* Feature required if unit is to be shut down for winter with water still circulating through unit, 

for freeze protection. The actuated suction ball valve is to stop liquid migration and protect the 

compressor.

CAUTION 

  

Introduction

14

Chiller Technical Manual 9635376 V1.3.0_06_2019

Chillers

TurboChill™ R513A Air Cooled and FreeCool

Unit Components

Refrigeration

Refrigeration

TCC

TCF

Compressors - Turbocor centrifugal

Dual maintainable pressure relief valves

Microchannel epoxy coated condensing coils

RTPF free cooling coils

-

Epoxy coated RTPF free cooling coils

-

Modulating starting line assembly

Filter driers with replaceable cores

Electronic expansion valves

Spray flooded evaporator

Full operating charge of R513A

Liquid and discharge shut off valves

Liquid line sight glasses (integral to EEV)

Micro-plate economiser

Actuated suction ball valve(s)*

Large capacity filter drier(s) with replaceable cores

Liquid line sight glasses

Low pressure switch with auto reset

2 High pressure switches with manual reset per compressor

High ambient starting valves

Suction and liquid pressure transducers

Discharge check (non return) valve(s)

 

 Standard features   

 Optional features  

 

 Feature not available

Summary of Contents for TCC11R04S-30

Page 1: ...Technical Manual TurboChill Air Cooled TCC and FreeCool TCF Chiller 200kW to 1650kW R513A Spray Evaporator ...

Page 2: ...this document The development of Airedale products and services is continuous and the information in this document may not be up to date It is important to check the current position with Airedale Ltd at the address stated This document is not part of a contract or licence unless expressly agreed No part of this document may be reproduced or transmitted in any form or by any means electronic or me...

Page 3: ...Conditions of Sale Warranty and Warranty Procedure available upon request Procedure When a component part fails a replacement part should be obtained through our Spares department If the part is considered to be under warranty the following details are required to process this requirement Full description of part required including Airedale s part number if known The original equipment serial numb...

Page 4: ...wable Pressure PS High Side 18 8 Barg Low side 10 3 Barg Based on the refrigerant temperature in the unit off state in the lowest permitted ambient temperature Based on the maximum allowable super heated refrigerant temperature Waterside AllowableTemperature Range TS Min 20 C to Max 40 C Maximum Allowable Pressure PS 10 0 Barg Based on the waterside temperature in the unit off state in the lowest ...

Page 5: ...nits without compressor enclosures are class A group 1 products and are only intended to be used at locations where there is a distance greater than 30m between the equipment and third party sensitive radio communication equipment CAUTION Electromagnetic Compatability EMC Protective Personal Equipment Airedale recommends that personal protective equipment is used whilst installing maintaining and ...

Page 6: ... be fitted to protect the compressor from liquid migration Free Cooling Chillers A minimum of 20 glycol concentration must be applied to all free cooling chillers Concentration should be increased so that its capable of protection at least 3K lower than the minimum operating ambient Flow Control Care to be taken when selecting a chiller within 5 of the evaporator minimum flow rate The end user mus...

Page 7: ...on 14 Turbocor Compressor 16 Condenser 17 Electrical 18 Condenser Fans 20 Waterside 21 Controls 25 Mechanical 29 Design Features Information 31 Specific Heat Capacity SHC 31 Minimum System Water Volume Calculations 31 Performance Effects of Glycol 33 Measurement of Sound Data 34 Pressure Relief Valve Discharge Piping 35 Water System 35 Standard Recommended Installation 35 Water Systems and Recomme...

Page 8: ...Centre of Gravity C of G 72 Point Loadings 74 Unit Lifting 78 Dimensions 80 Positioning 81 Airflow Maintenance Clearances 81 Anti Vibration Mounting Optional 82 Interconnecting Wiring 84 pLAN termination 85 Power Quality Harmonics 86 Pre Start Checks 87 pCO5 Built In Display and Keypad 88 Unit Operation 89 Restarting the Unit 89 Changing the Setpoint 90 Enabling Pumps 91 Maintenance 92 General Ins...

Page 9: ...Introduction 9 Chiller Technical Manual 9635376 V1 3 0_06_2019 Chillers TurboChill R513A Air Cooled and FreeCool Intentionally Blank ...

Page 10: ...ean Seasonal Energy Efficiency ratio Sound Levels Quiet R and Extra Quiet X Footprint For guidance the unit s information within this manual has been generated at nominal conditions due to the unit s ability to modulate capacity individually tailored unit solutions are available on request Please contact Airedale with your specific requirements and we will be pleased to provide you with an individ...

Page 11: ...the fan speed modulates in the conventional manner to maintain an optimised head pressure Free cooling is initiated wherever the outdoor ambient is 2K less than the return water temperature During concurent cooling mode the condensing temperature is constantly monitored and intelligently kept within the compressor envelope to allow the fans to run as fast as possible and therefore achieve the most...

Page 12: ...ser Fans High Airflow EC Condenser Fans No Discharge Plenum 300mm Fan Discharge Plenum 500mm Extended Height Fan Discharge Plenum Electrical Panel Single Point 3 Phase Isolation UltraCap Power Backup Control Panel Heater Panel Ventilation Emergency Stop Power Monitoring Weatherproof Rain Hood Controls Microprocessor Leak Detection Inteligent Head Pressure Control ...

Page 13: ...rator Actuated Suction Ball Valves Liquid and Discharge Shut Off Valves Liquid Line Sight Glasses Dual Pressure Relief Valves Micro Plate Economiser Coils Epoxy Coated Microchannel Condenser Coils RTPF FreeCooling Coils Waterside Differential Pressure Sensor Flow Switch Pump Interlock Water Filter Various Pump Options Immersion Heater Grooved and Clamped Type Connections ...

Page 14: ...ng coils RTPF free cooling coils Epoxy coated RTPF free cooling coils Modulating starting line assembly Filter driers with replaceable cores Electronic expansion valves Spray flooded evaporator Full operating charge of R513A Liquid and discharge shut off valves Liquid line sight glasses integral to EEV Micro plate economiser Actuated suction ball valve s Large capacity filter drier s with replacea...

Page 15: ...all be mounted on a rigid galvanised heavy duty sub frame Actuated Suction Ball Valve s To protect the compressors against liquid migration actuated suction line ball valves are fitted This protects the compressors when there is no cooling demand by keeping the refrigerant in the evaporator even if water is still flowing through the unit This option also allows partial pumpdown of the system refri...

Page 16: ...n is provided by a variable frequency drive Key benefits of Turbocor compressor technology Oil Free Operation More efficient heat exchange No oil entrainment issues pipe work can be optimised for performance not oil return Small and light only 120kg or 132kg compressor size dependant Turbocor compressor shaft and impellers levitate on a magnetic cushion eliminating friction and vibration resulting...

Page 17: ...ressure relief valve assembly shall be provided per evaporator circuit opening on pressure rise above 10 3 barg The dual shut off valve assembly incorporates 2 pressure relief valves which can be individually shut off via a 3 way valve This allows the maintenance of individual pressure relief valves without any requirement for refrigerant evacuation Rupture discs are also fitted on systems with a ...

Page 18: ...essure control Actuated suction shut off valve Power monitoring Individual mains power isolator for each compressor Separate electrical isolation for fans Single point isolation for connection of incoming 3 phase and earth mains power supply Emergency stop fitted to controls compartment door Circuit breakers for protection of all major unit components Phase rotation relay incorporating phase loss ...

Page 19: ...ing the latest Ultra Capacitor technology in external backup device for the EVD Evolution drivers and pCO controllers The module guarantees temporary power to the controller and drivers in the event of mains power failures The Ultra Capacitors are used to maintain the controller s main functions and to close the electronic valves in the event of mains power failures This avoids the need to install...

Page 20: ...nded vertical throw of air to reduce the chance of air re circulation As standard the enclosure is complete with an integral finger proof grille The fans offer maximum airflow performance while keeping sound levels to a minimum A mains EMC filter is fitted when the standard EC fan option is selected with the unit The filter is designed for convenient mains connection within the bus bar chamber The...

Page 21: ...water filter Pump hydronic options Grooved and clamped type connections Flanged connections Pump vibration eliminators Pump interlock Flow switch Differential pressure transducer Standard features Optional features Feature not available Each feature is a flow proving device and 2 out of the 3 should be fitted to any unit to validate warranty CAUTION options only available within units with suffici...

Page 22: ...rooved and Clamp Type Connections Grooved and clamp type connections shall be fitted to the unit Each feature is a flow proving device and 2 out of the 3 should be fitted to any unit to validate warranty CAUTION 1 2 3 Flanged Connections Flanged connections shall be fitted to the unit upon request excluding TCC evaporator only hydronic options Please contact Airedale Pump Vibration Eliminator Bell...

Page 23: ...hgear and isolating valve as standard Run standby pumps are rotated automatically to ensure even pump usage and prolong component life Pump AC Motor Fixed Speed Flow can be proven via the microprocessor display Factory fitted and supplied as standard complete with Differential pressure sensor Isolating valves Inlet strainer Vibration isolation Electrical switch gear Pump Inverter Driven Variable S...

Page 24: ...ass Options No bypass Comprises Shut off valves Filter Flushing bypass kit standard Comprises Shut off valves Filter Bypass leg with shut off valve Flushing bypass kit regulating Comprises Shut off valves Filter Bypass leg with double regulating valve Pump Configurations Single pump filter bypass flushing Comprises Single pump with vibration isolation Shut off valves Filter Bypass leg Single pump ...

Page 25: ... for viewing the unit operating status and making adjustments to control parameters by allowing the operator access to a series of display pages Also featured shall be a visual alarm and the facility to adjust and display control settings by local operator for information and control LCD Display ENTER Selects menus moves cursor to adjustable fields green LED UP DOWN KEYS To change adjustable field...

Page 26: ...through the keypad display The following conditions shall be detected triggering a visual display High compressor discharge temperature per compressor Low supply temperature Phase rotation Emergency stop Evaporator flow failure Low pressure safety switch Low suction pressure per compressor High liquid pressure Refrigerant leak detection Compressor 1 contactor status Compressor 2 contactor status d...

Page 27: ...ack set point for supply water temperature shall be selected to suit summer winter conditions or night setback Remote Set point Adjust Shall allow the chilled water set point to be adjusted via an external 0 10V signal Compressor Hours Run Displays hours run of each compressor Interactive Head Pressure Setpoint Management The combination of variable speed compressor EC fan and interactive control ...

Page 28: ... Terminal Unit with 8 bit encoding and error handling using 16 bit CRC Communication standard connection options of RS485 multipoint or RS232 point point Maximum Baud Rate of 19200 The data communication shall be asynchronous serial 8 data bits 2 stop bits and no parity in total 11 bits datum The data parameters from the controller shall be represented within Modbus registers each register contain...

Page 29: ...ls galvanised sheet steel with epoxy powder paint No discharge plenum 300mm height fan discharge plenum 500mm Extended height fan discharge plenum Anti vibration mounts spring or pad type Weatherproof rain hood Compressor enclosure Standard features Optional features Feature not available Lifting Lugs Lifting Lugs shall be fitted to the unit enabling full lifting requirements The lifting lug hole ...

Page 30: ...nit colour shall be Light Grey RAL 7035 The overall unit height when fitted with the optional 300mm discharge air plenum is 2800mm Extended Discharge Air Plenum Condenser Fan Site fitted and constructed from galvanised sheet steel coated with epoxy baked powder paint this plenum shall direct discharge air vertically as an aid to minimise air re circulation and also offers a degree of acoustic redu...

Page 31: ... 300 kW x Minimum Turndown x 1 2 Permanent Heat Load CLF Chiller loading factor Example 750kW output at 35 C Ambient and 7 12 C Water Permanent Heat Load 300kW Minimum Turndown 15 0 15 Factor 1 2 Vmin 750 x 60 x 2 x 750 x 0 15 x 1 2 1933 Litres 4 19 x 5 300 METHOD 2 Where the system permanent heat load is unknown where 750 x 3600 4 19 x 5 kW x 3600 Specific heat Capacity x Δt q water flow rate lit...

Page 32: ... rating conditions of 7 12 C water 35 C ambient The ESEER European Seasonal Energy Efficiency Ratio calculation method has been developed by Eurovent to give a single value that is a realistic indication of the efficiency of the chiller across the year round range of operation The ESEER value is calculated from the unit s performance at 20 25 30 and 35 C ambient temperatures for 25 50 75 and 100 l...

Page 33: ...23 C Output kW x 0 98 0 97 0 95 0 93 Compressor Input kW 0 99 0 98 0 96 0 95 Water Flow l s 0 99 1 02 1 04 1 07 Pressure Drop kPa 1 05 1 20 1 38 1 57 Propylene Glycol Nominal Correction Factors Glycol in System Freezing Point C 10 2 C 20 6 C 30 12 C 40 20 C Output kW x 0 97 0 95 0 91 0 88 Compressor Input kW 0 99 0 98 0 96 0 95 Water Flow l s 0 98 0 97 0 95 0 95 Pressure Drop kPa 1 08 1 17 1 31 1 ...

Page 34: ...igures obtained from test will be proven to not differ from the claimed figures by more than the allowable deviations specified in table 7 of section VII of Eurovent RS 6 C 003 2016 A weighted sound power 3dBA Acoustic data is representative of the unit running at the nominal duty and conditions under steady state operation Sound Directivity The global sound measurements quoted in the following ta...

Page 35: ...ller warranty CAUTION Full design water flow must be maintained at all times Variable water flow is not recommended and will invalidate warranty The correct operation of the flow proving device is critical if the chiller warranty is to be valid CAUTION Design Features Information Pressure Relief Valve Discharge Piping Considerations must be made when designing pipework for PRV venting This must be...

Page 36: ...balancing valves Pump Statement When installing circulating water pumps or equipment containing them the following rules should be applied Ensure the system is filled with water then vented and the pump primed with water before running the pump this is required because the pumped liquid cools the pump bearings and mechanical seal faces To avoid cavitation the NPSH Net Positive Suction Head incorpo...

Page 37: ...for flushing Bypass T2 Drain only present on 4 pass evaporators 2 air vents present on 4 pass evaporators 2 7 6 5 3 12 3 5 14 7 2 4 5 11 5 14 4 1 2 3 3 2 2 8 3 4 9 9 5 9 8 8 3 4 10 9 5 4 3 10 2 1 Evaporator 2 Automatic air vent 3 Drain 4 Butterfly shut off valve 5 Binder point 6 Filter 7 Flanged terminations option 8 Pump 9 AV mounts 10 Non return valve 11 Differential pressure transducer 12 Flow ...

Page 38: ...ass Evaporators 2 air vents present on 4 pass evaporators 11 4 2 14 3 5 3 2 14 6 7 7 12 3 4 4 14 15 3 3 2 2 5 16 2 5 3b 3b 5 5 13 5 5 5 Supply water Return water Optional flow switch Supplied loose 2 8 3 4 9 9 5 9 8 8 3 4 10 9 5 4 3 10 2 Pump Options 1 Evaporator 2 Automatic air vent 3 Drain 3b drain schrader point on free cool coils 4 Butterfly shut off valve 5 Binder point 6 Filter 7 Flanged ter...

Page 39: ...R08S 30 TCC11R06L 31 TCC11R08L 32 TCC11R10L 32 Capacity Cooling Duty Gross EC Fans 1 kW 225 245 255 365 395 420 Nom Input Cooling Only kW 69 70 70 128 134 141 EER 2 3 26 3 50 3 66 2 85 2 94 2 98 ESEER 3 4 50 5 05 5 32 4 76 4 88 5 06 Minimum Turndown Capacity Max 6 kW 156 52 0 149 49 6 77 25 8 122 30 5 119 29 8 118 29 4 Dimensions H 2800 x W 2200 Length mm 2626 3758 4890 3758 4890 6022 Machine Weig...

Page 40: ... 35 TCC12R14L 35 TCC12R16L 35 Capacity Cooling Duty Gross EC Fans 1 kW 435 465 560 625 700 745 Nom Input Cooling Only kW 138 142 193 211 242 259 EER 2 3 15 3 26 2 91 2 97 2 89 2 88 ESEER 3 4 54 4 73 4 95 4 77 4 85 4 94 Minimum Turndown Capacity Max 6 kW 77 12 9 75 12 5 118 14 7 117 14 6 116 14 5 115 14 4 Dimensions H 2800 x W 2200 Length mm 4890 6022 6022 7154 8286 9418 Machine Weight 7 kg 4645 51...

Page 41: ...22R16L 37 Capacity Cooling Duty Gross EC Fans 1 kW 790 435 465 625 700 745 Nom Input Cooling Only kW 283 135 138 200 226 241 EER 2 2 79 3 23 3 36 3 13 3 09 3 10 ESEER 3 4 94 4 30 4 67 4 27 4 53 4 75 Minimum Turndown Capacity Max 6 kW 115 14 3 88 14 7 84 14 0 122 15 3 121 15 1 119 14 9 Dimensions H 2800 x W 2200 Length mm 10550 4890 6022 7154 8286 9418 Machine Weight 7 kg 8345 4760 5390 6400 7030 7...

Page 42: ... TCC23R16L 39 Capacity Cooling Duty Gross EC Fans 1 kW 790 625 650 680 725 810 Nom Input Cooling Only kW 261 198 200 205 218 272 EER 2 3 03 3 15 3 25 3 32 3 33 2 98 ESEER 3 4 76 5 03 5 17 5 23 5 28 4 79 Minimum Turndown Capacity Max 6 kW 118 4 14 8 77 8 6 76 8 4 74 8 2 73 8 1 117 9 8 Dimensions H 2800 x W 2200 Length mm 10550 7154 8286 9418 10550 9418 Machine Weight 7 kg 8220 6880 7440 7850 8530 8...

Page 43: ... Capacity Cooling Duty Gross EC Fans 1 kW 835 895 800 835 1060 1080 Nom Input Cooling Only kW 273 290 249 255 360 360 EER 2 3 06 3 09 3 22 3 28 2 95 3 00 ESEER 3 4 91 5 04 5 18 5 23 5 01 5 08 Minimum Turndown Capacity Max 6 kW 117 9 7 116 9 7 76 6 3 75 6 2 117 7 3 117 7 3 Dimensions H 2800 x W 2200 Length mm 10550 11682 10550 11682 12814 13946 Machine Weight 7 kg 9270 10190 8910 9860 11360 11990 O...

Page 44: ...30 TCC11X08S 30 TCC11X06L 31 TCC11X08L 32 TCC11X10L 32 Capacity Cooling Duty Gross EC Fans 1 kW 195 215 225 300 315 330 Nom Input Cooling Only kW 58 57 57 95 90 90 EER 2 3 34 3 74 3 93 3 15 3 51 3 66 ESEER 3 4 67 5 16 5 45 4 72 5 09 5 32 Minimum Turndown Capacity Max 6 kW 81 27 1 78 25 8 122 40 7 120 29 9 118 29 4 78 19 4 Dimensions H 2800 x W 2200 Length mm 2626 3758 4890 3758 4890 6022 Machine W...

Page 45: ...12L 35 TCC12X14L 35 TCC12X16L 35 Capacity Cooling Duty Gross EC Fans 1 kW 355 380 500 570 600 635 Nom Input Cooling Only kW 107 107 167 182 183 190 EER 2 3 31 3 54 2 99 3 14 3 28 3 35 ESEER 3 5 18 5 31 4 96 5 29 5 35 5 31 Minimum Turndown Capacity Max 6 kW 75 12 5 118 19 6 117 14 6 116 14 5 115 14 4 115 14 3 Dimensions H 2800 x W 2200 Length mm 4890 6022 6022 7154 8286 9418 Machine Weight 7 kg 464...

Page 46: ...22X16L 37 Capacity Cooling Duty Gross EC Fans 1 kW 680 355 380 570 600 635 Nom Input Cooling Only kW 202 107 107 178 179 185 EER 2 3 36 3 32 3 55 3 20 3 36 3 44 ESEER 3 5 39 4 25 4 73 4 70 4 90 4 82 Minimum Turndown Capacity Max 6 kW 88 11 0 84 14 0 122 20 4 121 15 1 120 14 9 119 14 8 Dimensions H 2800 x W 2200 Length mm 10550 4890 6022 7154 8286 9418 Machine Weight 7 kg 8345 4760 5390 6400 7030 7...

Page 47: ...38 TCC23X16L 39 Capacity Cooling Duty Gross EC Fans 1 kW 680 570 590 610 640 740 Nom Input Cooling Only kW 196 178 175 174 179 243 EER 2 3 46 3 21 3 38 3 50 3 58 3 04 ESEER 3 4 97 5 18 5 36 5 45 5 54 5 10 Minimum Turndown Capacity Max 6 kW 78 9 7 76 8 5 74 8 2 73 8 1 117 13 0 117 9 7 Dimensions H 2800 x W 2200 Length mm 10550 7154 8286 9418 10550 9418 Machine Weight 7 kg 8220 6880 7440 7850 8530 8...

Page 48: ...24L 41 Capacity Cooling Duty Gross EC Fans 1 kW 760 800 700 735 1010 1040 Nom Input Cooling Only kW 239 245 208 213 334 334 EER 2 3 18 3 27 3 36 3 45 3 03 3 11 ESEER 3 5 14 5 25 5 50 5 54 5 23 5 29 Minimum Turndown Capacity Max 6 kW 116 9 7 76 6 3 75 6 2 117 9 8 117 7 3 71 4 5 Dimensions H 2800 x W 2200 Length mm 10550 11682 10550 11682 12814 13946 Machine Weight 7 kg 9270 10190 8910 9860 11360 11...

Page 49: ...ound Pressure 10m 59 56 55 51 53 48 48 49 57 TCC11R10L 32 Sound Power 89 87 86 83 85 79 80 81 89 Sound Pressure 10m 56 55 54 50 52 46 47 49 56 TCC12R08S 33 Sound Power 91 89 88 84 85 80 84 86 91 Sound Pressure 10m 59 56 55 51 52 48 52 53 59 TCC12R10S 33 Sound Power 89 87 87 83 84 79 84 86 90 Sound Pressure 10m 56 54 54 50 51 47 51 53 58 TCC12R10L 34 Sound Power 94 91 90 86 88 83 83 84 92 Sound Pre...

Page 50: ...ound Pressure 10m 59 57 56 53 53 49 53 55 60 TCC23R14S 38 Sound Power 90 89 88 84 85 81 86 88 92 Sound Pressure 10m 57 56 55 52 52 48 53 55 59 TCC23R16S 38 Sound Power 89 88 88 84 84 80 86 88 92 Sound Pressure 10m 56 55 55 51 52 48 53 55 59 TCC23R18S 38 Sound Power 88 87 87 84 84 80 86 88 92 Sound Pressure 10m 55 54 54 50 51 47 53 55 59 TCC23R16L 39 Sound Power 94 92 90 87 89 84 85 86 94 Sound Pre...

Page 51: ... 48 45 51 53 57 TCC12X10S 33 Sound Power 67 67 76 77 79 77 84 86 89 Sound Pressure 10m 54 53 50 48 48 45 51 53 57 TCC12X10L 34 Sound Power 63 63 68 79 84 79 83 84 89 Sound Pressure 10m 54 53 50 49 52 47 50 52 57 TCC12X12L 35 Sound Power 63 63 68 79 84 79 83 84 89 Sound Pressure 10m 55 54 50 49 52 47 50 52 57 TCC12X14L 35 Sound Power 63 63 68 79 84 79 83 84 89 Sound Pressure 10m 55 54 51 50 52 47 5...

Page 52: ... 49 47 53 55 58 TCC23X18S 38 Sound Power 89 88 85 83 83 80 86 88 91 Sound Pressure 10m 56 55 52 50 50 47 53 55 58 TCC23X16L 39 Sound Power 89 88 84 84 87 82 84 86 92 Sound Pressure 10m 56 55 51 51 54 49 51 53 59 TCC23X18L 39 Sound Power 89 88 85 84 87 82 84 86 92 Sound Pressure 10m 56 55 52 51 54 49 51 53 59 TCC23X20L 39 Sound Power 89 89 85 84 87 82 84 86 92 Sound Pressure 10m 56 55 52 51 54 49 5...

Page 53: ...C Fans 1 kW 260 280 365 400 405 440 Nom Input Cooling Only kW 72 75 118 131 120 134 EER 2 3 63 3 74 3 09 3 06 3 37 3 29 ESEER 3 4 74 4 96 4 40 4 57 4 82 4 60 Nominal Output Gross Free Cooling 4 kW 257 311 294 364 416 378 Ambient when Free Cooling 100 DX 5 C 1 8 3 3 1 4 0 6 2 3 0 3 Minimum Turndown Capacity Max 6 kW 71 23 7 71 23 8 123 30 7 120 30 0 118 29 5 73 12 1 Dimensions H 2800 x W 2200 Lengt...

Page 54: ...ly kW 134 139 211 221 235 256 EER 2 3 50 3 59 3 13 3 19 3 19 3 13 ESEER 3 4 74 4 98 4 59 4 70 4 74 4 73 Nominal Output Free Cooling 4 kW 444 505 567 639 709 780 Ambient when Free Cooling 100 DX 5 C 1 2 2 1 0 3 0 6 1 2 1 6 Minimum Turndown Capacity Max 6 kW 73 12 1 73 12 1 117 14 7 116 14 5 116 14 5 115 14 4 Dimensions H 2800 x W 2200 Length mm 6022 7154 7154 8286 9418 10550 Machine Weight 7 kg 649...

Page 55: ...07 238 200 EER 2 3 61 3 30 3 42 3 47 3 36 3 30 ESEER 3 4 47 4 21 4 42 4 61 4 57 4 58 Nominal Output Free Cooling 4 kW 439 567 629 697 780 567 Ambient when Free Cooling 100 DX 5 C 1 4 0 3 0 9 1 5 1 6 0 3 Minimum Turndown Capacity Max 6 kW 72 12 1 123 15 4 121 15 2 120 15 0 119 14 9 73 8 1 Dimensions H 2800 x W 2200 Length mm 6022 7154 8286 9418 10550 7154 Machine Weight 7 kg 6690 8400 9360 10270 11...

Page 56: ...ross EC Fans 1 kW 680 700 735 880 900 840 Nom Input Cooling Only kW 198 198 205 272 271 247 EER 2 3 43 3 53 3 58 3 24 3 33 3 40 ESEER 3 4 74 4 82 4 90 4 63 4 74 4 83 Nominal Output Free Cooling 4 kW 629 688 751 812 871 796 Ambient when Free Cooling 100 DX 5 C 0 9 1 8 2 3 0 8 1 5 1 2 Minimum Turndown Capacity Max 6 kW 73 8 1 72 8 0 73 8 1 117 9 8 117 9 7 73 6 1 Dimensions H 2800 x W 2200 Length mm ...

Page 57: ...lculations 9 Based on full load conditions and EC fans Pump electrical data is available from Airedale upon request Mechanical Data Notes Units TCF24R20S 52 TCF24R22L 41 TCF24R24L 41 Capacity Cooling Duty Gross EC Fans 1 kW 860 1035 1090 Nom Input Cooling Only kW 247 330 342 EER 2 3 48 3 14 3 19 ESEER 3 5 03 4 69 4 70 Nominal Output Free Cooling 4 kW 854 976 1049 Ambient when Free Cooling 100 DX 5...

Page 58: ...6 Capacity Cooling Duty Gross EC Fans 1 kW 225 240 280 335 345 365 Nom Input Cooling Only kW 59 60 86 100 94 105 EER 2 3 78 3 99 3 25 3 35 3 66 3 ESEER 3 4 80 5 06 4 32 4 67 4 90 4 87 Nominal Output Free Cooling 4 kW 210 259 224 290 340 297 12 Ambient when Free Cooling 100 DX 5 C 1 0 3 0 1 5 0 2 1 8 1 Minimum Turndown Capacity Max 6 kW 71 23 7 123 40 9 120 30 0 118 29 5 73 18 1 72 2 12 Dimensions ...

Page 59: ...1 kW 420 440 630 640 670 700 Nom Input Cooling Only kW 119 119 213 202 204 209 EER 2 3 53 3 70 2 95 3 17 3 28 3 34 ESEER 3 4 88 4 99 4 61 4 77 4 88 4 94 Nominal Output Free Cooling 4 kW 362 416 463 520 579 636 Ambient when Free Cooling 100 DX 5 C 0 2 1 2 3 0 1 2 0 2 0 6 Minimum Turndown Capacity Max 6 kW 73 12 1 117 19 5 116 14 5 116 14 5 115 14 4 72 9 0 Dimensions H 2800 x W 2200 Length mm 6022 7...

Page 60: ...70 700 630 Nom Input Cooling Only kW 116 202 191 192 196 201 EER 2 3 62 3 12 3 36 3 49 3 57 3 13 ESEER 3 4 43 4 01 4 40 4 57 4 67 4 58 Nominal Output Free Cooling 4 kW 362 463 520 579 636 463 Ambient when Free Cooling 100 DX 5 C 0 2 3 0 1 2 0 2 0 6 3 0 Minimum Turndown Capacity Max 6 kW 123 20 5 121 15 2 120 15 0 119 14 9 73 9 1 72 8 0 Dimensions H 2800 x W 2200 Length mm 6022 7154 8286 9418 10550...

Page 61: ...860 795 Nom Input Cooling Only kW 197 192 189 272 266 239 EER 2 3 33 3 50 3 62 3 10 3 24 3 33 ESEER 3 4 76 4 85 4 98 4 57 4 76 4 88 Nominal Output Free Cooling 4 kW 524 579 632 674 730 662 Ambient when Free Cooling 100 DX 5 C 1 5 0 2 0 8 1 5 0 5 0 8 Minimum Turndown Capacity Max 6 kW 72 8 0 73 8 1 117 13 0 117 9 7 12 72 6 0 Dimensions H 2800 x W 2200 Length mm 8286 9418 10550 10550 11682 10550 Mac...

Page 62: ... and EC fans Pump electrical data is available from Airedale upon request Mechanical Data Notes Units TCF24X20S 52 TCF24X22L 41 TCF24X24L 41 Capacity Cooling Duty Gross EC Fans 1 kW 815 955 1000 Nom Input Cooling Only kW 236 315 320 EER 2 3 45 3 03 3 12 ESEER 3 4 97 4 78 4 81 Nominal Output Free Cooling 4 kW 718 805 867 Ambient when Free Cooling 100 DX 5 C 0 1 0 6 0 1 Minimum Turndown Capacity Max...

Page 63: ...CF11R10L 45 Sound Power 87 86 85 82 84 78 80 81 88 Sound Pressure 10m 54 53 52 49 51 46 47 49 56 TCF12R08S 46 Sound Power 91 89 88 84 85 80 84 86 91 Sound Pressure 10m 59 56 55 51 52 48 52 53 59 TCF12R10S 34 Sound Power 88 87 86 82 83 79 84 86 90 Sound Pressure 10m 56 54 54 50 51 46 51 53 58 TCF12R12S 34 Sound Power 87 86 86 82 82 79 84 86 90 Sound Pressure 10m 54 53 53 49 50 46 51 53 57 TCF12R12L...

Page 64: ...ound Pressure 10m 60 58 57 53 54 49 53 55 60 TCF23R14S 50 Sound Power 91 89 88 85 85 81 86 88 92 Sound Pressure 10m 58 56 56 52 53 48 53 55 59 TCF23R16S 50 Sound Power 89 88 88 84 85 81 86 88 92 Sound Pressure 10m 56 55 55 51 52 48 53 55 59 TCF23R18S 50 Sound Power 88 87 87 83 84 80 86 88 92 Sound Pressure 10m 55 54 54 50 51 47 53 55 59 TCF23R18L 51 Sound Power 93 91 90 87 89 83 85 86 93 Sound Pre...

Page 65: ... TCF11X06L 43 Sound Power 84 83 79 79 82 77 80 81 87 Sound Pressure 10m 51 50 47 47 50 45 47 49 55 TCF11X08L 44 Sound Power 85 84 81 79 82 77 80 81 87 Sound Pressure 10m 52 51 48 47 50 45 47 49 55 TCF11X10L 45 Sound Power 86 85 82 80 82 77 80 81 87 Sound Pressure 10m 53 52 49 47 50 44 47 49 55 TCF12X08S 46 Sound Power 85 84 82 80 80 78 84 86 89 Sound Pressure 10m 52 52 49 47 48 45 51 53 57 TCF12X1...

Page 66: ...ound Pressure 10m 55 54 51 49 52 47 50 51 57 TCF22X18L 49 Sound Power 88 87 84 83 85 80 83 84 90 Sound Pressure 10m 55 54 51 50 52 47 50 51 57 TCF23X12S 50 Sound Power 87 86 83 81 82 79 86 88 91 Sound Pressure 10m 54 53 51 49 49 47 53 55 58 TCF23X14S 50 Sound Power 87 86 84 82 82 79 86 88 91 Sound Pressure 10m 54 54 51 49 49 47 53 55 58 TCF23X16S 50 Sound Power 88 87 84 82 82 79 86 88 91 Sound Pre...

Page 67: ...ata Evaporator Pressure Drop 100 Water 36 37 38 39 40 41 48 49 50 51 52 0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 Pressure Drop kPa Flow Rate l s 36 37 38 39 40 41 48 49 50 51 52 30 31 32 33 34 35 42 43 44 45 46 47 0 20 40 60 80 100 120 140 160 0 20 40 60 80 100 Pressure Drop kPa Flow Rate l s 30 31 32 33 34 35 42 43 44 45 46 47 ...

Page 68: ...porator Pressure Drop 20 Ethylene Glycol 36 37 38 39 40 41 48 49 50 51 52 0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 120 140 Pressure Drop kPa Flow Rate l s 36 37 38 39 40 41 48 49 50 51 52 30 31 32 33 34 35 42 43 44 45 46 47 0 20 40 60 80 100 120 140 160 180 0 20 40 60 80 100 Pressure Drop kPa Flow Rate l s 30 31 32 33 34 35 42 43 44 45 46 47 ...

Page 69: ...ronic Data Strainer Pressure Drop 100 Water Strainer Pressure Drop 20 Ethylene Glycol 0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 Pressure Drop kPa Flow Rate l s 5 6 8 4 0 20 40 60 80 100 120 140 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 Pressure Drop kPa Flow Rate l s 5 6 8 4 ...

Page 70: ...35 7490 7735 4310 1130 TCC12R18L 35 8345 8605 4930 1130 TCC22R08S 36 4760 4900 2340 1150 TCC22R10S 36 5390 5530 2710 1150 TCC22R12L 37 6400 6610 3070 1140 TCC22R14L 37 7030 7240 3760 1130 TCC22R16L 37 7790 8010 4280 1130 TCC22R18L 37 8220 8440 4800 1130 TCC23R12S 38 6880 7110 3240 1160 TCC23R14S 38 7440 7670 3890 1150 TCC23R16S 38 7850 8080 4240 1150 TCC23R18S 38 8530 8760 4940 1140 TCC23R16L 39 8...

Page 71: ...2 4805 4945 2730 1120 TCC12X08S 33 4645 4810 2360 1160 TCC12X10S 33 5190 5350 2750 1150 TCC12X10L 34 5290 5480 2750 1150 TCC12X12L 35 6325 6565 3130 1140 TCC12X14L 35 7110 7355 3600 1130 TCC12X16L 35 7490 7735 4310 1130 TCC12X18L 35 8345 8605 4930 1130 TCC22X08S 36 4760 4900 2340 1150 TCC22X10S 36 5390 5530 2710 1150 TCC22X12L 37 6400 6610 3070 1140 TCC22X14L 37 7030 7240 3760 1130 TCC22X16L 37 77...

Page 72: ...2R16L 47 9730 11060 4570 1100 TCF12R18L 47 10735 12195 5260 1090 TCF22R10S 48 6690 7330 2810 1090 TCF22R12L 49 8400 9310 3220 1070 TCF22R14L 49 9360 10450 3960 1060 TCF22R16L 49 10270 11440 4460 1060 TCF22R18L 49 11080 12370 5000 1050 TCF23R12S 50 8780 9700 3380 1080 TCF23R14S 50 9690 10710 4040 1080 TCF23R16S 50 10400 11570 4440 1070 TCF23R18S 50 11220 12450 5090 1070 TCF23R18L 51 12310 13720 513...

Page 73: ... 7385 8255 3230 1120 TCF12X12L 47 8140 9205 3240 1120 TCF12X14L 47 9065 10295 3890 1100 TCF12X16L 47 9730 11060 4570 1100 TCF12X18L 47 10735 12195 5260 1090 TCF22X10S 48 6690 7330 2810 1090 TCF22X12L 49 8400 9310 3220 1070 TCF22X14L 49 9360 10450 3960 1060 TCF22X16L 49 10270 11440 4460 1060 TCF22X18L 49 11080 12370 5000 1050 TCF23X12S 50 8780 9700 3380 1080 TCF23X14S 50 9690 10710 4040 1080 TCF23X...

Page 74: ...8S 36 655 605 575 485 705 685 655 530 TCC22R10S 36 750 710 635 540 815 795 705 580 TCC22R12L 37 920 875 770 625 975 945 835 660 TCC22R14L 37 855 785 705 615 545 895 835 760 665 575 TCC22R16L 37 875 840 800 730 650 910 890 855 780 680 TCC22R18L 37 800 745 710 670 615 565 825 785 750 715 660 595 TCC23R12S 38 860 890 870 740 950 1005 975 815 TCC23R14S 38 810 790 755 680 610 890 885 850 750 650 TCC23R...

Page 75: ...8S 36 655 605 575 485 705 685 655 530 TCC22X10S 36 750 710 635 540 815 795 705 580 TCC22X12L 37 920 875 770 625 975 945 835 660 TCC22X14L 37 855 785 705 615 545 895 835 760 665 575 TCC22X16L 37 875 840 800 730 650 910 890 855 780 680 TCC22X18L 37 800 745 710 670 615 565 825 785 750 715 660 595 TCC23X12S 38 860 890 870 740 950 1005 975 815 TCC23X14S 38 810 790 755 680 610 890 885 850 750 650 TCC23X...

Page 76: ...70 965 820 965 980 920 775 TCF22R12L 49 1195 1275 1270 1040 1195 1225 1160 945 TCF22R14L 49 1125 1155 1150 1070 930 1100 1090 1045 950 830 TCF22R16L 49 1160 1210 1275 1240 1065 1130 1150 1155 1095 955 TCF22R18L 49 1075 1090 1120 1140 1075 950 1040 1030 1025 1015 950 855 TCF23R12S 50 1100 1265 1360 1205 1140 1255 1275 1100 TCF23R14S 50 1065 1130 1180 1115 980 1085 1120 1115 1020 895 TCF23R16S 50 11...

Page 77: ...70 965 820 965 980 920 775 TCF22X12L 49 1195 1275 1270 1040 1195 1225 1160 945 TCF22X14L 49 1125 1155 1150 1070 930 1100 1090 1045 950 830 TCF22X16L 49 1160 1210 1275 1240 1065 1130 1150 1155 1095 955 TCF22X18L 49 1075 1090 1120 1140 1075 950 1040 1030 1025 1015 950 855 TCF23X12S 50 1100 1265 1360 1205 1140 1255 1275 1100 TCF23X14S 50 1065 1130 1180 1115 980 1085 1120 1115 1020 895 TCF23X16S 50 11...

Page 78: ... of lifting the whole chiller Use the appropriate spreader bars lifting slings with the holes lugs provided Lift the unit slowly and evenly If the unit is dropped it should immediately be checked for damage and reported to Airedale Allow free space abovethe fans to prevent air recirculation Lifting Dimensions 4 Point A A Number of Fans Lifting Lug Size A mm 4 35 1533 6 35 2332 8 35 3464 10 35 4077...

Page 79: ... Data Lifting Dimensions 8 Point B 5 0 0 0 m m A 60 A 60 A B A 2300 Number of Fans Lifting Lug Size Single Circuit Machines Dual Circuit Machines A mm B mm A mm B mm 12 35 3600 1536 3600 1490 14 35 4500 1536 4500 1536 16 35 4300 3100 4300 3100 18 35 5500 2800 5200 2968 20 35 6500 3164 6500 3139 22 35 6650 3966 24 35 6650 4950 ...

Page 80: ...0 500 2626 6 Fan mm 2200 2800 300 500 3758 8 Fan mm 2200 2800 300 500 4890 10 Fan mm 2200 2800 300 500 6022 12 Fan mm 2200 2800 300 500 7154 14 Fan mm 2200 2800 300 500 8286 16 Fan mm 2200 2800 300 500 9418 18 Fan mm 2200 2800 300 500 10550 20 Fan mm 2200 2800 300 500 11682 22 Fan mm 2200 2800 300 500 12814 24 Fan mm 2200 2800 300 500 13946 Contact Airedale for detailed general arrangement drawing...

Page 81: ...ctions Observe airflow and maintenance clearances Pipe work and electrical connections are readily accessible Where multiple units are installed due care should be taken to avoid the discharge air from each unit adversely affecting other units in the vicinity Within a side enclosed installation the fan MUST be higher than the enclosing structure Increased airflow and maintenance clearances for sid...

Page 82: ...th the mount with the largest deflection adjust the height of each mount using the levelling screw 3 Mountings must be adjusted incrementally in turn 8 Do not fully adjust 1 mount at a time as this may overload and damage springs 9 When all mounts are level lock each into place using the levelling lock nut 4 10 Lock all retaining nuts 6a and 6b to the extreme ends of the retaining studs 5 2 1 6a 5...

Page 83: ...Anti Vibration mount is larger than the unit base Consideration must be made with regard to steelwork concrete plinth sizes Full information is available on the approved General Arrangement drawings The base of the unit is open Considerations must be made for service and maintenance requirements if the unit is installed on a gantry AV Mount Overhang Support Steelwork ...

Page 84: ... regulations British standards and IEC requirements The control voltage to the interlocks is 24V always size the low voltage interlock and protection cabling for a maximum voltage drop of 2V Avoid large voltage drops on cable runs particularly low voltage wiring A fused and isolated electrical supply of the appropriate phase frequency and voltage should be installed Wires should be capable of carr...

Page 85: ...s TurboChill R513A Air Cooled and FreeCool The plugged termination ensures that the connections are made simultaniously Failure to attached the cables this way may cause damage to the controller CAUTION RxTx RxTx GND RxTx RxTx GND Panel Side Customer Side pLAN termination ...

Page 86: ...tage problems Excessive currents in neutral conductor The 3rd 5th 7th and 9th harmonics are considered to be the predominant frequencies produced by non linear loads To minimize the harmonic effect each Turbocor compressor is fitted with a 5 line reactor to help reduce the harmonics and improve the displacement power factor above 0 95 1 However to further reduce the effects and to help meet limits...

Page 87: ...S Visual Inspection Check that the unit is of satisfactory condition and that it has not been damaged A damaged component could indicate a reason why the unit is not operating for example a refrigerant leak etc Electrical Overloads Check that circuit breakers are all turned on If not investigate why they have tripped This could be the reason why the unit has turned off If the unit is operated with...

Page 88: ...RM red LED indicates alarm present 6 8 ROW LCD DISPLAY 7 CURSOR FLASHING Top left position HOME indicates adjustable fields Monitoring The microprocessor also monitors and displays the following measured parameters Supply water temperature C Return water temperature C Suction pressure of each circuit Barg Liquid pressure of each circuit Barg Suction temperature at each circuit C Subcool for each c...

Page 89: ... turn the unit on press the key to enter the program menu Using the or keys select the Unit On Off option and press When is pressed the above screen will be shown To turn the unit on simply press the key again and the screen will change Once the screen has changed to the above press the key which will return back to the main screen The chiller will be going through its start up sequence Pressing w...

Page 90: ...owing screen will be shown Using the or button scroll to the password screen Enter the password 4648 using the and keys and press after each number is entered The numbers start at 5555 So down one to 4 up one to 6 etc When the final number is entered the screen will jump to the set point adjustment screen To adjust the set point press the key to highlight the set point using the and keys enter the...

Page 91: ... Status Quick Menu Main Menu Alarm Log 43 5Hz 1234rpm 1 0A Status 43 5Hz Run OK 1 0 Navigates from one menu to another When the menu is changed the display shown will always be the top display of the new menu Navigates up and down in the individual menu On green The pump is running or has stopped by a stop function If flashing the pump has been stopped by the user CUE menu external start stop or b...

Page 92: ... should be inhibited primed and touched up with matching paint Check for excess vibration from other rotating equipment Clean Microchannel condenser coil Ensure no debris has collected under compressor housing if fitted Service Tools Test Equipment Touch up paint Stiff brush Safety Equipment Safety glasses goggles Procedures Coil Cleaning To clean micro channel condenser coils use detergent and a ...

Page 93: ...it from the fan to a PC The kit comprises of a USB to RS232 9 pin D type adapter This should be installed on the PC with the software supplied with the kit The COM port of the USB to RS232 adapter should be assigned to a free COM port between COM 1 and 4 via the system device manager Connect the RS232 to RS485 interface converter to the USB port of your PC via the USB to RS232 serial interface lea...

Page 94: ... 7 Barg HP limiting function 15 0 Barg 1 5 Barg differential Task Frequency Refrigeration 3 Mths 12 Mths 60 Mths Compare the following and compare results with commissioning records Suction liquid and discharge pressures Refrigeration system temperatures suction liquid and discharge Record superheat and sub cooling temperatures Check each circuit sight glass for dryness and bubbles for indication ...

Page 95: ... effects of glycol in the system are taken into account flow rate and pressure drop Input into the controller the reduced pressure drop kPa value normally 80 of design flow rate Once this value is programmed into the controller the water flow rate can be reduced to verify that the low flow alarm is activated Ensure that the tubes connected to the sensor are trace heated and insulated Flow Switch A...

Page 96: ...t Head pressure differential Bar Minimum suction pressure Barg Supply water set point Summer Day C Supply water set point Winter Night C Minimum supply water temperature C Task Frequency Controls 3 Mths 12 Mths 60 Mths Change controller battery The controller will keep the strategy for a short period of time with no battery Service Tools Test Equipment Small terminal screwdriver Safety Equipment E...

Page 97: ...ed to indicate The condition of the refrigerant in the system Lack of refrigerant Moisture content of the refrigerant The colour of the sight glass depends on the moisture content of the refrigerant The recommended moisture levels of a system should be below 75ppm An indication of green dry are to be considered as perfect conditions meaning full protection by the filter drier against effects from ...

Page 98: ...rtator inlet outlet water temperatures C Fixed outlet A 100 35 12 7 B 93 25 7 C 87 15 7 D 80 5 7 EU 2016 2281 Table 22 Rating Point T1 C Part load ratio Outdoor air dry bulb temperature C Fan coil application inlet outlet water temperature C Cooling floor application inlet outlet water temperatures C Fixed outlet Variable outlet A 35 100 35 12 7 12 7 23 18 B 30 74 30 7 8 5 18 C 25 47 25 7 10 18 D ...

Page 99: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 225 0 245 0 255 0 365 0 395 0 420 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 224 7 244 7 254 7 364 7 394 6 419 5 Declared EERd 35 C 3 21 3 45 3 60 2 83 2 90 2 93 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 165 5 180 2 187 6 268 6 290 6 309 0 Declared EERd 30 C 4 14 4 41 4 63 3 96 4 22 4 36 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 106 3 115 7 120 4 1...

Page 100: ... Rated Cooling Capacity Prated c 2 4 5 kW 435 0 465 0 560 0 625 0 700 0 745 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 434 6 464 6 559 5 624 6 699 5 744 4 Declared EERd 35 C 3 11 3 22 2 88 2 94 2 86 2 85 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 320 1 342 2 412 2 460 1 515 3 548 4 Declared EERd 30 C 4 01 4 21 3 91 3 85 3 94 4 02 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 205 7 219 8 264 8 29...

Page 101: ... Rated Cooling Capacity Prated c 2 4 5 kW 790 0 435 0 465 0 625 0 700 0 745 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 789 4 434 6 464 6 624 6 699 5 744 4 Declared EERd 35 C 2 76 3 19 3 32 3 10 3 06 3 06 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 581 5 320 1 342 2 460 1 515 3 548 4 Declared EERd 30 C 4 09 4 09 4 30 4 01 4 12 4 22 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 373 6 205 7 219 8 29...

Page 102: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 790 0 625 0 650 0 680 0 725 0 810 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 789 4 624 6 649 5 679 5 724 5 809 5 Declared EERd 35 C 2 99 3 12 3 22 3 28 3 29 2 95 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 581 5 460 1 478 5 500 6 533 7 596 4 Declared EERd 30 C 4 31 4 19 4 32 4 32 4 33 4 08 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 373 6 295 6 307 4 3...

Page 103: ...2021 Rated Cooling Capacity Prated c 2 4 5 kW 835 0 895 0 800 0 835 0 1060 0 1080 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 834 5 894 4 799 5 834 5 1059 4 1079 4 Declared EERd 35 C 3 03 3 06 3 19 3 24 2 92 2 98 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 614 8 658 9 589 0 614 7 780 5 795 2 Declared EERd 30 C 4 20 4 24 4 23 4 25 4 16 4 20 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 395 0 423 4 ...

Page 104: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 195 0 215 0 225 0 300 0 315 0 330 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 194 7 214 6 224 7 299 7 314 7 329 7 Declared EERd 35 C 3 30 3 69 3 87 3 13 3 47 3 62 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 143 4 158 0 165 5 220 7 231 8 242 8 Declared EERd 30 C 4 28 4 68 4 95 4 17 4 48 4 69 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 104 8 101 5 106 3 1...

Page 105: ... Rated Cooling Capacity Prated c 2 4 5 kW 355 0 380 0 500 0 570 0 600 0 635 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 354 7 379 7 187 8 569 6 599 6 634 6 Declared EERd 35 C 3 28 3 50 3 52 3 11 3 25 3 32 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 261 3 279 7 368 0 419 6 441 7 467 4 Declared EERd 30 C 4 61 4 67 3 78 4 29 4 28 4 34 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 167 8 179 7 236 5 26...

Page 106: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 680 0 355 0 380 0 570 0 600 0 635 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 679 5 354 7 379 7 569 6 599 6 634 6 Declared EERd 35 C 3 32 3 29 3 51 3 18 3 33 3 40 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 500 6 261 3 279 7 419 6 441 7 467 4 Declared EERd 30 C 4 42 3 44 4 44 4 13 4 29 4 41 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 321 6 167 8 179 7 2...

Page 107: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 680 0 570 0 590 0 610 0 640 0 740 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 679 5 569 6 589 6 609 6 639 5 739 6 Declared EERd 35 C 3 42 3 18 3 34 3 47 3 54 3 02 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 500 6 419 6 434 3 449 1 471 1 544 8 Declared EERd 30 C 4 51 4 33 4 54 4 57 4 67 4 16 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 321 6 269 6 279 1 2...

Page 108: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 760 0 800 0 700 0 735 0 1010 0 1040 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 759 6 799 5 699 6 734 5 1009 5 1039 4 Declared EERd 35 C 3 15 3 24 3 33 3 41 3 00 3 09 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 559 6 589 0 515 4 541 1 743 7 765 8 Declared EERd 30 C 4 38 4 51 4 67 4 67 4 44 4 46 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 359 6 378 5 331...

Page 109: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 260 0 280 0 365 0 400 0 405 0 440 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 259 5 279 5 364 4 399 4 404 4 439 3 Declared EERd 35 C 3 23 3 29 2 72 2 66 2 94 2 98 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 191 1 205 8 268 3 294 1 297 8 323 5 Declared EERd 30 C 4 28 4 50 3 75 3 97 4 25 3 83 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 122 7 132 1 172 3 1...

Page 110: ...21 Rated Cooling Capacity Prated c 2 4 5 kW 470 0 500 0 660 0 705 0 750 0 800 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 469 3 499 3 659 2 704 2 749 1 799 1 Declared EERd 35 C 3 16 3 21 2 83 2 85 2 83 2 73 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 345 6 367 7 485 5 518 7 551 8 588 6 Declared EERd 30 C 4 08 4 14 3 73 3 85 3 94 4 01 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 221 9 236 1 311 8 ...

Page 111: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 460 0 660 0 680 0 720 0 800 0 660 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 459 3 659 2 679 2 719 2 799 1 659 2 Declared EERd 35 C 3 24 2 94 3 04 3 06 2 90 2 99 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 338 3 485 5 500 3 529 7 588 6 485 5 Declared EERd 30 C 4 14 3 83 3 99 4 10 4 15 3 94 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 217 2 311 8 321 3 3...

Page 112: ...21 Rated Cooling Capacity Prated c 2 4 5 kW 680 0 700 0 735 0 880 0 900 0 840 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 679 2 699 2 734 2 879 2 899 2 839 2 Declared EERd 35 C 3 10 3 18 3 21 2 95 3 02 3 10 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 500 3 515 0 540 8 647 6 662 3 618 1 Declared EERd 30 C 4 09 4 11 4 16 4 01 4 13 4 04 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 321 3 330 8 347 3 ...

Page 113: ...0 1090 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 859 2 1034 1 1089 1 Declared EERd 35 C 3 17 2 88 2 92 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 632 9 761 7 802 2 Declared EERd 30 C 4 12 4 08 4 04 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 406 6 489 4 515 4 Declared EERd 25 C 5 88 5 57 5 62 Declared Cooling Capacity 20 C Pdc 2 3 5 kW 180 2 217 0 228 5 Declared EERd 20 C 6 90 6 38 6 38 Sound...

Page 114: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 225 0 240 0 280 0 335 0 345 0 365 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 224 6 239 6 279 6 334 5 344 5 364 5 Declared EERd 35 C 3 41 3 58 2 95 2 99 3 26 2 97 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 165 4 176 4 205 9 246 4 253 7 268 4 Declared EERd 30 C 4 37 4 62 3 86 4 08 4 33 4 17 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 106 2 113 3 139 3 1...

Page 115: ... Rated Cooling Capacity Prated c 2 4 5 kW 420 0 440 0 630 0 640 0 670 0 700 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 419 4 439 4 629 2 639 3 669 2 699 2 Declared EERd 35 C 3 20 3 35 2 66 2 85 2 94 2 97 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 308 9 323 6 463 5 470 8 492 9 515 0 Declared EERd 30 C 4 12 4 29 3 70 3 88 3 99 4 08 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 198 3 207 8 297 7 30...

Page 116: ...1 Rated Cooling Capacity Prated c 2 4 5 kW 420 0 630 0 640 0 670 0 700 0 630 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 419 4 629 2 639 3 669 2 699 2 629 2 Declared EERd 35 C 3 25 2 78 2 99 3 09 3 14 2 84 Declared Cooling Capacity 30 C Pdc 2 3 5 kW 308 9 463 5 470 8 492 9 515 0 463 5 Declared EERd 30 C 4 16 3 81 4 00 4 12 4 22 3 87 Declared Cooling Capacity 25 C Pdc 2 3 5 kW 198 4 297 7 302 4 3...

Page 117: ...C C 6 39 6 60 6 76 6 32 6 50 6 52 Declared Refrigerant Capacity PD 1 3 5 kW 523 2 535 2 547 2 675 2 687 2 635 2 Declared Power Input DD kW 33 5 34 7 35 2 44 0 43 9 50 3 Declared EERDC D 15 62 15 41 15 54 15 36 15 66 12 62 SSCEE 2 3 5 2 0 2 0 2 1 1 9 2 0 2 0 SSCEE Tier Tier 2 2021 Tier 2 2021 Tier 2 2021 Tier 2 2021 Tier 2 2021 Tier 2 2021 Rated Cooling Capacity Prated c 2 4 5 kW 655 0 670 0 685 0 ...

Page 118: ...Declared Power Input DC kW 105 7 130 9 135 4 Declared EERDC C 6 68 6 32 6 39 Declared Refrigerant Capacity PD 1 3 5 kW 651 2 763 1 799 1 Declared Power Input DD kW 56 5 50 3 55 8 Declared EERDC D 11 52 15 18 14 33 SSCEE 2 3 5 2 0 1 9 2 0 SSCEE Tier Tier 2 2021 Tier 2 2021 Tier 2 2021 Rated Cooling Capacity Prated c 2 4 5 kW 815 0 955 0 1000 0 Declared Cooling Capacity 35 C Pdc 2 3 5 kW 814 2 954 1...

Page 119: ...ls a replacement part should be obtained through our Spares department If the part is considered to be under warranty the following details are required to process this requirement Full description of part required including Airedale s part number if known The original equipment serial number An appropriate purchase order number A spares order will be raised under our warranty system and the repla...

Page 120: ...Ecodesign 120 Chiller Technical Manual 9635376 V1 0 0_01_2019 Chillers TurboChill R513A Air Cooled and FreeCool ...

Page 121: ...Ecodesign 121 Chiller Technical Manual 9635376 V1 0 0_01_2019 Chillers TurboChill R513A Air Cooled and FreeCool ...

Page 122: ...iredale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY Tel 44 0 113 2391000 Fax 44 0 113 2507219 E mail enquiries airedale com Web www airedale com TM_TURBOCHILL_TCC_TCF_R513A_9635376_09_2019 ...

Reviews: