATION OF WARRANTY AND LIABILITY which contains the complete and exclusive limited warranty of Seller This LIMITATION OF WARRANTY AND LIABILITY may not be amended modifie...

Page 5: ...ure 11 Measuring Duct Leakage Flow 12 Turning on the PAN300 Duct Leakage Tester 12 Using Leakage Test Application in the Model TA465 P 13 Troubleshooting Guide 16 APPENDIX A SPECIFICATIONS 17 APPENDIX...

Page 6: ...iv This page intentionally left blank...

Page 7: ...Incorporated TSI immediately The PANDA system consists of the following Qty Description Part Number Reference Picture 1 Low flow nozzle 6002598 1 Primary duct adapter spigot plus rubber bung to fit t...

Page 8: ...in 500 mm silicone tubes blue AFL9020005 1 16 ft 5 m silicone tube blue AFL9020005 1 Smoke cap holder assembly AFL71549801 1 Smoke pellets AFL9004167 1 K type thermocouple probe AFL82859201 3 Instrum...

Page 9: ...r supply using a 30 mA residual current device RCD or Ground Fault Circuit Interrupter GFCI It is IMPORTANT that the 110V PANDA yellow power socket be connected only to 110V to 120V supplies Connectin...

Page 10: ...4 Chapter 1 This page intentionally left blank...

Page 11: ...1 Select the section of the ductwork to be tested 2 Calculate the surface area of the ductwork of the section to be tested 3 Temporarily seal the all openings of the ductwork except one which will be...

Page 12: ...t to the vertical position to avoid damaging the cord 110 V 230 V Figure 1 110V and 230V Fan Speed Controllers NOTE The control pad on the Fan Speed Controller has been disabled Figure 2 Receptacle fo...

Page 13: ...Duct Adapter is open to the duct connect the 16 ft 5 m long blue silicone tube to it as shown in Figure 5 If the static pressure tap on the black Primary Duct Adapter is not open to the duct drill a...

Page 14: ...erify that the FLOW GRID MODE pressure taps on the inlet tubes are connected to the FLOW GRID pressure taps i e P1 to P1 and P2 to P2 b For positive pressure low flow testing add the low flow nozzle t...

Page 15: ...k square box Finally verify that the FLOW GRID MODE pressure taps on the inlet tubes are connected to the FLOW GRID pressure taps i e P1 to P1 and P2 to P2 d For negative pressure low flow testing add...

Page 16: ...10 Chapter 2 This page intentionally left blank...

Page 17: ...Model TA465 P Ventilation Meter to use these instruments in other applications If you do not have the manuals download them from TSI Incorporated s website www tsi com Measuring Duct Static Pressure 1...

Page 18: ...d speed by turning the Fan Speed Controller clockwise To decrease the fan speed turn the Fan Speed controller counter clockwise 1 Turn ON Model TA465 P 2 Zero the Model TA465 P pressure sensor with bo...

Page 19: ...the Model TA465 P 2 Use the keys to highlight the Applications item 3 Press the ENTER key to access the Applications menu MENU Zero Press Display Setup Settings Flow Setup Actual Std Setup Data Loggi...

Page 20: ...ilized select Run Test and press 4 The display will show the readings on the right Leakage Factor and Leak Rate will update in real time while other parameters will remain constant If the Leakage Fact...

Page 21: ...tic Pressure Flow Device Leakage Class Test Length Run Test LEAKAGE TEST Leakage Factor x xx Leak Limit x xx Leak Rate x xx Status OK Flow Device Flow Grid Baro Pressure 20 20 Temperature 20 C Time 9...

Page 22: ...eading on PVM620 is too low Required static pressure cannot be achieved with motor speed control settings at the maximum Leakage rate is too high Check for leaks using soap bubbles or smoke pallets Al...

Page 23: ...0 02 cfm Temperature Measurement TA465 P K Type thermocouple probe To EN60584 IEC 584 Barometric Pressure Measurement TA465 P Range 690 to 1 241 hPa 517 5 to 930 87 mm Hg 20 36 to 36 648 in Hg Accurac...

Page 24: ...18 Appendix A 0 500 1000 1500 2000 2500 3000 0 50 100 150 200 250 Static Pressure Pa Volume Flow l s PandaFan Performance Graph metric units...

Page 25: ...Specifications 19 0 1 2 3 4 5 6 7 8 9 10 11 0 50 100 150 200 250 300 350 400 450 500 Static Pressure ins wg Volume Flow CFM PandaFan Performance Graph imperial units...

Page 26: ...r the First Time It is IMPORTANT that the PANDA be connected to the power supply using a 30 mA residual current device RCD or Ground Fault Circuit Interrupter GFCI It is IMPORTANT that the 110V PANDA...

Page 27: ...BS EN 12237 2003 EU Ventilation for buildings Ductwork Strength and leakage of circular sheet metal ducts BS EN 1507 2006 EU Ventilation for buildings Sheet metal air ducts with rectangular section Re...

Page 28: ...h DW 143 uses units of l s m2 whereas others use m3 s m2 EN 1507 rectangular ductwork Air Tightness Class Air Leakage Limit fmax m3 s m2 Static Pressure Limit ps Pa Negative Positive at pressure class...

Page 29: ...A Practical Guide to Ductwork Leakage Testing Duct Pressure Class Static Pressure Limit Maximum Air Velocity m s Air leakage limits l s m2 Positive Pa Negative Pa Low pressure Class A 500 500 10 0 02...

Page 30: ...ressure during the test o Building and project reference o Design of installed ductwork including dimensions thickness of materials types of stiffening length type of duct tubes and fittings assembly...

Page 31: ...rve US Standards Ductwork classification and maximum air leakage Duct Class 1 2 inwg 3 inwg 4 6 10 inwg Seal Class C B A Sealing Applicable Transverse Joints Only Transverse Joints and Seams Joints Se...

Page 32: ...re 14 Allowable Air Duct Leakage from Rectangular Ducts per SMACNA Standard The SMACNA standard does not generally require correcting leakage flow rates to standard conditions unless 1 Air temperature...

Page 33: ...sychrometric chart 3 ACFM lb dry air minute humid volume ft3 lb dry air The SMACNA standard does not specify the information to be reported but instead defers to project documents However the SMACNA s...

Page 34: ...28 Appendix B This page intentionally left blank...

Page 35: ...29 Appendix C Typical Setup...

Page 36: ...30 Appendix C This page intentionally left blank...

Page 37: ...holds the wire coil When a smoke pellet is required to be used remove the bung and fit a pellet into the wire coil as shown in the sketch Light the pellet and immediately plug into the hole in the du...

Page 38: ...32 Appendix D This page intentionally left blank...

Page 39: ......

Page 40: ...Instruments Ltd Visit our website at www tsi com for more information UK Tel 44 149 4 459200 France Tel 33 1 41 19 21 99 Germany Tel 49 241 523030 P N 6005447 Rev B 2021 TSI Incorporated Printed in U...