507206-01
Page 48 of 59
Issue 1337
9. Replace the heating compartment access panel.
10. Turn on all electrical power to the unit.
11. Set the thermostat to desired setting.
NOTE:
When unit is initially started, steps 1 through 11 may
need to be repeated to purge air from gas line.
12. If the appliance will not operate, follow the instructions
“Turning Off Gas to Unit” and call your service technician
or gas supplier.
Turning Off Gas to Unit
1. Set the thermostat to the lowest setting.
2. Turn off all electrical power to the unit if service is to be
performed.
3. Remove the heating compartment access panel.
4. Move gas valve switch to
OFF.
5. Replace the heating compartment access panel.
Gas Pressure Adjustment
Gas Flow (Approximate)
Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for
two
revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.)
Divide by two
and compare to time in
Table 16. If manifold pressure matches Table 15 and rate
is incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.
NOTE:
To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
A pressure post on the inlet side of the gas valve
provides access to the supply pressure. Back out the
3/32 Hex screw one turn, connect a piece of 5/16”
tubing and connect a manometer to measure supply
pressure.
NOTE:
Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to re-tighten
the 3/32 Hex screw.
Manifold Pressure Measurement
1. A manifold post located on the gas valve provides
access to the manifold pressure. See Figure 57. Back
out the 3/32 Hex screw one turn, connect a piece of
5/16” tubing and connect to a manometer to measure
manifold pressure.
2. Start unit and allow 5 minutes for unit to reach steady
state.
3. While waiting for the unit to stabilize, observe the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue.
4. After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in Table
17.
NOTE:
Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to re-tighten
the 3/32 Hex screw.
Figure 56
Gas Valve Shown In “ON’ Position
GAS METER CLOCKING CHART
Model
Seconds for One Revolution
Natural
LP
1 cu ft Dial
2 cu ft Dial
1 cu ft Dial
2 cu ft Dial
045
80
160
200
400
070
55
110
136
272
090
41
82
102
204
110
33
66
82
164
Natural - 1000 btu/cu ft LP- 2500 btu/cu ft
Table 16
Summary of Contents for 95G2DFE
Page 3: ...507206 01 Page 3 of 59 Issue 1337 Figure 1 ...
Page 17: ...507206 01 Page 17 of 59 Issue 1337 A95DF2E 95G2DFE Table 7A ...
Page 18: ...507206 01 Page 18 of 59 Issue 1337 A95DF2E 95G2DFE Table 7B ...
Page 19: ...507206 01 Page 19 of 59 Issue 1337 A95DF2E 95G2DFE Table 7C ...
Page 27: ...507206 01 Page 27 of 59 Issue 1337 Figure 32 ...
Page 34: ...507206 01 Page 34 of 59 Issue 1337 Figure 48 TRAP DRAIN ASSEMBLY USING 1 2 PVC or 3 4 PVC ...
Page 36: ...507206 01 Page 36 of 59 Issue 1337 Figure 50 Table 10 ...
Page 40: ...507206 01 Page 40 of 59 Issue 1337 TYPICAL WIRING DIAGRAM Figure 54 ...
Page 56: ...507206 01 Page 56 of 59 Issue 1337 Start UP Performance Check List ...