Chiller Technical Manual 7525371 V1.3.0_06_2019
Chillers
TurboChill™ R513A Air Cooled and FreeCool
Installation Data
Positioning
The installation position should be selected with the following points in mind:
●
Position on a stable and even base, levelled to ensure that the compressor operates correctly.
●
Levelling should be to ± 1°.
● Where vibration transmission to the building structure is possible, fit spring anti-vibration mounts and flexible
water connections.
● Observe airflow and maintenance clearances.
●
Pipe work and electrical connections are readily accessible.
●
Where multiple units are installed, due care should be taken to avoid the discharge air from each unit adversely
affecting other units in the vicinity.
●
Within a side enclosed installation, the fan MUST be higher than the enclosing structure.
● Increased airflow and maintenance clearances for side-enclosed or multiple unit applications.
●
Ensure there are no obstructions directly above the fans to prevent air recirculation.
Airflow & Maintenance Clearances
Application
Distance between Overall Base Dimension
Single unit
1300mm
Side-enclosed or multiple units
2600mm