Technical Data
Ecodesign
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2018.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2018.
(5) All performance data based upon standard waterside configuration.
Notes: Units
TCF24X20S-52
TCF24X22L-41
TCF24X24L-41
SEPR
1,3,5
7.7
8.0
8.0
SEPR Tier
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Annual Electricity Consumption
kWh/a
786395.2
880205.0
929162.9
Rated Refrigerant Capacity P
A
1,3,5
kW
814.2
954.1
999.1
Rated Power Input D
A
kW
259.4
356.2
369.0
Rated EER
DC,A
3.14
2.68
2.71
Declared Refrigerant Capacity P
B
1,3,5
kW
759.9
890.5
932.5
Declared Power Input D
B
kW
168.0
216.9
221.9
Declared EER
DC,B
4.52
4.10
4.20
Declared Refrigerant Capacity P
C
1,3,5
kW
705.6
826.8
865.8
Declared Power Input D
C
kW
105.7
130.9
135.4
Declared EER
DC,C
6.68
6.32
6.39
Declared Refrigerant Capacity P
D
1,3,5
kW
651.2
763.1
799.1
Declared Power Input D
D
kW
56.5
50.3
55.8
Declared EER
DC,D
11.52
15.18
14.33
SSCEE
2,3,5
%
2.0
1.9
2.0
SSCEE Tier
Tier 2
(2021)
Tier 2
(2021)
Tier 2
(2021)
Rated Cooling Capacity P
rated,c
2,4,5
kW
815.0
955.0
1000.0
Declared Cooling Capacity 35°C Pdc 2,3,5
kW
814.2
954.1
999.1
Declared EER
d
35°C
3.14
2.68
2.71
Declared Cooling Capacity 30°C Pdc 2,3,5
kW
599.8
702.8
736.0
Declared EER
d
30°C
4.15
4.24
4.23
Declared Cooling Capacity 25°C Pdc 2,3,5
kW
385.3
451.5
472.8
Declared EER
d
25°C
5.95
5.64
5.70
Declared Cooling Capacity 20°C Pdc 2,3,5
kW
170.8
200.2
209.6
Declared EER
d
20°C
7.02
6.56
6.59
Sound Power Level
dB(A)
92
93
93
Air Volume
m³/h
279880
307868
335856
Off mode P
OFF
kW
0.427
0.427
0.427
Thermostat-off mode P
TO
kW
3.937
5.241
5.695
Standby Mode P
SB
kW
0.739
0.749
0.759
Crankcase heater mode P
CK
kW
0.000
0.000
0.000
Ec
od
esi
gn
118
Chiller Technical Manual 9635376 V1.0.0_01_2019