Preparing PAN300 System for Air Duct Leak Testing
9
c. For negative pressure,
high-flow testing,
remove the low flow
nozzle if it is installed.
Then, connect the grey
cast aluminum cam
lock connector to the
inlet side of the blower
per Figure 8. Close
both cam lock arms at
the same time to
ensure proper fit.
Connect the free end of
Figure 8. Negative Pressure,
High-Flow Set-Up
the 16-ft (5-m) silicone
tube
to pressure tap marked
DUCT
PRESSURE P4 (-)
on the black square box.
Finally, verify that the
FLOW GRID MODE
pressure taps on
the inlet tubes are connected to the
FLOW GRID
pressure
taps, i.e.,
P1 (+)
to
P1 (+)
and
P2 (-)
to
P2 (-)
.
d. For negative pressure,
low-flow testing, add
the low-flow nozzle to
the blower inlet if it is
not installed. Then,
connect the grey cast
aluminum cam lock
connector to the low-
flow nozzle per
Figure 9.
Close both
cam lock arms at the
same time to ensure
proper fit.
Connect the free end of
Figure 9. Negative Pressure,
Low-Flow Set-Up
the 16-ft (5-m) silicone tube to pressure tap marked
DUCT
PRESSURE P4 (-)
on the black square box.
Fan
Inlet
Cam Lock
Connector
Fan
Inlet
Low Flow
Nozzle
Cam Lock
Connector
Summary of Contents for PAN300 Series
Page 2: ......
Page 6: ...iv This page intentionally left blank...
Page 10: ...4 Chapter 1 This page intentionally left blank...
Page 16: ...10 Chapter 2 This page intentionally left blank...
Page 34: ...28 Appendix B This page intentionally left blank...
Page 35: ...29 Appendix C Typical Setup...
Page 36: ...30 Appendix C This page intentionally left blank...
Page 38: ...32 Appendix D This page intentionally left blank...
Page 39: ......