ULTIMA REMOTE AIR COOLED
Chillers
26
Chillers
Installation & Maintenance : 6259535 IM E 02/2013
-
Controls
VIEWING UNIT OPERATING STATUS
Status Menu
Allows access to view operating status of Digital and Analogue Inputs and Outputs.
Using the
Navigation
instructions, the following
Sub-Menus
shown in sequence can
be accessed:
Digital Inputs
ID1
Phase Rotation (Optional) or MCCB status
ID2
Emergency Stop
ID3
Evaporator Flow Switch
ID4
Remote On/Off (Optional)
ID5
Compressor 1 Contactor Status
ID6
Compressor 2 Contactor Status
ID7
Compressor 3 Contactor Status
ID8
Compressor 4 Contactor Status
ID9
Circuit 1 Low Pressure Switch
ID10
Circuit 2 Low Pressure Switch
ID11
Pump 1 Contactor Status (Optional) or Remote Pump Interlock
ID12
Pump 2 Contactor Status (Optional)
ID13
Remote Pump On/Off (Optional)
ID14
Remote Summer/Winter Or Night Setback (Optional)
ID15
Not Used
ID16
Not Used
ID17
Compressor 5 Contactor Status
ID18
Compressor 6 Contactor Status
Analogue Inputs
Standard
B1
Circuit 1 Liquid Pressure
B2
Circuit 2 Liquid Pressure
B3
Circuit 1 Suction Pressure (Not connected with EEV option) or Leak Detector
B4
Return Water Temperature
B5
Supply Water Temperature
B6
Circuit 2 Suction Pressure (Not connected with EEV option) or Leak Detector
B7
Chilled Water Differential Pressure (Optional)
B8
Remote Setpoint Adjustment or Condenser Water Inlet
B9
Evaporator Inlet Water or Coil 1 Temperature
B10
Ambient or Coil 2 Temperature
Analogue Inputs
Fitted with Electronic Expansion Valve Option (EEV)
B1
Circuit 1 & Circuit 2 Suction Temperature
B3
Circuit 1 & Circuit 2 Suction Pressure
Digital Outputs
NO1
Compressor Contactor 1
NO2
Compressor Contactor 2
NO3
Pump 1 Contactor (Optional)
NO4
Compressor Contactor 3
NO5
Compressor Contactor 4
NO6
Pump 2 Contactor (Optional)
NO7
Circuit 1 Condenser Coil Valve 1
NO8
Circuit 1 Condenser Coil Valve 2
NO9
Circuit 2 Condenser Coil Valve 1
NO10
Circuit 2 Condenser Coil Valve 2
NO11
Not Used
NO12
Alarm Circuit 1
NO13
Alarm Circuit 2
NO14
Circuit 1 Reversing Valve
NO15
Circuit 2 Reversing Valve
NO16
Supplementary Heat
NO17
Compressor 5 Contactor
NO18
Compressor 6 Contactor
Analogue Outputs
Y1
Not Used
Y2
Circuit 1 & 2 Condenser Fan Speed Controller (Modulated Head Pressure Control)
Y3
Circuit 2 Condenser Fan Speed Controller (Modulated Head Pressure Control)