Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
87
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data – X2C0 Continued
SC25D067-X2C0-0
SC25D073-X2C0-0
SC25D080-X2C0-0
Standard Condenser Match
1 x CR105
1 x CR105
1 x CR105
Unit Data Full Function- X2C0
Nominal Run Amps
A
88.6
90
93.8
Maximum Start Amps
A
232.3
227.3
266.3
Recommended Mains Fuse Size
A
100
100
125
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Unit Data Cooling Only – X2C0
Nominal Run Amps
A
62.80
65.68
73.38
Maximum Start Amps
A
206.6
203
245.9
Recommended Mains Fuse Size
A
80
80
100
Evaporator Fan Motor - Per Fan
Motor Type
AC
AC
AC
Quantity x Motor Size
kW
3 x 2.38
3 x 2.38
3 x 2.38
Full Load Amps
A
5
5
5
Locked Rotor Amps
A
17.5
17.5
17.5
Compressor 1 , Circuit 1
Motor Size
kW
10.86
12.15
13.73
Nominal Run Amps
A
19.2
20.7
24.5
Locked Rotor Amps
A
163
158
197
Type of Start
Direct On Line
Compressor 2, Circuit 1
Motor Size
kW
10.86
12.15
13.73
Nominal Run Amps
A
19.2
20.7
24.5
Locked Rotor Amps
A
163
158
197
Type of Start
Direct On Line
Standard Condenser Match - AC Motor Per Fan
Quantity x Motor Size
kW
3 x 0.6
3 x 0.6
3 x 0.6
Full Load Amps
A
2.62
2.62
2.62
OPTIONAL EXTRAS
Electric Heating
Number of stage of Reheat
3
3
3
Number of Elements
9
9
9
Rating (Total)
kW
31.5
31.5
31.5
Current Per Phase
A
45.47
45.47
45.47
Humidifier
Capacity
kg/hr
15
15
15
Rating
kW
11.25
11.25
11.25
Full Load Amps
A
16.2
16.2
16.2
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
3 x 2.2
3 x 2.2
3 x 2.2
Full Load Amps
A
3.3
3.3
3.3
Locked Rotor Amps
A
3.3
3.3
3.3
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
3 x 3.1
3 x 3.1
3 x 3.1
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
4.8
Standard Condenser Match - EC Motor-Per Fan
Quantity x Motor Size
kW
3 x 0.73
3 x 0.73
3 x 0.73
Full Load Amps
A
3.3
3.3
3.3
Condenser Match - SCAF Fan
Quantity x Motor Size
kW
3 x 1.4
3 x 1.4
3 x 1.4
Full Load Amps
A
6
6
6
(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
X
2
C