Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data – X2X2
SC19D055-X2X2
SC19D070-X2X2
SC19D080-X2X2
Standard Condenser Match -
2 x CR50
2 x CR65
2 x CR65
Unit Data Full Function- X2X2
(1)
Nominal Run Amps
A
63
74.6
82.1
Maximum Start Amps
A
124.5
150.2
168.9
Recommended Mains Fuse Size
A
80
100
100
Max Mains Incoming Cable Size
mm²
70
70
70
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Unit Data Cooling only – X2X2
Nominal Run Amps
A
46.8
58.4
65.9
Maximum Start Amps
A
108.3
134
152.7
Recommended Mains Fuse Size
A
63
80
80
Evaporator Fan - Motor - Per Fan
Motor Type
EC
EC
EC
Quantity x Motor Size
(2)
kW
2 x 2.2
2 x 2.2
2 x 2.2
Full Load Amps
A
3.3
3.3
3.3
Locked Rotor Amps
A
3.3
3.3
3.3
Compressor 1 , Circuit 1 & 2
(3)
Motor Size
kW
4.6
5.6
6.3
Nominal Run Amps
A
8.5
11.4
13.3
Locked Rotor Amps
A
70
87
100
Type of Start
Direct On Line
Compressor 2, Circuit 1 & 2
(3)
Motor Size
kW
4.6
5.6
6.3
Nominal Run Amps
A
8.5
11.4
13.3
Locked Rotor Amps
A
70
87
100
Type of Start
Direct On Line
Standard Condenser Match – AC Motor Per Fan
Quantity x Motor Size
kW
2 x 0.6
2 x 0.6
2 x 0.6
Full Load Amps
A
2.62
2.62
2.62
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
2
2
2
Number of Elements
6
6
6
Rating (Total)
kW
21
21
21
Current Per Phase
A
30.31
30.31
30.31
Humidifier
Capacity
kg/hr
15
15
15
Rating
kW
11.25
11.25
11.25
Full Load Amps
A
16.2
16.2
16.2
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
2 x 3.1
2 x 3.1
2 x 3.1
Full Load Amps
A
4.8
4.8
4.8
Locked Rotor Amps
A
4.8
4.8
4.8
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size
kW
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Standard Condenser Match - EC Motor-Per Fan
Quantity x Motor Size
kW
2 x 0.73
2 x 0.73
2 x 0.73
Full Load Amps
A
3.3
3.3
3.3
SCAF Condenser Match - Motor - Per Fan
Quantity x Motor Size
kW
2 x 1.4
2 x 1.4
2 x 1.4
Full Load Amps
A
6
6
6
(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
X
2